| 1 | Taking down carefully aluminium / copper point wiring (light, fan, socket, powerpoint) including batten, conduit and fittings such as switches, ceiling rose, sockets, brackets, light fittings, switch board etc removing, making good distrubed surfaces of wall, floor, ceiling etc complete all as specified and directed. |
| 2 | M&L for point wiring with 1.5 sqmm cable PVC unsheathed and insulated copper multistranded conductor (FRLS) 1100 Volts grade cable (red colour cable to be used for phase connection and black colour cable to be used for neutral connection) including PVC concealed conduit medium grade with all accessories including 1.5 sqmm copper multistrand conductor (FRLS) 1100 Volts grade unsheathed PVC insulated (green colour) continuity earth wire connected to common earth dolly and sunk cast pressed steel terminal box made out of MS sheet for mounting of fittings like switch, socket and fan regulator with 3 mm thick hylum laminated sheet cover incl cutting chases pinning in, for concealed conduit wiring and making goods of disturbed surface not exc 15 cm girth complete all as specified and as directed for the following:- Note: Cutting and chasing deemed to be included in coated rate. |
| 3 | Light/Fan/Exhaust fan/Bell point |
| 4 | 5 amp socket on same boared |
| 5 | 5 Amp switch socket on Independent Board. |
| 6 | All as per item No 2 here in before but 4.0Sqmm P.V.C insulated un sheathed cable with stranded copper conductor for 5 pin 6/16 Amp switch socket combination on independent board complete all as specified and directed. |
| 7 | S&F for socket only 3 pin, 5 Amps flush type 230/240 V complete all as specified and as directed .( For same Board only) |
| 8 | S&F for switch socket combination 2 in 1, 5/6 Amps flush type230/240 V complete all as specified and directed. |
| 9 | S&F for switch socket combination 3 pin, 15/16 Amps flush type 230/240 V complete all as specified and directed. |
| 10 | S&F for ceiling rose 3 phase/PVC/polycarbonate,isolated body,surface type with ISI marked complete all as specified and as directed, |
| 11 | S&F for switch piano flush type 5/6 amps , 240 volt single pole one way complete all as specified and directed. |
| 12 | S&F for Step type electronic fan regulator flush type230 volt 5 speed control and connecting up and fix position complete all as specified and directed. |
| 13 | S&F for bell push piano flush type, 5/6 amps, 240 volt, single pole complete all as specified and directed. |
| 14 | S&F for buzzer/ ding dong bell, AC 230 volt, single pole complete all as specified and directed. |
| 15 | S&F in repair of wall decorative ultra slim LED 18/20 Watt, 230 volts, 50 Hz, 4 feet, lighting fixture with extruded polycarbonate lighting fixture, environmental friendly, energy efficient ready to use pack including lamp complete all as specified and directed.Cat Part No : Crompton TCS-108-20-65-SL-DP-NWH. |
| 16 | S&F in repair of ultra slim LED batten 10 Watt, 230Volts, 50 Hz, decorative ultra slim LED lighting fixture with extruded polycarbonate, environmental friendly including lamp, connection wire complete all as specified and directed.Cat Part No : Crompton TCS-108-10-65-SL-DP-NWH. |
| 17 | S&F for LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.Cat Part No : Crompton TCS-145-36-65-SL-DP-NWH. |
| 18 | Taking down old serviceable LED light of any type and refixing it in its original or new location existing bldg complete all as specified and directed. |
| 19 | S&F for building security light LED type of minimum 3500 Lumens (35watts) pressure die cast aluminium housing IP 66 protection with all accessories internally prewired and including connecting up with twisted copper conductor cable of suitable size including bracket made of 32mm dia GI light grade pipe of 1.2m long bent to shape fixed with suitable MS clamps, bolts, nuts and washers duly painted including taking down old fittings complete all as specified and directed.Cat Part No : Crompton ERP-427-35-57-HL2-LM-NBK. |
| 20 | S&Fin repair of factory made sheet metal enclosure for DBs double door, TPN, 415 volt,4 Way, IP-42 protection with bus bar, neutral link, earth link complete all as specified and directed. |
| 21 | S&F in repair of factory made sheet metal enclosure for DBs double door, SPN, 240 volt,8 Way, IP-42 protection with bus bar, neutral link, earth link complete all as specified and directed. |
| 22 | S&F in repair of factory made sheet metal enclosure for DBs double door, SPN, 240 volt,4 Way, IP-42 protection with bus bar, neutral link, earth link complete all as specified and directed. |
| 23 | S&F in repair of 240V, 10KA \"C\" curve miniature circuit breaker (MCB) SP 10 to 32 Amp current carrying capacity complete with connection testing complete all as specified and directed. |
| 24 | S&F in repair of 240V, 10KA \"C\" curve miniature circuit breaker (MCB) SPN 32-40 Amp current carrying capacity complete with connection testing complete all as specified and directed. |
