| 1 | Note :(i) Please refer Sch A/ BOQ Notes before quoting the tender for all phases/ items mentioned below.(ii) Amount of Schedule of credit shall be deducted offline |
| 2 | Supply & fix in replacement, testing, commissioning of LT panel board, CPRI approved as per IEC-61439, weather proof, outdoor type powder coated, double door shutter, made out of CRCA sheet3.15 mm thick outer and 2.00 mm thick for inner door confirming degree of protection IP-66 to with angle iron 50x50x6 mm outoor, floor mounting type with closed aluminium bus bar chamber of size not less than 1.5 times of incommer including necessary insulator suitable for 3 phase, 4 wire 50 Hz AC,CPRI approved including provn of digital ammeter 0-350A,digital voltemeter 0-500 Volts, CT\"s of suitable ratio, indicator lamps R-Y-B, selector switches and internal wiring including making PCC block type 30 cm grouting etc all as specified and directed with the following work alsoincludes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc the bottom portion of enclosure shall be minimum 60 cm above ground level of legs of angle iron. LT panel comprising of following specification are:-(a) MCCB, TPN, 320 amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB TPN 250 Amps, 16 KA at 415 Volts- 01 Nos (Outgoing) (c) MCCB TPN 160 Amps, 25 KA at 415 Volts- 01 Nos (Outgoing) (d) MCCB TPN 160 Amps, 25 KA at 415 Volts- 01 Nos (Outgoing) (e) MCB TPN 63 Amps, 16 KA at 415 Volts - 01 (Outgoing) (f) MCB SPN 40 Amps, 10 KA at 230 Volts - 02 (Outgoing) (g)Phase indicating lamp RYB, neon type (set of three ) -01 Set(h)VAF+PF meters , accuracy class 0.5 |
| 3 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 200 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming)(b) MCCB, TPN, 160 Amps, 16 KA at 415 Volts- 01 Nos (Outgoing)(c) MCCB TPN 63 Amps, 25 KA at 415 Volts- 01 Nos (Outgoing)(d) MCCB TPN 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(e) MCB SPN 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(f)Phase indicating lamp RYB neon type (set of three ) -01 Set(g)VAF+PF Meters , Accuracy class 0.5 |
| 4 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 350 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming)(b) MCCB, TPN, 63 Amps, 25 KA at 415 Volts- 03 Nos (Outgoing) (c) MCCB, TPN, 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(d) MCB SPN 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(e)Phase indicating lamp RYB neon type (set of three ) -01 Set (f)VAF+PF meters , accuracy class 0.5 |
| 5 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 350 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB TPN 63 Amps, 25 KA at 415 Volts- 03 Nos (Outgoing) (c) MCCB TPN 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(d) MCB SPN 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(e)Phase indicating lamp RYB neon type (set of three ) -01 Set (f)VAF+PF meters , accuracy class 0.5 |
| 6 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 200 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB, TPN, 63 Amps, 25 KA at 415 Volts- 02 Nos (Outgoing) (c) MCCB, TPN, 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(d) MCB SPN 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(e) Phase indicating lamp RYB neon type (set of three ) -01 Set (f)VAF+PF meters , accuracy class 0.5 |
| 7 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 400 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB, TPN, 125 Amps, 25 KA at 415 Volts- 08 Nos (Outgoing)(c) MCCB, TPN, 63 Amps, 25 KA at 415 Volts- 01 Nos (Outgoing)(d) MCCB, TPN, 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(e) MCB SPN 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(f) Phase indicating lamp RYB neon type (set of three ) -01 Set (g)VAF+PF meters , accuracy class 0.5 |
| 8 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 400 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB, TPN, 250 Amps, 25 KA at 415 Volts- 01 Nos (Outgoing)(c) MCCB, TPN, 125 Amps, 25 KA at 415 Volts- 03 Nos (Outgoing)(d) MCCB, TPN, 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(e) MCB, SPN, 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(f) Phase indicating lamp RYB neon type (set of three ) -01 Set (g)VAF+PF meters , accuracy class 0.5 |
