Tender For Repair Replacement Of Lightening Protection Aviation Light Earthling Air Termination Rod In High Rise Building At Cheering Enclave Under Ge North Delhi Cantt10, Delhi-Delhi
TDR : 54151029
Tender Notice
BOQ
19 Days Left
Delhi
Delhi
Tender For Repair Replacement Of Lightening Protection Aviation Light Earthling Air Termination Rod In High Rise Building At Cheering Enclave Under Ge North Delhi Cantt10
Name of Work: REPAIR/ REPLACEMENT OF LIGHTENING PROTECTION, AVIATION LIGHT, EARTHLING, AIR TERMINATION ROD IN HIGH RISE BUILDING AT CHEERING ENCLAVE UNDER GE (NORTH) DELHI CANTT-10
Sl. No.
Item Description
1
Supply and fix in replacement Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductorsand down conductors above the ground level
2
Supply and fix in replacementGI strip 32x6mm burried in ground as earthing loop
3
Supply and fix in replacement single pointed air termination aluminium rod 12 mm dia ,300 mm long.
4
M&L for earthing with copper steel earth plate electrode 60cm x 60cm x 3.15mm thick buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer ofcharcoal dust and common salt filling in alternate layers and electrode connections by usingcopper strip of size 20mm x 3mm as earthing leadupto the body ofthe equipment by means ofbolts, nuts, check nuts and washers made of copperand thimbles and protected by light grade 40mm diaGI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:3:6type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type ofsoil, returning, filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 ofSSR 2009 (Part-I) complete all as specified and as directed.Note:- On testing after completion if the desired earth resistance is not obtained the earthing will be be redone without any extra cost.
5
Test point Terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 nos, 8mm dia, 25mm long hex head screw complete all as directed
6
Supply and fix GI pipe 20mm bore light grade
7
Providing cement contrete inblock form roof kerbs or mud stops rounged or chamfered on edges of size150x150x300 mm type B1 1:2:4 (20 mm graded aggregate) all as specified and directed.
8
S&F LED Based outdoor weatherproof Aviation Obstruction Lighthing with inbuilt AC-DC convertor 48V/160-230 VAC housed in Die-Cast Aluminium (LM 6)/Aviation Orange Finish Ultra violet stablised Acrylic lens for directing light built in photo controller / Buit in SS Bird Spike Soild State high flux light Emitting Diode/Intensity: 32.5 Candelas, IP rating: IP-65, Life:>500000 Hrs/Sealed with EPDM Gasket power supply: AC-DC converter 48V/160-320 VAC standards: confirms to ICAO Annex 14-6, FAA AC No. 70/7460-IG, Radio Interference: BS 800/EN 55014 Connections, necessary welding, clamping, mounting with 32 mm dia GI pioe, 1.2 mtr height, 1.5 sqmm copper wire with 20 mm PVC conduit fixing on work portions upto nine storeys height bldg. incl taking down unsv complete