| 1 | Taking out non clog sewage submersible pumpincluding electric motor of capacity 10HP& 20 HP, 3 phase, 415 Volts, disconnecting all electrical & machanical connection, dismantling the motor and pump, cutting out the burnt/old/unservecible moulded winding, cleaning the slots with non greasy materials, replacing with moulded copper reassembling pump & motor after making it serviceable by means of repair/ rewinding of pump ormotor or both and lowering/ fixing in its orignal position and testing complete all asspecified and directed.Note:-(i)The cost of bush &necessary T&P required for taking out, dismantling and lowering deemed to be included in quoted rates.(ii)Parts required for replacement or rewinding of motors shall be paid seperatly under respective item.(iii)The contractor shall carryout the functionality/ serviceable test of submersible pump & motors before and after the lowering . Cost of the same shall deemed to be included in quoted rates.(iv) Cost of transportation if any shall also deemed to be included in the qupted rates. (v) If the winding of motor is burnt and needs rewinding, then burnt winding shall be cut in the presence of GE/AGE concern. |
| 2 | S&F in repair for following parts to be replaced under item No. 01 above:- |
| 3 | Winding of motor, 10 HP, 3 phase 415 boths with and included super enamelled copper winding wire with \"F\" class insulation |
| 4 | Winding of motor, 20HP, 3 phase 415 boths with and included super enamelled copper winding wire with \"F\" class insulation |
| 5 | Bearing of suitable for 10 HP motor |
| 6 | Bearing of suitable for 20 HP motor |
| 7 | Impeller mechine seal for10HP motor |
| 8 | Impeller mechine seal for 20 HP motor |
| 9 | M&L for taking out Induction electric motor 20/25 HP, 3 phase ,415 Volts after disconnecting all electrical ,transporting to workshop & machanical connection including dismantling the motor, cutting the burnt/old/unserveciblewinding and cleaning the slots with non greasy materials and replacing with super enamelledcopperwinding wire of existing guageincluding repalcement of unserviceable parts such as DE and NDE bearing, fan blade and reassemblingand refixing on the foundation and testing after making all electric connection complete all asspecified and directed. |
| 10 | M&L for taking out Induction electric motor 7.5/10 HP, 3 phase ,415 Volts, disconnecting all electrical & machanical connection, dismantling the motor,cleaning the slots with non greasy materials and replacing with super enamelledcopperwinding wire of existing guageincluding repalcement of unserviceable parts such as DE and NDE bearing, fan blade and reassemblingand refixing on the foundation and testing after making all electric connection complete all asspecified and directed. |
| 11 | Taking out centrifugal pump suitable for 7.5/10 HP, 3 phase, 415 Volts after dismantlingall the connection and transporting to workshopfor repairing pump by replacing with and including unserveciable partsand reinstalling in true alignment, making all electrical and machenical and testing complete all asspecified and directed.Note:- Parts required for replacement or rewinding of motors shall be paid seperatly under respective item. |
| 12 | S&F in repair for following part to be replaced in above item:- |
| 13 | Bearing of size upto 7.5 HP |
| 14 | Bearing of size upto10 HP |
| 15 | Bush of size upto 7.5 HP |
| 16 | Bush of size upto 10 HP |
| 17 | Impeller of size upto 7.5 HP |
| 18 | Impeller of size upto10 HP |
| 19 | Gland packing |
| 20 | Gland -I bolts |
| 21 | MS Coupling |
| 22 | Star coupling |
| 23 | Water seal |
| 24 | Gasket |
| 25 | Studs |
| 26 | Supply & Fix 3 Pole Power Contactor MNX 9 having coil 240V, 50/50 Hz AC3 Rating, up to 500 V including taking down old U/S complete all as specified and directed. |
| 27 | Supply & Fix 3 Pole Power Contactor MNX 32 having coil 240V, 50/50 Hz AC3 Rating, up to 500 V including taking down old U/S complete all as specified and directed. |
| 28 | S&F Panel relay 3 phase 415 V MNF of range as suitable for 5 to 20 HP motor complete all as specified and directed. |
| 29 | S&F Panel connector 2/4 pole 3 phase 415 V of range as suitable for 5 to 20 HP motor complete all as specified and directed. |
| 30 | Supply and mixing water disinfectant containing 65% to 70% chlorine contents (calcuim based granular disinfectant for water treatment, packed in 45 Kg plastic drum of approved make complete all as specified and directed. |
