Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Note :(i) Please refer Sch A/ BOQ Notes before quoting the tender for all phases/ items mentioned below.(ii) Amount of Schedule of credit shall be deducted offline |
| 2 | Excavation in trenches not exc 1.5 mtr wide & not exc 1.5 mtr in depth for foundation etc or for manholes, laying of pipe lines, cables, pipes etc in hard dense soil and getting out complete all as specified and directed. Note- Cost for dewatering from trenches,valve chamber and around the valve etc included in the said work. |
| 3 | Returning filling in, including spreading, leveling watering & well ramming in layers not exc 25 cm thick complete all as specified and directed. |
| 4 | Removing excavated material to a distance not exc 50 mtr & depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and diected. |
| 5 | Dismantling of existing motorized valve of size from 50mm to 450mm its electrical connection and connected items , setting a side andrefixing the same after carriying out its servicing, oiling, greasing including minor spare part i.e. capacitor and limit switches etc completecomplete all as specified and directed.Note- Cost for dewatering from valve chamber and around the valve included in the job work. |
| 6 | Supply, Installation, Testing and Commissioning of Flow Switch as per IS-3854, IP-64 in replacement along with all necessary installation accessories complete all as specified & diected.Make:DANFOSS / SWITZER / SIEMENS / RAPID CONTROL / JOHNSON CONTROL/ Universal Switch Gear Control. |
| 7 | Supply and fix shaft of Stem Material SS - 410 alongwith for operation of 450mm motorized butterfly valve alongwith its MS casing duly anti rust painted of suitable size to existing valve and its acutator .Note - Length of shaft and its casing shall be as per existing one or as per OEM recommendations |
| 8 | Supply and fix shaft of Stem Material SS - 410 alongwith for operation of 250mm motorized butterfly valve alongwith its MS casingduly anti rust painted of suitable size to existing valve and its acutator.Note - Length of shaft and its casing shall be as per existing one or as per OEM recommendations |
| 9 | Supply and fix shaft of Stem Material SS - 410 alongwith for operation of 200mm motorized butterfly valve alongwith its MS casing duly anti rust painted of suitable size to existing valve and its acutator.Note - Length of shaft and its casing shall be as per existing one or as per OEM recommendations |
| 10 | Supply and fix shaft of Stem Material SS - 410 alongwith for operation of 150mm motorized butterfly valve alongwith its MS casing duly anti rust painted of suitable size to existing valve and its acutator.Note - Length of shaft and its casing shall be as per existing one or as per OEM recommendations |
| 11 | Supply and fix shaft of Stem Material SS - 410 alongwith for operation of 100mm motorized butterfly valve alongwith its MS casing duly anti rust painted of suitable size to existing valve and its acutator.Note - Length of shaft and its casing shall be as per existing one or as per OEM recommendations |
| 12 | Supply and fix shaft of Stem Material SS - 410 alongwith for operation of 80mm motorized butterfly valve alongwith its MS casing duly anti rust painted of suitable size to existing valve and its acutator.Note - Length of shaft and its casing shall be as per existing one or as per OEM recommendations |
| 13 | Supply and fix Butterfly Valve (Wafer Type), PN-1.6 as per IS-13095 with S.S-304 Disc 100mm dia including gaskit and nut bolts washer complete all as specified and directed.Make-Sant/Zoloto/Kartar |
| 14 | Supply and fix Butterfly Valve (Wafer Type), PN-1.6as per IS-13095 with S.S-304 Disc 150mm dia including gaskit and nut bolts washer complete all as specified and directed.Make-Sant/Zoloto/Kartar |
| 15 | Supply and fix Butterfly Valve (Wafer Type), PN-1.6as per IS-13095 with S.S-304 Disc 200mm dia including gaskit and nut bolts washer complete all as specified and directed.Make-Sant/Zoloto/Kartar |
| 16 | Supply and fix Butterfly Valve (Wafer Type), PN-1.6 as per IS-13095 with S.S-304 Disc 250mm dia including gaskit and nut bolts washer complete all as specified and directed.Make-Sant/Zoloto/Kartar |
| 17 | M & L for copper rewinding of single phase motor suitable to existing 80mm dia to 150mm motorized actuator for operation of existing valve including taking down existing one and transportation to workshop and refixng the same after carrying out repair etc complete all as specified and directed. |
| 18 | M & L for copper rewinding of single phase motor suitable to existing 200mm dia to 250mm motorized actuator for operation of existing valve aincluding taking down existing one and transportation to workshop and refixng the same after carrying out repair etc complete all as specified and directed. |
| 19 | M & L for copper rewinding of single phase motor suitable to existing 450mm motorized actuator for operation of existing valve including taking down existing one and transportation to workshop and refixng the same after carrying out repair etc complete all as specified and directed. |
