| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.(a) Group C |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(a)2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(b)2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (a) 4 way (4 + 12), Double door |
| 5 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) Single pole |
| 6 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(b) Triple pole and neutral |
| 7 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required(a) 8 Module (125mmX125mm) |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(a) 5/6 A switch |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(b) 15/16 A switch |
| 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(c) 3 pin 5/6 A socket outlet |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(d) 6 pin 15/16 A socket outlet |
| 12 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)(a) 24-26 watt |
| 13 | Dismantling of Existingdamage conduit ,casingcapping wiring ,light fittings, switch board ,Panel etc. with all accessories on surface & recesse of wall/celling & mending good the damages to original finish incl painting etc.at entire campus as reqd. |
| 14 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.(a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 15 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 16 | Supplying of aluminium conductor PVC insulated, PVC sheathed/ XLPE insulated inner sheathed steel strip armoured power cable of 1.1 KV grade conforming to IS:7098(Part-I) 1988 or latest amended following sizes etc .(a) 4X 95 Sqmm |
| 17 | Supplying of aluminium conductor PVC insulated, PVC sheathed/ XLPE insulated inner sheathed steel strip armoured power cable of 1.1 KV grade conforming to IS:7098(Part-I) 1988 or latest amended following sizes etc .(b) 4X 50 Sqmm |
| 18 | Supplying of aluminium conductor PVC insulated, PVC sheathed/ XLPE insulated inner sheathed steel strip armoured power cable of 1.1 KV grade conforming to IS:7098(Part-I) 1988 or latest amended following sizes etc .(c ) 4x 35 sqmm |
| 19 | Supplying of aluminium conductor PVC insulated, PVC sheathed/ XLPE insulated inner sheathed steel strip armoured power cable of 1.1 KV grade conforming to IS:7098(Part-I) 1988 or latest amended following sizes etc .(d ) 4x25 sqmm |
| 20 | Supplying of aluminium conductor PVC insulated, PVC sheathed/ XLPE insulated inner sheathed steel strip armoured power cable of 1.1 KV grade conforming to IS:7098(Part-I) 1988 or latest amended following sizes etc (e ) 4x16 sqmm |
| 21 | Supplying and fixing 25Amodular AC motor statrer on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(f ) 4x10 sqmm |
| 22 | Laying and fixing ofoneNo. PVCinsulated & PVCsheathed/XLPE al conductorcable of1.1KV grade of following size on the wall surface as reqd.(a)Above 35 sqmm and upto 95 sqmm (clamed wih 25x3 mm MS flat clamp) |
| 23 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.(a) Above 35 sq. mm and upto 95 sq. mm |
| 24 | Laying of one no PVC insulated and PVC sheetedpower cable with7/18 stay wire with sutable clampas required for cable size (a) Above 35 sq. mm and upto 95 sq. mm |
| 25 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.(a) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 26 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required(a) Upto 35 sq. mm |
| 27 | Laying of one no PVC insulated and PVC sheetedpower cable with7/18 stay wire with sutable clampas required for cable size (a)Upto 35 sq. mm |
| 28 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 29 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.(a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 30 | Supplying and fixing of light class G.l. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required |
| 31 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(a) 4 x 50 sqmm (35mm) |
| 32 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(b ) 4x 35 sqmm (32mm) |
| 33 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(c) 4 x 25 sqmm (28mm) |
| 34 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(d ) 4X16 sqmm (28mm) |
| 35 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(e ) 4x10 sqmm (25mm) |
| 36 | Supplying and fixing 250 mm x 200 mm x 105 mm outdoor SMC PVC junction box along with supply and fixing of required connector terminals. |
| 37 | Supplying and fixing270 mm x 225 mm x 135 mm outdoor SMC PVC junction box along with supply and fixing of required connector terminals. |
| 38 | Fabrication, supplying and istallation of out door typefloor mounted MV3 phase 4 wire 50 Hz ACFeeder Pillar distribution boardof size 1000 mm x 900 mm x 300mm fabricatedwith2.00 mm (SWG-14) sheet steel for frame work and cover, angle iron legs of 450 mm in length in brick foundation with net plaster finishing, cable gland plate including cleaning and finishing with powder coated painting complete having 200 amps capacity TPN aluminum alloy bus bar, including bus bar support, both side hinged doors with locking arrangement, ventilation, cable termination plate, 2 No. earth studs withSupplying and fixing the following units including internal connection with contol wires of following MCCBs(a) 125 A, 36KA 4 pole MCCB - 1 No(b) 63A FP MCB- 2 nos(c) 40 A FP MCB - 1 no |
| 39 | Fabrication, supplying and istallation of out door typefloor mounted MV3 phase 4 wire 50 Hz ACFeeder Pillar distribution boardof size 1000 mm x 900 mm x 300mm fabricatedwith2.00 mm (SWG-14) sheet steel for frame work and cover, angle iron legs of 450 mm in length in brick foundation with net plaster finishing, cable gland plate including cleaning and finishing with powder coated painting complete having 200 amps capacity TPN aluminum alloy bus bar, including bus bar support, both side hinged doors with locking arrangement, ventilation, cable termination plate, 2 No. earth studs withSupplying and fixing the following units including internal connection with contol wires of following MCCBs(a) 125 A, 36KA 4 pole MCCB - 1 No(b) 63A FP MCB-3 nos(c) 40 A FP MCB - 1 no |
| 40 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life endsas per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).(a) 45 Watt |
| 41 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 42 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required |
| 43 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 44 | Less Credit for Old 1.5/2.5/4 sqqmmwire from Engineering Section |
| 45 | Less Credit for Old tube light |
| 46 | Less Credit for Old Ceiling Fan |