| 1 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 2 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 3 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 4 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 5 | 5/6 A switch |
| 6 | 15/16 A switch |
| 7 | 3 pin 5/6 A socket outlet |
| 8 | 6 pin 15/16 A socket outlet |
| 9 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 10 | Single pole (16A/20A) |
| 11 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) |
| 12 | 6 way (4 + 18), Double door |
| 13 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 14 | Supplying and fixing of 63A rating, TPN, 415V, 10 kA, \"C\" curve, miniature circuit breaker (MCB) suitable for inductive load of following poles along with GI enclosure with complete connections including all necessary accessories, testing and commissioning etc. as required. |
| 15 | Supplying and fixing of 40 amps, 415 volts,“C” curve TPN MCB in sheet steel enclosure, on surface or in recess with complete with connections, testing and commissioning etc. as required. |
| 16 | Supply,Transprtation, storing at site, shifting at work place, installation, Testing and commissioning of the followingrating Double Conversion UPS system with IGBT Technology with SNMP card, Interlink Cables and MS Rack to accommodate Battery externally as per specifications and complete in all respects.The scope also includes Installation, Testing and Commissioning of Sealed Maintenance Free lead acid Batteriescomplete with intercell connectors & copper cables, Battery breaker, battery stand made out of Powder Coated MS Angles with adequate supports to carry the load of the batteries.& also TVSS at the input of each UPS to protect against transients, surges & Noise as per the tender specifications |
| 17 | Supply, installation, Testing & commissioning of 10 kVA Double Conversion UPS system with IGBT Technology with Input 3 Phase 4 Wire415 V± 10 & 3 Phase 4 Wire 415V AC Output ± 1% AC UPSwith Isolation Transformeralong with suitable battery set 20 Nos (12V, 42AH) batteryback up 30 minutes with complete connection cables, Rack, accessories, etc., as instructed/directed by engineer incharge.(Make : Numeric, Model No. :HPi 33 EVO) or equivalent model of other makes in the tender. |
| 18 | Supplying and fixing following size/ modules, PVC box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 19 | 06 Module |