| 20 | S & fixsingle phase motor forelectrically actuated valve as per 60529, IP-65/68suitable to existing 100mm dia to 150mm dia motorized actuator for operation of existing valve recommended by OEM including taking down existing one complete all as specified and directed. |
| 21 | S & fixsingle phase motor forelectrically actuated valve as per 60529, IP-65/IP68 suitable to existing 200mm dia to 250mm dia motorized actuator for operation of existing valve recommended by OEM including taking down existing one complete all as specified and directed. |
| 22 | S & fix single phase motor forelectrically actuated valve as per 60529, IP-65/IP68 suitable to existing 450mm dia motorized actuator for operation of existing valve recommended by OEM including taking down existing one complete all as specified and directed. |
| 23 | S & Fix PCB Card for Valves suitable to existing 100mm dia to 150mm diamotorized actuator for operation of existing valve recommended by OEM including taking down existing one complete all as specified and directed. |
| 24 | S & Fix PCB Card for Valves suitable to existing 200mm dia to 250mm diamotorized actuator for operation of existing valve recommended by OEM including taking down existing one complete all as specified and directed. |
| 25 | S & Fix PCB Card for Valves suitable to existing 450mm diamotorized actuator for operation of existing valve recommended by OEM including taking down existing one complete all as specified and directed. |
| 26 | S & Fix in repalcement of Relay with base 4 C/O, 24V DC including taking down existingcomplete all as specified and directed by Engr in Charge.Make- Leone/IDEC/L&T |
| 27 | S & Fix in repalcement of Relay with base 4 C/O, 240V AC including taking down existingcomplete all as specified and directed by Engr in Charge.Make- Leone/IDEC/L&T |
| 28 | Supply, Installation, testing and Commissioning of 100 mm dia extended type , single phase, Motor Actuated wafer type Butterfly valve as per IS 13095 with disc material SS - 304, Stem Material SS - 410, Seat EPDM, hand wheel for manual operation and having 05 nos. limit switches for Open / Close condition, valve position indicator and over ride trip. The housing of actuator should be of Aluminium Dicast. The actuator must have planetary gear set to transfer the largest torque in the most compact form. The mounting shall be direct on valve type. Input Voltage : 230V AC, Designed Line Pressure : 16 kg/sq cm gear set type : Planetary Gear Set , In built CPU:- Quad-core 64-bit ARM Cortex A53 clocked at 1.2 GHz inbuilt 4 USB 2 ports, In built Base Ethernet Port, In built Micro SD port for loading your operating system and storing data, In built wireless LAN and Bluetooth Low Energy , The mounting shall be indirect type using specialized extended type arrangement of GI pipe of suitable size/thickness, so that actuator mounting is at least 36 inches above pipe level complete all as specified and directed.Make of Actuator - SAMSON / UNIVERSAL SWITCH GEAR CONTROL / EMERSON / ROTORK / AUMAMake of Butterfly - Sant/Zoloto / KIRLOSKAR/L&T |
| 29 | Supply, Installation, testing and Commissioning of 150 mm dia extended type, single phase, Motor Actuated wafer type Butterfly valve with disc material SS - 304, Stem Material SS - 410, Seat EPDM, hand wheel for manual operation and having 05 nos. limit switches for Open / Close condition, valve position indicator and over ride trip. The housing of actuator should be of Aluminium Dicast. The actuator must have planetary gear set to transfer the largest torque in the most compact form. The mounting shall be indirect on valve type. Input Voltage : 230V AC, Designed Line Pressure : 16 kg/sq cm.Gear Set Type : Planetary Gear Set., In built CPU:- Quad-core 64-bit ARM Cortex A53 clocked at 1.2 GHzInbuilt 4 USB 2 ports , In built Base Ethernet Port, In built Micro SD port for loading your operating system and storing data, In built wireless LAN and Bluetooth Low Energy . The mounting shall be indirect type using specialized extended type arrangement of GI pipe of suitable size/thickness, so that actuator mounting is at least 36 inches above pipe level complete all as specified and directed. Note -Make of Actuator - SAMSON / UNIVERSAL SWITCH GEAR CONTROL / EMERSON / ROTORK / AUMAMake of Butterfly - Sant/Zoloto / KIRLOSKAR/L&T |
| 30 | Supply, Installation, testing and Commissioning of 200 mm dia extended type, single phase, Motor Actuated wafer type Butterfly valve with disc material SS - 304, Stem Material SS - 410, Seat EPDM, hand wheel for manual operation and having 05 nos. limit switches for Open / Close condition, valve position indicator and over ride trip. The housing of actuator should be of Aluminium Dicast. The actuator must have planetary gear set to transfer the largest torque in the most compact form. The mounting shall be indirect on valve type. Input Voltage : 230V AC, Designed Line Pressure : 16 kg/sq cm. Gear Set Type : Planetary Gear Set., In built CPU:- Quad-core 64-bit ARM Cortex A53 clocked at 1.2 GHzInbuilt 4 USB 2 ports , In built Base Ethernet Port, In built Micro SD port for loading your operating system and storing data, In built wireless LAN and Bluetooth Low Energy . The mounting shall be indirect type using specialized extended type arrangement of GI pipe of suitable size/thickness, so that actuator mounting is at least 36 inches above pipe level complete all as specified and directed.Note -Make of Actuator - SAMSON / UNIVERSAL SWITCH GEAR CONTROL / EMERSON / ROTORK / AUMAMake of Butterfly - Sant/Zoloto / KIRLOSKAR/L&T |