| 31 | Supply and mixing Poly Aluminium Chloride (PAC 01) Grade 29% for water treatment plant, packed in plastic drum/PE bags of make as approved by GEcomplete all as specified and directed andby Engineer-in-charge. |
| 32 | Supply and mixing white Polyelectrolyte (PE) powder Cationic/Anionic for water treatment plant, packed in plastic drum/PE bags of make as approved by GEcomplete all as specified and directed andby engr-in-charge. |
| 33 | Supply and mixing water disinfectant containing 10% to 15% chlorine contents (Calcuim based granular/ powder disinfectant for water treatment) complete all as specified and directed andby engr-in-charge. |
| 34 | Supply and mixing Aluminum sulfate (Alum) suitable for flocculation as specified & directed by engineer in charge |
| 35 | Taking down chemical dosing pump, single phase 230Volts 50 Hzs of capacity1.5 gln to 4.75 glns/hrs suitable for 70 mtr head range complete all asspecified and directed. |
| 36 | S&F in repair/replacement for following part in item:- |
| 37 | FRP tank of existing cap |
| 38 | SS agitator shaft including motor |
| 39 | Skid/tank mounted |
| 40 | Pump maint kit |
| 41 | Level switch |
| 42 | Flow controlvalve |
| 43 | Control panel |
| 44 | M&L periodical servicing of diesel engine driven Gen set 3 phase 415 volts 50 c/s AC supply by cleaning thoroughly and replacing fuel filters, air filters, oil filters draining out engine oil etc. and replacing with new oil, tightening of all gaskets, connection of battery terminals, electric cable connections foundation bolts, coupling bolts etc including test running and tappet setting of alternator by checking and setting of voltage and frequency all as directed by Engr-in-Charge.Make of DG SET : Kirloskar/Crompton / CumminsMake of filters : Kirloskar/Crompton/ Fleet guard/ MICO.Note: Engine oil, Fuel filters, Air filters, Oil filters replaced will be measured and paid separately under respective item of BoQ for following capacities of DG set. |
| 45 | 125 KVA DG SET |
| 46 | 40 KVA DG SET |
| 47 | M&L for coolant radicool SFO premix of Castrol or equivalent of TVS/Volvoline |
| 48 | M&L for drain out the old used engine oil from sump of DG sets, cleaning & refilling with new engine oil 15 W 40 up to required level including topup.Make: Castrol/HP or equivalent of Servo |
| 49 | Supply only Diesel filter suitable for 40/125 KVA DG set |
| 50 | Supply only Lub Oil filter suitable for 40/125 KVA DG set |
| 51 | Supply only Air filter suitable for 40/125 KVA DG set |
| 52 | Labour for cutting/pruning of tree branches along security light pole around 2mtr radius of security light fitting and removing from site including arrangement of T&P (i.e. Axe, rope & ladder etc) complete all asspecified and directed. |
| 53 | Disconnecting & dismentling of damaged/unsv cable any type/ make and supply & laying (in repair) cable PVC insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor using lugs/ferrul bothe end of cable and testing complete all asspecified and directed for following size:- |
| 54 | 10 Sqmm 2 Core |
| 55 | 16 Sqmm2 Core |
| 56 | 10 Sqmm 4 Core |
| 57 | 16 Sqmm 4 Core |
| 58 | Excavation in trenches in soft/loose soil not exceeding 1.5 M wide and not exceeding 1.5 Mtr deep and getting out including filling bottom surface to required level or slope for laying of pipes/ cables complete all as specified and directed.Note :-For the digging of soil , JCB machinewill not be allow at site, it will be done by labour only andcontractor will beresponsibleto repairthe existing cable , pcc plinth etc without extra costwhich will be damaged during execution of work. |
| 59 | Removing excavated surplus soil not exceeding 50 mtr and depositing where directed ata level not exceeding 1.5mtr above the starting point complete all as specified and directed. |
| 60 | Returning filling including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft soil complete all as specified and directed. |
| 61 | Supply and laying dry well burnt locally available brick sub class \"B\" old sizebricks laid flat with width equal to the length of whole bricks over cable as cable protection complete all as specified and directed. |
| 62 | M&L for sand cushioning with dry local Ganga sand for cable protecting underground cable (8 cm before laying the cable and 15 cm after laying the cable) in trenches including punning the sand upto 18 cm thick and consolidated complete all as specified and directed.Note :Punned thickness18 cm shall be measured only. |