| 25 | S&Fin repair of 240V, 10KA \"C\" curve miniature circuit breaker (MCB) TPN 63 Amp current carrying capacity complete with connection testing complete all as specified and directed. |
| 26 | S&F in replacement of Factory made sheet metal enclosure for VTPN DBs double door (Fixed flush to the wall), suitable for 125 Amps MCCB as incommer & outgoing as TPN 415 volt,4 Way, IP-43 protection with 200 Amp rated bus bar and 4.0Sq. mm copper PVC sheathed cable for earth continuity and suitable for having MCB’s complete all as specified and directed.Note :- MCCB/MCB will be paid separately under individual item of this schedule. |
| 27 | S&F in repair of sheet metal enclosure, single pole and neutral with two pin and earth plug and socket, 20 Amps, 230 Volts, 50 Hz complete with one single pole MCB of 20 Amps, 10kA, 230 volts, 50Hz, C curve type complete all as specified and directed. |
| 28 | M&L in repairfor sub main wiring with 2 run of FRLS PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 4.0 sqmm alongwith one run of FRLS PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 4.0 sqmm as earth continuity conductor drawn through & including medium grade concealed PVC conduit complete all as specified and directed. |
| 29 | M&L in repairfor sub main wiring with 2 run of FRLS PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 6.0 sqmm alongwith one run of FRLS PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 6.0 sqmm as earth continuity conductor drawn through & including medium grade concealed PVC conduit complete all as specified and directed. |
| 30 | M&L for sub main wiring with 4 run of FRLS PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 6.0 sqmm alongwith one run of FRLS PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 6.0 sqmm as earth continuity conductor drawn through & including PVC casing caping medium grade complete all as specified and directed. |
| 31 | S&F in repair of 415V 16KA curve MCCB TPN 125 Amps current carrying capacity complete with connection testing complete all as specified and directed. |
| 32 | M&L for Earthing complete with GI plate electrode 600x600x6.30mm thick, buried directly and preferably vertically in ground(earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected with Galvanize earth wire 4 mm diaby means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No 3, connected to earthing with DBs all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber & RCC 1:2:4 type B1 cover 40mm thick, with 8mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways,20mm dia GI medium grade pipe for watering , water funnel complete all as specified and testing on completion. |
| 33 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified and directed. |
| 34 | M&L for cable jointing kit for 11KV (Earthed) grade cable, straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 95 sqmm, 3 core XLPE armoured aluminium conductor cable and testing complete including cutting of old joint complete all as specified and directed. |
| 35 | S&F for cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed. |
| 36 | S&F for cable jointing kit for 11 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed. |
| 37 | Excavation in trenches not exceeding 1.50 mtr wide and n.exc 1.50 mtr deep for taking out/ laying of under ground cable, pole, pipe, stay and getting out in soft soil strata including making good to the disbturbed surfaces such as hardstanding, footpath/ pavments complete all as specified and directed. |
| 38 | Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cm spread any type of soil complete all as specified and directed. |
| 39 | Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.50 mtr above the starting point complete all as specified and directed. |
| 40 | M&L for sand cushioning to under ground cable provided with a layer of sand 8 cm depth before laying of cable and 15 cm depth after laying and stretching the cable complete all as specified and directed.Note: Punned thickness of sand shall be measured & paid. |
| 41 | Supply and laying un-reinforced precast concrete cable cover, class HVP, type 2 with peak, size 450mm x 180mm x 40mm complete all as specified and directed. |
| 42 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure under 3.0mtr below the ground level with out distrubing the tarmac area complete all as specified and directed. |
| 43 | M&L for precast cable route indicatorof size 100x30x10 Cms by using 20 mm graded aggregate type B11;2;4for cable indicator and engraving as \"HT CABLE\" slightly round from one side incl Red painting with two coat of synthetci enamel paint of a coat of primer complete all as specified and directed. |
| 44 | Material and labour laying well burnt old sizebricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection all as specified. |