| 31 | Supply & Fix in repalcement Motor Control Panel of Sewage Non clogging Pump to operate automatically on the basis of Upper level and lower level and shall be made of 2mm thick CRCA Sheet single door indoor type with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finishand factory assembled, The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54 , front side double door type with locking arrangementand nut bolt fitting for back side, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber. The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars. Control wiring of the panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured and drawing of control wiring shall be provided duly laminated and fixed to the left/right side from inner side of the panel.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.The panel shall be wall mounted type . All MCCBs shall be provided with spreader links with phase separators and connected through Aluminium Busbar to busbar of panel and Alumnium busbar extension shall be provided for LT cable connections complete all as specified and as directed. The overall size of the panel shall not be less than 900mmX250mmX900mm (LxBxH).The panel shall be provided with and including following accessories:-Note:Cost for dismantling of existing panel , its all cable connection and reconnection all connections after fixing new one complete all as specified and directed.Note: (i) Panel Drawing alongwith line plan of complete control wirring of accesories shall be submitted by contractor. Make of Soft starter and Contactor shall be same make. Panel shall be brought on the site after approval of panel drawing by Engr-in-Charge.(a)4 Nos bus bars of high conductivity aluminium alloy, 4 Nos for phase (R,Y,B,N) rating 100 Amp rating 50 KA.(b) 03 Nos LED Indicators for RYB as phase indicator, 02 Nos Indicator for On/Off indication, 01 Nos Indicator for Triping indication,415 V, 50 Hz, Surface mounted with Surge & Low volatge glow protection Make- L&T(c) Float Sensor -02 Nos for Upper level and lower level alongwith its cable. Panel shall be designed to operate Motor Auto/Manual/Bypass arrangement to operate Sewage pump Automatically as per water level of Sewage Well.(d) Incomer 3 pole MCCB 40A- 01 Nos Ics=100%Icu , 25 KA with Protection against overloads:Conforms to IS/IEC 60947-2 , lr adjustable from .67 to 1 x ln, Adjustable short-circuit settings: 6 - 12 x In*, Compact sizeMake:- L&T/Legrand/Siemens/ABB(e)Soft Starter as per IEC 60947-4-2suitable for 20HP Non Clog Sewage Pump 15 KW,30 Amp Rated current , Three-phase controlled, Operational voltage: 208 – 690 VAC , Wide rated control supply voltage: 100 – 250 V 50/60 Hz, Both in-line and inside-delta connection, Coated circuit boards protecting from dust, moist and corrosive atmosphere, Detachable keypad rated IP66 (4X outdoor), Built-in bypass for energy saving and easy installation, Built-in Modbus RTU for monitoring and control, compatible /Support for all major communication protocols, Analog output for measurement of current, voltage, power factor etc. including communication accessories to connect existing scada system and overload relay compatible to soft starter etc Qty-01 NosMake:- ABB Cat Part No PSE30-600-70/Legrand/Siemens(f) 3 Pole power Contactor with auxilary /add on blocks as required and suitable to 20 HP Non Clog Sewage Pumps for bypass arrangement of Soft Starter (g) Start Push Button & Stop Push Button for 01 Motors(h) Voltmeter -01 Nos , Ammeter-01 Nos Multifunction Meter LED ,Accuracy Class 1, with V, A, F, PF, kW, kVA, Old energy, On and Run hours, site selectable kWh/ kVAh including suitable size of CTs etc Make - Legrand/L&T/Schneider |
| 32 | Supply & Fix in repalcement Motor Control Panel made of 2mm thick CRCA Sheet single door indoor type with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finishand factory assembled, The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54 , front side double door type with locking arrangementand nut bolt fitting for back side, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber. The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars. Control wiring of the panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured and drawing of control wiring shall be provided duly laminated and fixed to the left/right side from inner side of the panel.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.The panel shall be wall mounted type . All MCCBs shall be provided with spreader links with phase separators and connected through Aluminium Busbar to busbar of panel and Alumnium busbar extension shall be provided for LT cable connections complete all as specified and as directed. The overall size of the panel shall not be less than 900mmX250mmX900mm (LxBxH).The panel shall be provided with and including following accessories:-Note:Cost for dismantling of existing panel , its all cable connection and reconnection all connections after fixing new one complete all as specified and directed. Note: (i) Panel Drawing alongwith line plan of complete control wirring of accesories shall be submitted by contractor. Make of Soft starter and Contactor shall be same make. Panel shall be brought on the site after approval of panel drawing by Engr-in-Charge. |
