| 1 | Supplying, Fabrication and Installation of 4 mtr. high pole made out of 65 mm dia NB, B class G.I pipe ISI marked duly welded with MS base plate of size 300 mm x 300 mm x 12 mm thick with suitable earth stud on base plate and collar typemounting arrangement for light fitting on the pole, making suitable size hole in pole at a height of 2.5 metre from base plate for cable entry/exit, painting & numbering of pole, making suitable size hole in base plate for cable entry/exit into the pole and fixing the pole on the foundation with the nuts-bolts, washers etc. complete as required. |
| 2 | Providing and laying in position 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)reinforced cement concrete foundation of size450 mm x 450 mm x 1200 mm deep (800 mm below ground level and 400 mm above ground level) including excavation of earth, refilling, providing, cutting, bending and placing in position, reinforcement of cold twisted bars of 12mm. dia-1200mm long (approx) 8Nos, and reinforcement ring of cold twisted bar of 8mm dia -1400mm long (approx) -6 nos, (with suitable spacing) including centering & shuttering as required with providing, fixing and positioning of one set of foundation bolts comprising of 4 nos., 16 mm dia, 750 mm long J-Type MS bolts (Threaded portion shall be galvanized) along with 3 nos. GI nuts and 2 nos. GI washers etc. per bolt and 1 no. anchor plate (3mm thick) of suitable size and providing 63 mm.(O.D) DWC pipe ISI marked for cable entry & exit etc. complete as required. |
| 3 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105<120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 4 | Supplying, Installation, testing and commissioning of 40 Watt post top lantern having IP-66, lumen efficancy >105 lumen/wattwith spun aluminium housing and pressuredie cast aluminium spigot offers symetric light distribution with clear polycarbonate diffuser ( light fitting shall be approved by Engineer-in-Charge as per requirement ) etc complete as required. |
| 5 | Supply & fixing of pole connector box made out of Glass Reinforced Polyester Sheet Moulding Compound Conforming to IS:13410-1992 Grade S1 of outside dimensions 280 mm(H) x 170 mm(W)x 115 mm (D) (all the corners of the box should be round & not pointed ones) suitable to mount on 40/50/65 mm dia GI pole with the followingprovisions/accessories mounting in box complete as reqd.(i)2 nos. clamps made out of 19mm x 3 mm GI strip of suitable length for mounting box on the pole.(ii) Water tight front cover with 2 nos. stainless steel hinges & 1 no. screw for tightening.(iii)4 way, 220 V, 30 A, dough moulded connector (SMC with stainless steel inserts)(iv) 16 amp. Moulded SMC rewireable kit-kat---1 no.(v) Suitable size hole at suitable location on rear wall for cable & wire entry.(vi) Earthing bolt M6 x 20 mm |
| 6 | Supplying , Installation, testing and commissioning of floor mounted Light control LT feeder pillar cubical type double door of size of 1000 mm x 900 mm x 300 mm deep duly compartmentalized and with general arrangement made out of 2mm thick CRCA sheet having hinged gasket cover and screwed knobs with double locking arrangement and rain protection covers 100 mm and supported with of MS angle iron legs and bottom frame of size 35mm x 35mm x5mm x 0.7mtr. long grouted with 1:3:6 CC foundation and should be 0.4 mtr. above ground level. Legs should be covered with brick walls, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles wherever required, painting, numbering i/c supply and fixing of following accessories complete as required.(a)63 Amps. Four Pole MCB (\"C\"-Series), 10kA----1 No.(b) Analogue Timer switch for daily operation and toggle switch forauto/manual --1 No. (c) 32 Amps. AC-3, 3 pole power contactor -----1 No. (d) 30 Ampere 4 way neutral link/connector ------2 Nos. (e) Voltmeter(0-500 Volt) 96mm X 96mm square type with selector switch---1 No (f) Phase Indicating Lamp Set with fuses ----1 Set (g) Danger notice plate -----1 No (h)Ammeter (0-30Amp) 96mm X 96mm square type ----1No.(i)Lifting hook on the top of panel board and lighting arrangement inside the feeder pillar---- 1 No. (j) 32 Amps. SP MCB (\"C\" Series), 10KA- 6 Nos.(k) Al busbar 100 AMP capacity, 300 mm long (4 nos) |
| 7 | Supplying, Fabrication and installation of wire mesh protection frame for existing feeder pillar made out of 8 SWG M.S wire mesh size (75mm X25mm rectangle nominal) of following size with base frame made of M.S angle iron 35mm x 35mm x 5mm and with M.S strip support of size 35mm X 5mm in cross and 0.5 mtr long legs support of same angle iron (as per drawing attached) , i/c door in front portion, supplying and fitting of godown lock i/c locking arrangement, painting and grouting of angle iron frame with legs in CC 1:3:6 foundation etc. as approved by Engineer incharge etc. complete as reqd.a) 2 mtr (H) X 1.5mtr (W) X 1.0 mtr (D) |
| 8 | 2Cx16 sq. mm |
| 9 | b) 4C x 25 sq. mm |
| 10 | Supplying & drawing following size of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required.a)3 x 1.5 sq. mm, DSR |
| 11 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. (i) 63mm dia (OD-63mm & ID- 51 mm nominal) |
| 12 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.a)Upto 35 sq. mm , DSR |
| 13 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required. , DSR |
| 14 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required., DSR |
| 15 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. ,DSR |