| 9 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 400 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB, TPN, 100 Amps, 25 KA at 415 Volts- 04 Nos (Outgoing)(c) MCCB, TPN, 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(d) MCB, SPN, 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(f) Phase indicating lamp RYB neon type (set of three ) -01 Set (e) VAF+PF meters , accuracy class 0.5(g)LT outdoor type IP-54 encloscire timer switch panel(i) MCB TPN 40 Amp, \"C\" Curve, 415 V , 10 KA - 01 Nos.(ii) Contactor 25 Amp, 415 V - 01 Nos.(iii) Electronic Timer 1 Phase - 01 Nos. |
| 10 | All as per item No 1.10 here-in-before but with followings specification complete all as specified and directed.(a) MCCB, TPN, 400 Amps, Icu=Ics 35 KA adjustable type thermal magnetic based release at 415 Volts- 01 Nos (Incoming).(b) MCCB, TPN, 100 Amps, 25 KA at 415 Volts- 02 Nos (Outgoing)(c) MCCB, TPN, 63 Amps, 25 KA at 415 Volts- 02 Nos (Outgoing)(d) MCCB, TPN, 63 Amps, 16 KA at 415 Volts - 01 (Outgoing)(e) MCB, SPN, 40 Amps, 10 KA at 230 Volts - 01 (Outgoing)(f) Phase indicating lamp RYB neon type (set of three ) -01 Set (e) VAF+PF meters , accuracy class 0.5 |
| 11 | Supply, errecting, testing and commissioning of High Mast pole system consisting of two section suitable for 55 m/s wind speed alongwith head frame, made out of hot dip galvanised steel structure 16 Mtrs long, steel wire rope 6mm dia 97/19 guage, double drum winch, luminiaries carriage suitable for 06 luminiaries in symmetrical arrangement and other accesories manufactured in factory with raising lowering system comprising double drum winch, trailing cable, connector, integral power tool motor, manual handle, junction box, lightining finial, with and including supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template and outdoor stand mounted feeder pillar with 32 A, TPN, MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminiaries and timer switch with all connected accessories for automatic switching of light, power tool control with 2 Nos, 9 A contactors and raise lower push button, incoming 25 sq. mm and out going 2.5 sq. mm terminals with all connected items as required at site complete all as specified and directed with and including following specifications:-Notes: (i) High mast pole system shall be of Make:Bajaj/ GE/ Crompton/ Philips/ Havells as approved by GE. (ii) The cost of aviation light, feeder piller box, copper cable 2.5 Sqmm from feeder piller box to LED light is deemed to be included in the quoted rate.(iii) The cost for excavation in fdn, returning fillingin, RCC foundation etc. shall be born by the contractor and design should be as per manufacturer recommendations & no extra amount will be paid to the contractor on this account. |
| 12 | HIGH MAST SYSTEMHeight of mast : 16 MeterNo. of Section: TwoMaterial Construction:S355 Grade as per IS 2062/BS-EN10 025Base dia and top diameter (A/F): Top :150mm & Botton :460 mmCross section of Mast : 20 side polygonStandard for Galvanisation: A per BS EN ISO 1461Size of Opening and door at base:1200 x 2500 mmDiameter of base plate : 570 mmThickness of base plate:25 mmLighting protection finial :GI single spike of length 1200mmMax. wind speed : 55m/s as per IS 875 (Part III)Number of foundation bolts: 12 NosPCD of foundation bolts : 590 mmType / diameter / length of foundation bolts : TS 600/30mm dia/ 850 mm long |
| 13 | LUMINAIRES CARRIAGEMaterial of construction :50 NB ERW Class B-M.S PipeDiameter of carriage ring (mm) :535 mm (ID)Construction: 08 Arm, Welded, 2 SectionsLoad carrying capacity: 16 Luminaire |
| 14 | TRAILING CABLEConductor : Copper,6 core,2.5 SqmmInsulation: PVC FlexibleNo.of circuits per mast :One No cable per mast |
| 15 | WINCH / POWDER TOOLType /SWL of winch: Double drum, SWL 750 Kg Method of Operation :IntegralMotorMotor Capacity : 1.0 HP ( Including suitable starter)No of Speeds :6 Pole, Single speedTorque Limitor :With Mechanical Tripping Facility |
| 16 | STAINLESS STEEL WIRE ROPEGrade / construction :AISI 316, 7/19 ConstructionNumber of Ropes :Two ContinuousDiameter (mm): 6 mm, 97/19 guage, Breaking load Capacity : 2350 Kg x 2 |
| 17 | M&L earthing complete with GI strip as earth lead and MS galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32 x 6 mm with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 using 20 mm gradded stone aggregate and RCC cover with frame including plastering and white wash, charcoal, common salt 15cm at round the earth plate, watering pipe 20mm med grade/galvanized and 40mm dia GI pipe medium grade for GI strip protectionwith GI funnel complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2020. Notes : Contractor shall be produce test result data sheet , if result not came as required, he has to redone without any extra cost. (i) The unit rate includes for 40mm dia, medium grade, protection pipe and earth lead upto 7.50 meter. (ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately. (iii)PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate. |