| 33 | (a)4 Nos bus bars of high conductivity aluminium alloy, 4 Nos for phase (R,Y,B,N) rating 150 Amp rating 50 KA. |
| 34 | (b) 09 Nos LED Indicators for RYB as phase indicator, 04 Nos Indicator for On/Off indication, 02 Nos Indicator for Triping indication,415 V, 50 Hz, Surface mounted with Surge & Low volatge glow protection Make- L&T |
| 35 | (c) Incomer 4 pole MCCB 40A- 01 Nos Ics=100%Icu , 25 KA with Protection against overloads:Conforms to IS/IEC 60947-2 , lr adjustable from .67 to 1 x ln, Adjustable short-circuit settings: 6 - 12 x In*, Compact sizeMake:- L&T/Legrand/Siemens/ABB |
| 36 | (d)Soft Starter as per IEC 60497-4-2 suitable for 20HP Submersible Pump 15 KW,30 Amp Rated current , Three-phase controlled, Operational voltage: 208 – 690 VAC , Wide rated control supply voltage: 100 – 250 V 50/60 Hz, Both in-line and inside-delta connection, Coated circuit boards protecting from dust, moist and corrosive atmosphere, Detachable keypad rated IP66 (4X outdoor), Built-in bypass for energy saving and easy installation, Built-in Modbus RTU for monitoring and control, compatible /Support for all major communication protocols, Analog output for measurement of current, voltage, power factor etc. including communication accessories to connect existing scada system and overload relay compatible to soft starter etc.Qty-01 NosMake:- ABB Cat Part No PSE30-600-70/Legrand/Siemens |
| 37 | (e)Soft Starter IEC-60947-4-2 suitable for 12.5HP MonoblockPump 11 KW,25 Amp Rated current , Three-phase controlled, Operational voltage: 208 – 690 VAC , Wide rated control supply voltage: 100 – 250 V 50/60 Hz, Both in-line and inside-delta connection, Coated circuit boards protecting from dust, moist and corrosive atmosphere, Detachable keypad rated IP66 (4X outdoor), Built-in bypass for energy saving and easy installation, Built-in Modbus RTU for monitoring and control, compatible /Support for all major communication protocols, Analog output for measurement of current, voltage, power factor etc. including communication accessories to connect existing scada system and overload relay compatible to soft starter etc. Qty-01 NosMake:- ABB Cat Part No PSE25-600-70/Legrand/Siemens |
| 38 | (f) 3 Pole power Contactor with auxilary /add on blocks as required and suitable to 20 HP Submersible Pump -01 Nos and 12.5 HP Monoblock pump for bypass arrangement of Soft Starter Make:- L&T/Schnider/Siemens/ABB |
| 39 | (g) Start Push Button & Stop Push Button for each Motor |
| 40 | (h) Voltmeter -02 Nos , Ammeter-02 Nos Multifunction Meter LED ,Accuracy Class 1, with V, A, F, PF, kW, kVA, Old energy, On and Run hours, site selectable kWh/ kVAh including suitable size of CTs etc Make - Legrand/L&T/Schneider |
| 41 | Supply and lay MS Pipes flanged typeof size 50mm dia heavy grade with all fittings laid in floors or fixed to walls and ceilings etc of sizes as shown complete all as specified and directed. |
| 42 | Supply & Fix in repalcement Motor Control Panel made of 2mm thick CRCA Sheet single door indoor type with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finishand factory assembled, The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-54 , front side double door type with locking arrangementand nut bolt fitting for back side, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber. The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars. Note: Earthwork and PCC work shall be measured and paid seperately. Cost for dismantling of existing panel , its all cable connection and reconnection all connections after fixing new one complete all as specified and directed.Note: (i) Panel Drawing alongwith line plan of complete control wirring of accesories shall be submitted by contractor. Make of Soft starter and Contactor shall be same make. Panel shall be brought on the site after approval of panel drawing by Engr-in-Charge.(ii) Height of panel is except canopyControl wiring of the panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured and drawing of control wiring shall be provided duly laminated and fixed to the left/right side from inner side of the panel.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 0.6 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators and connected through Aluminium Busbar to busbar of panel and Alumnium busbar extension shall be provided for LT cable connections complete all as specified and as directed. The overall size of the panel shall not be less than 1000mmX300mmX1000mm (LxBxH).The panel shall be provided with and including following accessories:- |