| 63 | S&F aluminium thimbles cables lugs for cables of size 10 to 35 Sqmm including necessary crimping wirh crimping tool complete all as specified and directed. |
| 64 | M&L in replacement for 40mm bore gi tubing light grade with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including taking down existing pipe complete all as specified and directed. |
| 65 | S&F in repair cable junction box shock & rust proof of external dimension 230mm x 170mm x 105 mmincluding provision of 4 way heavy duty PVC insulated connector of suitable size including all fixing arrangements complete all as specified and directed. MAKE: Sintex cat No. GSJB-2014 or equivalent inLegrand/Havells. |
| 66 | S&F in repair service cable un armouredof size 6 sqmm 2 core,1100 volts grade,heavy duty cable with PVC insulated solidaluminium conductor served with an inner sheathing of PVC tape and overall PVCsheathed including taking down old/ unserviceble service wire complete all as specified and directed. |
| 67 | S&F in repairservice cable un armouredof size 10 sqmm 2 core,1100 volts grade,heavy duty cable with PVC insulated solidaluminium conductor served with an inner sheathing of PVC tape and overall PVCsheathed including taking down old/ unserviceble service wire complete all as specified and directed. |
| 68 | Taking down existing non functional security/ street light fittings from pole/ wall/ pipe of any type of LED fitting of any wattage for repairingincluding replacement/ unserviceable accessories like SPD, LED Driver etc & refixingthe same with & including connecting cable of 3 core PVC sheathed Aluminium conductor not less than 4 Sqmm from light fitting to cable looping box & tightening of brackets, clamp by nut, bolts and washerincludingtesting, complete all as specified and directed. NOTE : (i) Replacement and fixing of unserviceable component etc required will be measured & paid separately under respective items of this schedule as S&F in repair here under.(ii) Fitting shall be connected with existing electric wire / cable, in case of existing wire / cable found unserviceable same shall be measured and paid in relevent items.(iii) Any type of Ladder or arrangement for dismantling of light from pole/ hanger pole shall be arranged by the contractor. |
| 69 | Supply and Fix in replacement of LED drivers of capacity 35 to 90 wattstreet light/flood light. Make : Havells/Philips/HPL/Crompton/Syska |
| 70 | Supply and Fix in replacement of LED drivers of capacity 100-200 watt street light/flood Make : Havells/Philips/HPL/Crompton |
| 71 | S&F in repair LED bulb for garden light 15 W 230V AC type suitable with retrofitting holder complete all as specified and directed. |
| 72 | S&F in replacement of PVC insulated PVC sheathed stranded copper conductor cable 1.5 Sqmmthree core complete all as specified and directed. |
| 73 | S&F in repair new generation energy saving and environmental friendly long life LED street light 70W made up of pressure die cast aluminium housing with high efficiency LED as lighting source and Toughened glass having Bottom Opening seperate driver compartment with IP66 protection and impact resistance of IK07. |
| 74 | Supply and fixing in repair LED flood light 50 watt 230 V AC Colour temp- 3000K/6500K(Warm white/cool white) outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant rectifier and with inbuilt SPD and potted driver complete all as specified and directed. |
| 75 | All as per item No 42 above but for 70 W |
| 76 | All as per item No 42 above but for 150 W |
| 77 | All as per item No 42 above but for 200 W |
| 78 | S&F in repair LED Post Top Gate Light Mushroom 15 watt 230 volts AC outdoor type for 360 degree indirect light IP 65 protection made from engineering grade polymer, supplied along with B22 LED Bulb including connection with PVC insulated & sheathed stranded copper conductor cable three core of size 1.5 Sqmm complete all as specified & directed. |
| 79 | S&F in replacement New generation, Unique concept LED Bollard 10 Watt Colour temp- 3000K/6500K in IP 66 to ensure sustainable performance in all sections and aesthetics which keeps the surrounding lively with PVC insulated & sheathed stranded copper conductor cable three core of size 1.5 Sqmm complete all as specified & directed. |
| 80 | S&F in replacement bracket for street light made out of 40 mm bore GI pipe medium grade not less than 1.2 mtr length bent at 120 degree to shape fixed on pole/wall with and including50mm X 6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primercomplete all as specified & directed. |
