| 1 | Supply, installation, testing and commissioning of Active Harmonic current Filter, 2x100 A rating with 500/600 A capacity panel,415 V,50 Hz, 3 phase 3w/4w compatable,modular in nature ( to add additional module of 100 A)of standard rating, complying to the technical specifications enclosed. The installation includes all the power, control circuits with adequate rated PT, CT\"s,control and power circuit wiring as required for satisfactory operations complete in all aspects as per site condition. |
| 2 | Supply, installation, testing and commissioning of Addtional module of 100 A rated current harmonic filter in the existing AHF system with necessary accessories as requires complete in all aspects for satisfactory working as per site condition. Will be operated based on the power quality study and requirement as mentioned in Si.No-3 |
| 3 | To conduct a detailed power quality study at various loadsfor minimum 1 or 2 days and provide proper authorised report as required for each transformer before & after lining up the AHF system for verifying compatability of the system provided with all accessories as requiredas per site condition |
| 4 | Supply of web based Energy monitoring system software which will be supporting to 75Nodes with Webview,Data logging and report generation from energy meters , Auto emailing ,Indivdualmeter communication status with communication failure alarm on screen, section wiseenergy consumption. SupportVoltage , Amps, KWH, KVAH , Harmonics,Running hours, PF, Hz, MD stored and display this details ,Report to be in made and down load via excel day by day, month wise, particularperiodand other standard features, along witha warranty of minimum 18 months, having technical& service support for the minimumlife time of the system, suitable forCSIR-CECRI\"s SS-1 & SS 2 complete in all aspects as per site condition for satisfactory operations as required |
| 5 | Supply , installation, testing and commissioning ofdigital LED MFM meter ofClass 1.0 acuracy with RS 485 communication port suitable for sub feeders of size not less than 96x96 CM, flush mounting on the existing feeder panel by replacing of old existingMFM meter, having minimum parameters of V,A,F,PF,KW,Old energy,On hours, site selectable kWH/kVAH,Auto scrolling and freeze mode for constant single phase viewing available, etc., complete in all aspects CT & PT wirings etc., with required accessories. |
| 6 | Supply , installation, testing and commissioning ofdigital LED MFM meter ofClass 0.5 acuracy with RS 485 communication port suitable for 22 kV SS HT panel suitably mounted on the existing feeder panel by replacing of old existing MFM meter, having minimum parameters of V,A,F,PF,KW,kVA,kVAR,kWH,kVAH,Import & export Wh,Vah & Runhours,On hours,Phase angle, Interrupts, THD, Events(High-Low), Neutral Current, Max Demand(with RTC), Individual Harmonics upto 31st order,Auto scrolling and freeze mode for constant single phase viewing available etc., complete in all aspects CT & PT wirings etc., with required accessories. |
| 7 | Supply , installation, testing and commissioning ofdigital LED MFM meter ofClass 1.0 acuracy with RS 485 communication port suitable for Substation LT Incomer panel,generator incomer panel and SS-2 old panel incoming suitably mounted on the existing feeder panelby replacing of old existing MFM meter, having minimum parameters of V,A,F,PF,KW,kVA,kVAR,kWH,kVAH,Import & export Wh,Vah & Runhours,On hours,Phase angle, Interrupts, THD, Events(High-Low), Neutral Current, Max Demand(with RTC), Individual Harmonics upto 31st order,Auto scrolling and freeze mode for constant single phase viewing availableetc., complete in all aspects CT & PT wirings etc.,with required accessories. |
| 8 | Supply, installation,testing and commissioning of 1 port RS 485 to Modbus TCP communication Gateway, whichSupports Auto Device Routing for easy configurationSupports route by TCP port or IP address for flexible deploymentConverts between Modbus TCP and Modbus RTU/ASCII protocols1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports16 simultaneous TCP masters with up to 32 simultaneous requests per masterEasy hardware setup and configurationcomplete in all aspects suitable to the system as required as per site condition |
| 9 | Supply of2 core RS 485 communicable shielded, twisted pair cable suitable for the above system as required as per site condition. |
| 10 | Supply and fixing of suitable medium duty PVC conduit of Min 19 MM or as required for the system provided with required accessories complete in all aspects as per site condition to draw thecommunication cable as requried. |
| 11 | Supply, testing and commissioning of CAT 6 Ethernet Patch Chords 2 meter stranded typeConductor: 24 AWG, Snagless cable,1000 base Ethernet transmission of reputed make as approved by department complete in all aspects suitable to the system as required as per site condition |
| 12 | Supply, installation,testing and commissioning of Gate way converter IP chords of reputed make as approved by department & Meters configuaration complete in all aspects suitable to the system as required as per site condition |
| 13 | Drawing the communication cable in the existing pipe/trench/wall and inside the panel along with termination(excluding civil works) as required as per site condition. |
| 14 | Installation,testing and commissioning of the EMS soft ware for 75 nodes including metering, data collection,Group report module generation, email features and other aspects of the system complete in all aspects as required as per site condition for satisfactory operation of the system. |
| 15 | Supply, installation,testing and commissioning ofDesktop computer with monitor,CPU, keyboard,mouse and pre installed OS having the technical parameters as per the enclosed technical specification sheet complete in all aspects for satisfactory operations of the envisaged EMS system as per site condition. |
| 16 | Supply,installation,testing and commissioningof communication system and integration with EMS software for collection of essential/Electricaldata to Substation-1 from theexisting control panel end of followingSolar On grid system of 140 KW at one area,370 KW Solarat four different places ,2x750 KVA Cummins generator control panel data and 1X320 KVA Generator Cumminswith 2 core RS 485 communicable shielded, twisted pair cable suitable for the above systemas required as per site condition complete in all aspects as requried. The site details are enclosed. |
| 17 | Excavating trenches of required width for pipes,cables etc., including excavation for sockets,depth upto 1.5 m including getting out the excavated materials, returning the soil as required in lyers not exceeding 20 cm in depth, including consilidating each deposited layers byramming, watering etc., stacking servicable material for measurements and disposal of unservicable materials as directe, within a lead of 50 m for all types of soil |
| 18 | \"Deployment of Electricians :- For Trench cutting,cable removing and termination work which arises during work execution of above work in Panel area or in trench area in Sub station-1 & sub station-2 |
| 19 | Deploymentof MasonGrade-2 :- For any trench cutting area plastering work andany chipping/plasteringwork at panel area in Substion-1 & substation-2 |