| 43 | (a)4 Nos bus bars of high conductivity aluminium alloy, 4 Nos for phase (R,Y,B,N) rating 250 Amp rating 50 KA. |
| 44 | (b) 03 Nos LED Indicators for RYB as phase indicator, 02 Nos Indicator for On/Off indication, 01 Nos Indicator for Triping indication,415 V, 50 Hz, Surface mounted with Surge & Low volatge glow protection Make- L&T |
| 45 | (c)Incomer Manual Changeover 04 Pole 250Amps , 415V , 50 Hz,Terminal Shrouds, Source Separator and Phase Barriers included ,Staggered Terminals make cable termination easy, Suitable for horizontal as well as vertical mounting & Incomer 4 pole MCCB 250A- 01 Nos Ics=100%Icu , 25 KA with Protection against overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s, Protection against short circuits, lsd adjustable from 1.5 to 10 x lr , tsd adjustable from 0 to 0.5s , Inbuilt Instantaneous Protection , Option for In built or add on module for Earth Leakage Protection, Adjustable tripping: 0 - 0.3 - 1 - 3s, In built Display for Current Metering with accuracy of class 1, Internal Battery with battery measure function, Communication Ready via COMM Port, Logical Selectivity Ready (Zone Selective Interlocking), Dynamic Selectivity as per Selectivity Charts, In Built USB Port for Software Diagnosis, Suitable for Isolation. Qty- 01 NosMake:- L&T/Legrand/Siemens/ABB |
| 46 | (d)Soft Starter IEC-60947-4-2suitable for 75HP VT PumpMotor 55 KW,106 Amp Rated current , Three-phase controlled, Operational voltage: 208 – 690 VAC , Wide rated control supply voltage: 100 – 250 V 50/60 Hz, Both in-line and inside-delta connection, Coated circuit boards protecting from dust, moist and corrosive atmosphere, Detachable keypad rated IP66 (4X outdoor), Built-in bypass for energy saving and easy installation, Built-in Modbus RTU for monitoring and control, compatible /Support for all major communication protocols, Analog output for measurement of current, voltage, power factor etc. including communication accessories to connect existing scada system and overload relay compatible to soft starter etc. Qty-02 NosMake:- ABB Cat Part No PSTX105-600-70/Legrand/Siemens |
| 47 | (e) 3 Pole power Contactor with auxilary /add on blocks as required and suitable to 75 HP VT Pumps for bypass arrangement of Soft Starter Make:- L&T/Schnider/Siemens/ABB |
| 48 | (f) Start Push Button & Stop Push Button for 02 Motors |
| 49 | (g) Voltmeter -02 Nos , Ammeter-02 Nos , Multifunction Meter LED ,Accuracy Class 1, with V, A, F, PF, kW, kVA, Old energy, On and Run hours, site selectable - 01 Nos (For main incoming)kWh/ kVAh including suitable size of CTs etc Make - Legrand/L&T/Schneider |
| 50 | Supply, Installation, Testing and Commissioning of 4 Core XLPE 1.5 Sqmm armed Copper multistranded conductor Shielded cable for Communication of scada actuators etc complete all as speciifed and directed .Make - Havells/Polycab/Finolex |
| 51 | Supply, Installation, Testing and Commissioning of 6 Core XLPE 1.5 Sqmm armed Copper multistranded conductor Shielded cable for Communication of scada actuators etc complete all as speciifed and directedMake - Havells/Polycab/Finolex |
| 52 | Supply, Installation, Testing and Commissioning of 2 Core XLPE 1.5 Sqmm armed Copper multistranded conductor Shielded cable for Communication of scada actuators etc complete all as speciifed and directed.Make - Havells/Polycab/Finolex |
| 53 | Supply, installation, testing and commissioning of Cat6 - 8 pair unshielded twisted pair UTP lan armoured cable for Sensors complete all as specified and directed. Make : D Link/ Havells / Polycab/ KEI |
| 54 | Supply and lay High density polyethylene pipes (HDPE) as per IS-14333 of size 25mm dia of pressure rating 6 kgf/cm2 laid in trenches complete all as specified and directed. |
| 55 | Supply, Installation, Testing and Commissioning of 250 mm dia, Water Flow Meter as per BIS 12933, along with RS 485 communication, all necessaryinstallation accessories like gate valve, barrel piece, double nipple, elbows/bends etc with following specificationcomplete all as specified and directed:-Accuracy: - ±2.0% of readingFlow velocity range, m/s: - 0.02 - 5Output: - Two way isolated pulse output(pulse equivalent and output pulse canbe arbitrary programmed); two-wired system 4-20mA output.Maximum pipeline pressure, MPa / bar: - 25Ambient temperature range, °С: - 5 - 65Protection: - IP 68Technical Specification: - Less than 0.01 m/s starting velocity, Multi line 9 digital LCD accumulative flow and 4 digitalfor instantaneous flow, Date cumulative record and data acquisition function, Various of Units selected, includingCubic meter, USA gallon, Cubic feet and Liter, With the two way PT1000 temperature transducer, which can realizethe heat measurement.Display parameters: - Flow Rate, Totalizer - Forward, Reverse, Net, No of hours meter was installed, worked.Archives have record of Daily reading for 31 days and monthly reading for 32 Months.Note -1) Supply, wiring & testing, commissioning, programming of Water Flow Meter shall be carried out by authorizedsystem integrator of the provided makes. The engineer shall submit a letter from the OEM as proof of his being anauthorized system integrator of the OEM. The engineer shall also submit a signed report on original letterhead ofthe OEM that programming, wiring & testing, commissioning has been carried out by him.Make of item - UNIVERSAL SWITCH GEAR CONTROL /EMERSON/KROHNE MARSHALL/ YOKOGAWA ELECTRICPower Supply: - Lithium battery |