| 81 | Supply & fixing in repair of automatic street light switch using infrared sensor based on nature switch for automatic switching of street lights. Nature switch operation should be based on nature light lux level For switching ON is <60 lux for >30 sec and switching OFF >10 lux for >30 sec.The nature switch along with suitable contactor ,MCB should be enclosed in a pole/ wall mountable enclosure with mounting brackets, cable glands, openable door with lock and key, rust proof , electric shock proof, termite proof, outdoor mountable electrically insulating body capable of enduring solar radiation in the outdoor confirming to IP 65/66 suitable for three phase Max load of 5 KW complete all as specified and directed.Make -Swadeep Cat No. SWADEEP-02EC5KW3P or equivalent in siemens /Indoasian. |
| 82 | Supply & fixing in repair of automatic street light switch using infrared sensor based on nature switch for automatic switching of street lights. Nature switch operation should be based on nature light lux level For switching ON is <60 lux for >30 sec and switching OFF >10 lux for >30 sec.The nature switch along with suitable contactor ,MCB should be enclosed in a pole/ wall mountable enclosure with mounting brackets, cable glands, openable door with lock and key, rust proof , electric shock proof, termite proof, outdoor mountable electrically insulating body capable of enduring solar radiation in the outdoor confirming to IP 65/66 suitable for single phase Max load of 5 KW complete all as specified and directed.Make -Swadeep Cat No. SWADEEP-02EC3KW1P or equivalent in siemens /Indoasian. |
| 83 | S&F in repair Contactor 3 phase, rating 20 Amps per phase suitable for for existing automatic street light switchincludingnecessary connection and testing after connection complete all as specified and directed. Make :L&T/Siemens. |
| 84 | S&F in repair Contactor single phase, rating 32 Amps suitable for for existing automatic street light switchincludingnecessary connection and testing after connection complete all as specified and directed. Make :L&T/Siemens. |
| 85 | Supply and fixing in repair of MCB TPN40-100 Amp ,\"C\" Curve,10KA rupturing capacity all as specified and as directed. |
| 86 | Supply and fix in repair of MCBSPN, 220V , 50Hz , 32Asuitable for existing timer control board complete all as specified and directed. |
| 87 | Supply and fix in repair of MCBSPN, 220V , 50Hz , 40-63Asuitable for existing timer control board complete all as specified and directed. |
| 88 | Supply and fix in repair of MCBSP, 220V , 50Hz , 5-32AC\" curvefor street lightcomplete all as specified and directed. |
| 89 | Taking out old/unsv/rusted including S&Fof steel tubular pole 410-SP 31(9.0m long pole) complete with cast iron base plate, pole cap, mild steel bolt, nuts and screws complete including dismantling of exsiting pole all as specified including consisting of following works:- (a) Excavation in trenches not exceeding 1.5 mtr wide & 1.57 mtr deep for pole foundation & getting out in soft/loose soil, returning filling in the excavated of soil after fixing the pole in foundation ramming earth around in layer not exceeding 25 cm thick and disposal of surplus soil to a distance not exceeding 50 mtrs complete all as specified and directed.(b) M&L for PCC 1:4:8, type D2 (using 40mm graded crushed stone aggregate) in foundation 900mmx600mm cross section and planting depth 1.5 mtr for concrete encasing the pole upto GL complete all as specified and directed.(c) M&L for providing PCC 1:3:6, type C-1 (using 20mm graded crushed stone aggregate) for plinth block/collar above GL 500mm high and 450mm dia complete all as specified and directed. |
| 90 | Contd/...(d) M&L for painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminium paint over a coat of red oxide primer including preparation of surface including painting of 30 cm wide bands 3 Nos with synthetic enamel paint of appropriate colour in alternate layer upto the height of 1.5mm above plinth block.(e) M&L for writing letter or figures (Block Roman, Italic as Indian) with thick synthetic enamel paint of apprised shade not exceeding 5 cm height including numbering of pole complete all as specified and directed. |