| 18 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, galvanised steel striparmoured, heavy duty cable, 1100 volts grade, laid in trenches, passing through pipes/ducts, on walls with shadel, etc including taking out old unserveciable cable, any type with aluminium conductor of size 16 Sqmm nominal cross section x 4 core complete all as specified and directed. |
| 19 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for pole foundation, cable trench, etc and getting out insoft/hard soil or rock complete all as specified and directed. |
| 20 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each complete all as specified and directed. |
| 21 | Removing excavated materials soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 22 | M&L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection (8 cm below cable & 15 cm above cable) complete all as specified and directed. Note:- Punned thickness shall be measured & paid seperatly. |
| 23 | Supplying and laying class LV, type I, flat, size 250mm x 150mm x 40mmfor cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed. |
| 24 | Supply, erection & testing of 9.00 meter hot dip, galvanized octagonal pole top 70mm, bottom 155mm thickness 250x250x163mm with mounted on RCC pedestal as per manufacture foundation nuts & bolts EN-8 grade as per IS 1307 including junction box plate IS-2062 made of MS Fe-910 & Connected accessories including 1.2 meter single arm bracket & writing pole nos including taking out old poles any type/size complete all as specified and directed.Note- Excavation, PCC shall be measured and paid separately under respective item.The octagonal pole shall be designed to withstand the maximum wind speed as per IS-875 |
| 25 | S&F repair/replacement of factory made RCC precast earthing pit cover chamer of size 600 mm x 600 mm x 450 mm & 50 mm thick all as specified and directed. |
| 26 | S&F in repair MCCB, 630 Amp, 4 Pole, 50 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting and protection against ground fault ,including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 27 | S&F in repair MCCB, 400 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting and protection against ground fault ,including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 28 | S&F in repair MCCB, 250 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting and protection against Earth protection leakage fault ,including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 29 | S&F in repair MCCB, 200 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting andEarth protection leakage fault module,including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 30 | S&F in repair MCCB, 160 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting, with thermal release range 125-160 Amp including spreader terminals and phase barriersincluding taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 31 | S&F in repair MCCB, 100 Amp, 3 Pole, 16 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 100-125 Amp including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 32 | S&F in repair MCCB, 63 Amp, 3 Pole, 16 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release including spreader terminals and phase barriers including taking down old unserviciable burnt MCCB, complete all as specified and directed. |
| 33 | M&L making coping to the new/existing PCC/steel polesabove the GL withPCC 1:3:6 type B-1 using 20 mm graded broken stone aggregate as in mass concrete complete all as specified and directed. Note :- Quoted rates deemed to be including for dismantling of broken copings. |
| 34 | M&L PCC (1:4:8) type D-2 using 20mm graded stone aggregates as in foundation filling and mass concrete for foundation bed concrete in stays /poles complete all as specified and directed. |
| 35 | S&F air circuit breaker 4 pole, 415 V, with manual drawout typewith microprocessor release of capacity of 1250 Amps including accessories complete all as specified and directed. |
| 36 | Deduct Schedule of credit (calculation will be done off line) Rs. 31380.00 |