| 56 | S & Fix wafer type butterfly valve 50mm dia valve PN 1.6 as per IS 13095 with SG iron disccomplete all as specified and directed.Make-Sant/Zoloto/Kirloskar |
| 57 | Supply, installation, testing and commissioning of 15 mm dia Brass / SS, direct Acting / Diaphragm type pilot operated Solenoid Valve for air release with manual bypass arrangement along with all necessary installation accessories like gate valve, barrel piece, double nipple, elbows/bends etc. suitable for line pressure of 4 kg/sqcm complete all as specified & diected. Make: AVCON/ ROTEX/ DANFOSS/ SIEMENS/ SWITZER/ Universal Switch Gear Control |
| 58 | Supply, installation, testing and commissioning of 25 mm single phase motorised ball Valve for priming and with manual bypass arrangement along with all necessary installation accessories like gate valve, barrel piece, double nipple,elbows/bends etc. suitable for line pressure of 4 kg/sqcm complete all as specified & diected. Make: JOHNSON CONTROLS/ RITE TORK / EMTORK Universal Switch Gear Control |
| 59 | Supply, Installation, Testing and Commissioning of Pressure Switch in replacement along with all necessary installation accessories like GI barrel piece, double nipple etc. having range 0-6 sq cm. With Weather proof enclosure complete all as specified & diected. Make:DANFOSS / SWITZER / SIEMENS/ Universal Switch Gear Control |
| 60 | Disconnecting and taking out existing defective LT cables alongwith old size bricks etc of following sizes and setting aside for further disposal as diected ( Note: Excavation & earthwork will be measured & paid & separately) |
| 61 | (a) 4/6/2 Core XLPE armed 1.5 Sqmm Copper multistranded conductor, 2 Core 10 Sqmm , 4Core 10 Sqmm to70 sqmm 3.5 Core |
| 62 | (b) 3.5 Core 95 to 240 sqmm |
| 63 | Relaying serviceable LT UG cable of follwing sizesomplete all as specified and directed.Note - Excavation / earthwork, cable protection covers & sand cushioning will be measured and paid separately under respective item of sch A |
| 64 | (a) 3.5 Core 240 Sqmm to 3.5 Core 95 Sqmm |
| 65 | (b) 3.5 Core 35 Sqmm to 3.5 Core 70 Sqmm |
| 66 | (c) 4/6/2 Core XLPE armed 1.5 Sqmm Copper multistranded conductor, 2 core 10 sqmm to 4 Core 16 Sqmm |
| 67 | S & Fix LT heat shrinkable straight through joint for XLPE 2 Core PVC insulated copper armoured cable complete all as specified and directed |
| 68 | S & Fix LT heat shrinkable straight through joint for XLPE 4 Core PVC insulated copper armoured cable complete all as specified and directed |
| 69 | S & Fix LT heat shrinkable straight through joint for XLPE 6 Core PVC insulated copper armoured cable complete all as specified and directed |
| 70 | Supply and laying Burnt clay fly ash building bricks designation 75(Kg/cm2), laid in right angle along the cable, complete all as specified. |
| 71 | M& L for sand and lay for dry river sand filling in trenches for UG cable protection with a layer of 8cm deep before laying of cable and 15cm above the top edge of the cable of after laying of the cable complete all as specified and directed. |
| 72 | M&L for joint with rubber or fibre board gasket for flanged pipes and fittings including necessary excavation, returning and refilling complete all as specified and directed for following pipe sizes:- |
| 73 | (a) 200mm bore |
| 74 | (b) 250 mm bore |
| 75 | (c) 300 to 450 mm bore |
| 76 | S & F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws for scada valve as rain protection sheet complete all as specified and directed.Note :- MS Square pipes /Angel iron shall be paid seperately |
| 77 | S&F ultrasonic level transmitter at sump and overhead tank for measurement of level with following specifications;- Range : 0-8 meters, Accuracy : 0.5 % minimum, Supply Voltage : 24 V DC, Output : 4-20 mA , 0-10 V DC Make: Pepperl+ Fuchs / Nivelco / Siemens/ Banner |
| 78 | M&L for Floor/PCC/Footpath cutting through existing PCC/floor/Footpath approx size width 25cm X 90cmdepth as required for Realying/Laying of cable/ pipe etc and making good with and including earthwork and necessary excavation, complete material required to match with the existing one or with PCC 1:2:4 type B1 complete all as specified and as directed by Engineer-in-charge. |
| 79 | M & L for shifting of LT motor panel of motorzied valves including dismantling of all accessories of Panel alongwith its all accessories of any size any type and angle irons, PCCdemolition, disconnecting all connections of cables of any size/type and transportation from existing place to MES Store yard specified place all as specified and directed.Note: (a) Any damage of accessories shall be the responsibilty of contractor and repalcement against damged item shall be done by the contractor without any cost effect.(b) Earth work and PCC work shall be paid and measured seperately. |