| 91 | M & L for erecte, test and commissioning of High Mast pole systemconsisting of two section suitable for 55m/s wind speed alongwith head frame, made out of hot dip galvanised steel structure 20 Mtrs long, steel wire rope6mm dia 97/19 guage, double drum winch, luminiaries carriage suitable for 08 LED flood light in symmetrical arrangement and other accesories manufactured in factory with raising lowering system comprising double drum winch, trailing cable, connector, integral power tool motor, manual handle, junction box, lightining finial, (Wiring material from JB to individual luminiare & MCB in base compartment are not included and are a part of installation), with supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template and outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminiaries, power tool control with 2 No 9A contactors and raise lower push button, Incoming 25 sq. mm and out going 2.5sq. mm terminals. 20M High mast of BAJAJ Make or equivalent in Crompton, Philips, Havells. |
| 92 | Contd/...Note : Foundation bolts manufactured from special steel along with nuts, washeres, anchor plates and templates complete as recommeded by manufacturer or all as dircted by Engri-in-Charge.(i) The cost ofAviation light, lightning arrester spike,feeder piller box,copper cable 5 core,2.5 Sqmmfrom feeder piller box to 250 Watt LED light deemed to be included in the quoted rate.(ii) The cost for RCC foundation shall be born by the contractor and design should be as per manufacturer recommendations & no extra amount will be paid to the contractor on this account.(iii) Design/drawing for foundation is as per manufactrer approval.(iv) The excavation of soil for RCC work for the foundation deemed to be included in the quoted rate(v) LED Flood light 200W shall be measured and paid separately. |
| 93 | Supply and fixingLED flood light 200 watt 230 V AC Colour temp- 3000K/6500K (Warm white/cool white) outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant rectifier and with inbuilt SPD and potted driver complete all as specified and directed. |
| 94 | Earthing completewith galvanizedsteelearthplateelectrode600 x 600 x 6 mmburieddirectlyinground( earthpitnotlessthan2.25 mdeepbellowgroundlevel )withtopedgeoftheplatenotlessthan1.5 m bellownormalgroundlevel, connectedtogalvanizedearthlead wire 4 mmdia.bymeansof galvanizedironorsteelbolts , nuts , check nuts andwashers, andconnectedto equipmentsasdirected,includingfunnelwithGI med grade wateringpipe20 mmbore , wiremesh ,charcoalorcokeandcommonsaltinalternatelayersof15 cmcompactedthicknessallaroundtheearthelectrode ,withconcretepitinPCC1 :3:6type C-1 , 50 mmthickprecastRCC1 : 2 : 4typeB-1 coverslabreinforcedwith8 mmdiadeformedbar15 cm C/Candsuitablehandleof 10 mmdia roundbar,GI medium grade pipe for earth lead protectionincludingnecessaryexcavationearthworkinsoft/loosesoilanddisposalofspoiltoadistancen.exc.50 mandnecessarytestingcompleteallasshownonelectricalplateNo. 3ofMESSSRPart-I and as directed. |
| 95 | M&L for carrying out general periodical servicing and checking of the complete engine / transmission system / suspension system / exhaust system /cooling system / Electrical system and braking sysytem and hydrolic system complete along carring out wheel Rotation /Alignment along with greasing of wheel bearingsand rectify for the minior complaints defectsas per manufacturer recommendation /including replacement of required necessary minor spares such as nut,bolts, fuses and Replacement of diesel / Petrol Fuel filter (Primary and secondary) and Engine oilfilter complete sets along with o rings, new nuts and washers and cleaning of air filters/ breather,Radiator tank with Blower and labour for filling/topping up and Replacement of Engine oil /coolant / brake oil andtuning and testing of engine under idealload conditionsforvehiclesall as specified and directedNote (i) Rate Quoted includes the cost of minor acessories such as nuts and bolts O rings and all fuel/lube filters (ii) Engine Oil, Break oil, differentil oil, Coolant , air filter, Diesel filters, Spark plugs, Major U/S items shall be measured and paid under relevant Item. |
| 96 | All asper Item No 61.00 but for TATA Mobile |
| 97 | All asper Item No61.00 but for Bajaj Platina |
| 98 | All asper Item No61.00 but for Hero Honda Splendor |
| 99 | Supply Only Engine Oil for above mentioned vehicle |
| 100 | Supply Only Brake Oil |
| 101 | Supply Only Differential Oil |
| 102 | Supply Only Coolant |
| 103 | Supply Only Oil Filter |
| 104 | Supply Only Fuel Filter |
| 105 | Supply Only Spark Plug |
| 106 | Supply Only Air Filter |