| 80 | Supply & fix in replacement LT feeder pillar panel weather proof outdoor type double door, fabricated out of3.15 mm thick CRCAsheet with epoxy power coating of RAL-7035 ( Siemens Gray) shade with matt finishwith seven tank pre treatment process.The panel shall be fabricated by CPRI tested manufacturer only. The Panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof.All doors and covers shall be provided with cylindrical panel locks and shall be fully gasketed with neoprene rubber and shall be lockable.The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or as specified below. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment.The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured for indicators/ Meters etc. All joints and connection shall be done with galvanised or codmium plated high tensile nuts, bolts and washers.The Panel shall be provided with digital multifunction meter with cast Resign CTs & RYB LED indicating lamps at Incoming .The panel shall be provided with heavy duty ss cable glands of adequate size for incoming and all outgoing cables. The panel shall be provided with Busbar chamber and cable alley of suitable size. The single line circuit diagram showing the arrangements of circuit inside the distribution board shall be provided inside the panel door and covered with transparent laminated plastic sheet.The panel shall be provided with manufacturer\"s name plate, skull & bones danger notice board etc.The panel shall be provided with 04 Nos 50mmx50mmx6mm thick angle iron supports of not less than each 0.9 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement.All terminals shall be provided with spreader links with phase separators on both sided and suitable for incoming cables complete all as specified and as directed.The overall size of the panel shall not be less than 900mmx400mmx900mm (LxDxH). The panel shall be provided with and including following accessories :-Note : PCC and Earthwork shall be measured and paid sepeartelya) Aluminium bus bars 400 amps, 50KA rating suitable for 3 phase 4 wire system for connection of 6 Nos LT Cables for 240 Sqmm size 02 Nos, 150 Sqmm -02 Nos, 120 Sqmm - 01 Nos, 95 Sqmm - 01 Nosb) On load change over switch four pole with advance Neutral 400 amps current rating open execution conforming to IS 13947 (part-3) Make - L&T/Havells/C&S Qty-01 Noc) Voltmeter -01 Nos , Ammeter-01 Nos Multifunction Meter LED ,Accuracy Class 1, with V, A, F, PF, kW, kVA, Old energy, On and Run hours, site selectable - 01 Nos (For main incoming)kWh/ kVAh including suitable size of CTs etc Make - Legrand/L&T/Schneider |
| 81 | M & L for shifting of Control panel of motorzied valves including dismantling of all accessories of Panel alongwith its all accessories of any size any type and angle irons, PCCdemolition, disconnecting all connections of cables of any size/type and installation, testing ,refixing the all accessoies and reconnecting of existing cables etc and transportation from existing place to specified place all as specified and directed.Note: (a) Any damage of accessories shall be the responsibilty of contractor and repalcement against damged item shall be done by the contractor without any cost effect.(b) Earth work and PCC work shall be paid and measured seperately. |
| 82 | Taking out of borewell submersible pump of any type and capacity upto 12.5 HPalongwith column pipe and 3 core flat cable complete after disconnecting of all electric and water line connectionforany make of pump & motor up to 170mtr complete all as specified and directed |
| 83 | Dismantling of borewell submersible pump bowl assembly of any make and capacity and size complete( to be measured only after lifting carefully without damaging any parts of the pump and setting aside in Pump house/specified nearest location of ascertaining the serviceability of existing dismantled parts including reassembling pump complete all as specified and directed with the following works :-(a) Cleaning of completepump assembly parts, discharge case,impeller , Shaft suction casing bowls disc & bearing etc.(b) Checking of all rotary and statutory parts of pump bowl & stage casing assembly and making free for their satisfactory run, rewinding and reinsulation of motor winding and making it serviceble.(Note : cost forreplacement of minor spares i.e.rubber \"O\" ring , oil seal, upper bush, motor bush and thrust bearing etc. is deemed to be included in the item rate). |
| 84 | Lowering down of borewell submersible pump of any type and capacity upto 12.5 HPalongwith UPVC column pipe and 3 core flat cable complete including (rethreading to GI pipe if required) and reconnecting of all electric and water line connectionforany make of pump & motor up to 200mtr complete all as specified and directed.Note: Column pipe and Submersible cable measured and paid seperately. |
| 85 | Servicing/repair maintenace of Motor Control panels VT pump Control Panel/Sewage Pump Control Panel/Centrifugal Motor Control Panel/Submersible Motor ControlPaneletc complete all as specified and directed:-Scope of work shall be comprising followingactivities:-(a) Troubleshooting and finding of fault of control panel installed at Pump House etc, Servicing and maintenace/repairs and replacement of defective components/ spare parts of control panels including checking of all accessories contactors, timers, relays VMR etc. installed at Pump Houses/Swimming pool/Sewage Pumps.(b) To attend break down maintenance immediately and replacement of unservicable spare parts within 24 hours as required at site as directed by AGE/JE.(c) All minor components/spare parts replaced included in this item i.e. connector/Copper Lugs/ Aluminium Lugs/ Nut Bolt etc / reconnecting burnt Cable connections etc and its cost deemed to be included in the unit rate quoted in item. |
| 86 | Supply & fix in Microcontroller-based water level control system complete with automatic and manual operation, designed to monitor and control tank water level using a suitable water level sensor for RCC Overhead tanks Approx height of tank shall not be less than 18 Mtr . The system shall include a microcontroller ,SMPS power supply, relay/contactor outputs, and all internal wiring, suitable for 2 nos. motorized on/off valve actuators with matching valves shall be provided for inlet/outlet control. A 2-line HMI/LCD display shall be mounted on the panel for real-time status of water level, valve status, cycle count, and system. Manual OPEN and CLOSE push buttons shall be provided for each valve along with Auto/Manual mode selection. The control logic shall support programmable four (4) ON/OFF operating cycles for the valves. An industrial 4G LTE modem with antenna shall be included for remote monitoring android app, and data communication. The system shall be complete with all necessary terminals, cables, accessories, testing, and commissioning, ready for operation as a turnkey solution and including 4g Modem, Adroid App, Programming, Configuartion etc complete all as specified and directed by Engr-in-charge. |
| 87 | S&F of CI/DI bend (any type, radius and angle), tapers any type, Flanges, straight bend including decreasing or double socket etc; tee pieces, tail peiecessingle branch, flanged adapter, \"Y\" junction, all sockets or socket and spigot or flanged, collars, caps and plugsfor spigot socketed pipes of upto 150mmsizecomplete all as specified and directed. |
| 88 | S&F UPS input 220Volt - 240 Volt , 50/60HZ with 8.7A Single Phase and Out put 220Volt-240 Volt , 50/60HZ with 5.21A Single Phase, Capacity 2000VA/1200W as per IS 16242(PArt1) and IEC 62040-1 including taking down existing one complete all as specified and directed. |
| 89 | Dismantling of Scada valve of size from 50mm to 450mm including its electrical connection and connected items , setting a side andrefixing the same including gaskits,nut bolt washers etc with new one complete all as specified and directed. |
| 90 | Taking out existing CI/DI pipe line, of any class including CI fitting with spigot and socket ends/ flanged end and lead joint including burning out lead joints and recovering lead for reuse in new CI pipes/fittings of any class/type complete all as specified and directed of foloowing sizes:- |
| 91 | (a) 80mm bore |
| 92 | (b) 100 mmbore |
| 93 | (c )150 mm bore |
| 94 | (d) 200 mm bore |
| 95 | (e) 250 mm bore |
| 96 | Relaying ofCI/DI pipe including fittings with spigot and socketed end/ flanged end, centrifugally cast laid in trenches after cleaning internally and externally, drawing out forigen material/rust complete with and including new titon joint for fixing of pipe complete all as specified and directed for following sizes:-Note :- (i)Earth work, joints and CI specials/fittings of the pipes shall be measured and paid separately under appropriate item. |
| 97 | (a) 80mm bore |
| 98 | (b) 100 mmbore |
| 99 | (c )150 mm bore |
| 100 | (d) 200 mm bore |
| 101 | (e) 250 mm bore |
| 102 | M&L for mild steel framed work for made of angle iron with and including mild steel sheet as required including necessary welding, cutting, hinges, locking arrangments, flanges for connection of GI Pipes with CI pipes and its nut bolts etc including painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 103 | S & F HMI 3V DC Battery round typesuitable to existing system or as per OEM recommended complete all as specified and directed. |
| 104 | S&F FRLS PVC Insulated Single Core Unsheathed Industrial Flexible Cable conforming to IS 694:2010 with Bright Annealed Copper Conductor for Voltage Grade 1100 Volts of following sizesincluding taking down existing one and saddling wherever required complete all as specified and directed:- |
| 105 | (a) 10 Sqmm |
| 106 | (b) 16 Sqmm |
| 107 | (c) 25 Sqmm |
| 108 | (d) 35 Sqmm |
| 109 | (e) 50 Sqmm |
| 110 | M&L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in copping/supports and similar work including necessary form work for control panel etc including dismantling exiting one complete all as specified and directed. |
| 111 | Supply and lay High density polyethylene pipes (HDPE) as per IS-14333 of size 50mm dia of pressure rating 6 kgf/cm2 laid in trenches complete all as specified and directed. |
| 112 | Deduct Schedule of credit (calculation will be done off line) Rs. 145050.00 |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail