| 1 | Attending the complaints of unserviceable LED street light/high mast light fitting comprising of 45W/ 60W/ 80W/160 Watt of any make any model fitted on the pole at any height with any type of fixing arrangement by taking down and checking loose connection in FRP box/ ACSR conductor or street light and making it serviceable and refixing itto the proper height and removing hanging grasses etc and tightening of all nuts,bolts,clamps and fixing of the street light at proper direction all as directed by Engineer- in- charge. |
| 2 | Attending the complaints of unserviceable high mast light fitting comprising of 80W/160 Watt flood lights of any make any model fitted on the pole at any height with any type of fixing arrangement by taking down and checking loose connection making it serviceable and refixing itto the proper height and tightening of all nuts,bolts,clamps and fixing of the street light at proper direction all as directed by Engineer- in- charge. |
| 3 | M&Lin repair of surge protection device (SPD) Suitable for 45 watt LED street light complete all as per directed |
| 4 | M&Lin repair of driver suitable for 45 to 60 watt LED street light complete all as per directed |
| 5 | M&Lin repair of driver suitable for 80 watt LED flood light complete all as per directed. |
| 6 | M&Lin repair of surge protection device (SPD) Suitable for 160 watt LED street light complete all as per directed. |
| 7 | M&Lin repair of Driver Suitable for 160 watt LED street light complete all as per directed |
| 8 | Supply and fixing bracket made out of GI tubing light grade 25mm dia, 1.5 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron of size 25x4 mm with suitable nuts and bolts for holding/fixing of bracket on steel pole including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge. |
| 9 | M&Lin repair automatic street light timer switch using infrared sensor based for single phase & three phase timer completeincluding taking down old unserviceable switch all as per directed. |
| 10 | Supply and fix in replacement power contactor 25 to 32 Amps,for single phase for automatic street light timer complete all as per directed. |
| 11 | Supply and Fix in replacement power contactor 32 to 40 Amps, for three phase for automatic street light timer complete all as per directed. |
| 12 | S&F in replacement PVC insulated multi stranded aluminum conductor cable sheathed 4 sqmm two core and making connections of street light , flood light etc. complete all as directed. |
| 13 | M&L in repair Hot moulded (FRP) junction box of size 250mm x 200mm for street light pole with locking arrangementwith 32 Amps, 4 way heavy duty terminal block suitable connection for three phase incoming cable three phase outgoing cable and single phase connection for light fittings including MCB SP 10 Amps 01 Nos enclosed in thermoplastic box in closed shock proof safe IP 65, weather, vermin proof, dust and water proof complete with two number cable entryglandof standard size with suitable size mild steel clamps to fix on pole complete all as specified and directed by Engineer-in-Charge. |
| 14 | S&F in replcement of copper conductor multistranded 1.5 Sqmm 2 core 1100 volts grade complete all as specified and directed. |
| 15 | M&L in replacemet twin core 6 sqmm nominal cross sectional area multistranded aluminium conductor cable over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated complete all as specified and directed. |
| 16 | Excavating in trenches,not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out soft/loose soil including returning filing and removal of soil and making good disturbed surfaces complete all as specified and directed |
| 17 | Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm all as specified and directed. |
| 18 | Removing the excavated soil from the trench n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point all as specified and directed. |
| 19 | Boring/Drilling (horizontally) manually under existing road, pavement, hard standing suitable for passing GI tubing of 40 to 80 mmbore complete all as specified. |
| 20 | M&L fo supplying and fixing galvanised mild steel pipe /tubing of size 40 to 80 mm bore dia, light grade complete with all fittings, laid in trenches / under roads, drain, paths, fixed to poles/ walls with clamps , bolts , nuts and washers complete all as specified and directed. |
| 21 | Supply and laying double wall corrugated pipe (DWCP) of outer /inner dia 77/63 mm for undergroundXLPE LT cable upto size 16 Sqmm, Non-metallic, resistance to compression : type 450, resistance to impact; normal, resistance to bending: pliable, resistance to external influence; ingress protection: IP 67, resistance against corrosion: without protection, resistance to flame propagation: non flame propagating,conforming to IS-16205 (part-24) 2017 including necessary jointing material i.e snap fit coupler with rubber ring, sealing plug, tees, bend, angel bend etc for passing electrical cable complete all as specified anddirected by Engr - in charge. |
| 22 | Supply and fix in replacement three phase of 5 KW automatic street light switch using Street light timer switch multi functional digital for automatic switching on & offof street lights at a preset time along with suitable three phase power contactor of 32 to 40 amps current rating,incommingMCB TPN and outgoing TPN MCBs of 32 to 40 Amps and, size of circuit should be multistranded FRLS min size of 6 Sqmm, selection operation should be enclosed in a pole/wall mounted enclosure made of rust proof, electric shock proof termite proof and FR grade special mounting compound conforming to IP 54 complete all as specified and directed. |
| 23 | M&L for servicing the raising and lowering mechanism of high mast light with opening the gear box and greasing of all movingparts for smooth functioning of raising and lowering of the lantern carriage for maintenance purposes complete all as specified and directed. |
| 24 | Cutting, Trimming of tree branches around 3 meter from over head conductor with necessary tools and ladders completed all as specified and directed. |
| 25 | M & L Painting of steel pole (swan neck type or straight type) up to 9 mtr heightwith cross arms, clamp of any length and shape for LT overhead line/ for street lightwith two coat of aluminium paint after scraching out old paint, cleaning and exiting surface rust free, preparation of the existing surface,including marking pole numbers in a 15 cm dia yellow circle with number writting with blacksyenthic paint/ Stricker, includingpainting strips in alternate from bottom to top with three strips of white syenthatic paint & two strips of Yellow/ black paint(as per existing pattern through out the circumference of pole, including removing extrapapdi by sand paper and makinggood and applying one coat of white washing on PCC copping of pole complete all as specified and directed. |
| 26 | M & L Painting to the PCC polesstrips in alternate from bottom to top with three strips of white synthatic paint & two strips of yellow/ black paint (as per existing pattern) through out the circumference of pole including one coat of lime wash on PCC copping of pole, two coat ofaluminium paint to channels, cross arm, clamps and pipes fixed/ mounted on pole after scraching out old paint, cleaning complete all as specified and directed. |
| 27 | S & Fin replacement pre-stressed cement concrete pole, 9 metre long of cross section 102 mm x 172 mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678-1998 errecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in black and white colour upto 1.5 metre height from top of PCC pedestal/coping of poles complete all as specified and directed. |
| 28 | Restreching existing over head lines consisting following lines of ACSR and GI wire any size of 4/5 lines of ACSR conductor and tightening with aluminium binding wire of suitable size complete all as specified and directed. |
| 29 | S&F in replacement aluminium conductor, steel reinforced (ACSR) of any size, any type as per existing one and stringing properly on the insulators and binding with aluminium wire, connectors, jumpers etc complete all as specified and directed. |
| 30 | M&L in replacement of shackle type porcelain, vitreous brown insulator in repair including one galvanised MS strap of size 31x3 mm, 12mm dia insulator bolts washers and nut for 1100 Volts grade 75mm in height and 90mm dia including dismantling of unserviceable LT insulators pin/ shackle/ disc & loop type from existing OH lines complete all as specified and directed. |
| 31 | M&L for heat srinkable type straight through joint outdoor type for LT UG cable 10 to 16 sqmm 4 coreincluding excavation and earth work in any type of soil/ hard standing floor complete all as specified and directed. |
| 32 | M & L for PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation for stays & mass concrete including necessary form work and fair finishing completeall as specified and directed by Engineer-in-Charge. |
| 33 | M & L for PCC (1:4:8) type B-1 using 20 mm graded stone aggregate as in coping of poles etcincluding weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-Charge. |
| 34 | Supply, install, testing & commissioning of CPRI approved LT panel board, outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire , 50 HZ , AC supply system.The panel shall be factory made, double door outdoor type made out of 3..0 mm thick MS sheet totally enclosed dust, vermin & rust proof front operated, front & rear opening with locking arrangement fixed with MS angle iron frame of sie 50X50X6 mm and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable etc including taking down old unserviceable panel all as directed at site and comprising of the following:-(i)TPN 40 Amp - 01 No (ii)Timer switch for flood lights- 01 No(iii) Contactor 16 Amp 3 Pole- 03 No (iv) Rising and lowering push button with control wiring- 02 Nos |
| 35 | S&F in replacement aluminium bus bar fixed on insulators of suitable size and capacity as required at site complete all as specified and directed. |
| 36 | Surface dressing not exceeding 15 cm deep in soft/loose soil including cleaning of E&M installation premises, uprooting of tiny trees,tree cutting , cleaning , leveling ,spreading bushes, beeds, grass and removing poly bags, brick bats, stone pebels debris , Cleaningof sub station bldg , two pole / four pole structuire area , HT line etc complete all as specified and directed by Engineer in Charge. |
| 37 | Material and labour in replacement of existing rusted danger notice board with pressed vitreous painted plate fabricated out out of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamp bolts and nuts of approved size 20 X 15 cm size complete all as specified and directed. |
| 38 | M&L for stay assembly complete comprising stay cable of suitable size , stay bow 40 cm long, 14mm dia complete with accessories as shown in electrical plate No - 1 of SSR 2009 Part - 1 (on page 495), with and incl 20 mm dia, 1.8 mtr long galvanised stay rod with threaded ends, GI nuts, bolts , washers, thimbles with and incl 300mmx300mmx6mm stay plate, with and incl dismentling of existing damaged assembly, complete all as specified and directed by Engr-in-Charge. |
| 39 | M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI wire 4 mm dia as earthelectrode bolted or rivetted to earth plate at one end and connected to equipments at another end, 20 dia bore GI pipe \"light grade\" as water pipe from earth chamber to upper edge of earth plate, test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1 excavation, earth work complete all as specified and directed. |
| 40 | Supply, installation, commissioning and testing in replacement factory made LT feeder pillar box outdoor type CPRI approved suitable for 3 phase, 4 wire, 415 Volts AC supply, outdoor cubical type,dust and vermin proof powder coated, made out of 3.0 mm thick CRCA sheet with angle iron frame made out of MS angle 40 x 40 x 6 mm both side openable double door type with proper locking arrangements duly finished with using powder coated paint of approved colour over a coat of red oxide primer all over steel surfaces with 80 cm high angle iron legs welded on four corners of frame embedded in PCC 1:2:4 using 20 mm graded stone aggregate upto 25 cm foundation and proper glanding, lugs and nuts bolts etc for all cables and comprising of following accessories including disconnecting and taking down existing panel etc complete all as directed with sufficient working space with and including to accomodate the following accessories: -(a) Aluminium bus bar 200 Amps rating 3 phase 4 wire system.(b) Incoming:- MCCB 4 Pole 160 Amp 415 volts with breaking capacity 25 KA (c) Outgoings:- (i) MCCB 415 volts, 3 pole 100 Amps with breaking capacity 16 KA – 01 Nos.(i) MCCB 415 volts, 3 pole 63 Amps with breaking capacity 16 KA – 02 Nos (ii) SPN 32 Amp- 01 Nos(d) Digital multifunction meter with CTs – 01 Set. (e) LED type indicator for RYB – 01 Set |
| 41 | Supply only LT self adhesive PVC electrical insulation tape of size width 25 mm and25 mtr long complete all as specified and directed. |
| 42 | Attending the complaints of timer panel including timer and contactor of LED street light/high mast light fitting with checking loose connection or wiring and setting the time of timer in panel and making it serviceable complete all as specified and directed. |
| 43 | Supply and laying double wall corrugated pipe (DWCP) of size 90/76 mm (outer/inner) dia for LT cable upto size 70 Sqmm, Non-metallic, resistance to compression : type 450, resistance to impact; normal, resistance to bending: pliable, resistance to external influence; ingress protection: IP 67, resistance against corrosion: without protection, resistance to flame propagation: non flame propagating,conforming to IS-16205 (part-24) 2017 including necessary jointing material i.e snap fit coupler with rubber ring, sealing plug, tees, bend, angel bend etc for passing electrical cable complete all as specified anddirected by Engr - in charge. |
| 44 | All as per Item No 43 above but DWC pipe of size 120/103 mm (outer/inner dia) for LT cable of size upto 240 Sqmm. |
| 45 | M&L for cutting LT Cable armouredends of size 25 Sqmm to 50 Sqmm burn out old lugs 3 Phase & neutral any size and specificaion, preparing ends for connecting cable end aluminium tube terminals/lugs & dressing, crimping incliding MS nut bolts and washers of suitable size complete all as specified and directed. |
| 46 | All as per item No 45 above but size 25 Sqmm to 50 Sqmm |
| 47 | All as per item No 45 above but size 120 Sqmm to 150 Sqmm |
| 48 | All as per item No 45 above but size 185 Sqmm to 300 Sqmm |
| 49 | M & L for filling and spreading aggregate using 40 mm grade trap stone aggregate around LT panels etc. complete all as specified and directed. |
| 50 | Material and labour for painting of LT panel outdoor/indooroff sizes removing existing old paint with the help of sand/emery paper etc. Preparing surfaces externally including cleaning etc. Applying externally one coat synthetic enamel paint including cleaning and surface dressing upto 25 cm depth around 1 mtr of the panels complete all as specified and directed. |
| 51 | M & Lin repairs Insulator Pin type, pocrcelain , vitreous, white , brown or green, insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut , 100 mm height, 65 mm dia. For 1100 volts grade as per existing complete all as specified. |
| 52 | Disconnecting faultyLT cables of any size and any lengthfrom both ends hiring of cable fault detector machine to detect exact position of fault/ detecting of fault manually by excavation, removal of fault,Re-connections and testing of cables including excavation, returung filling, Removal, relaying of cable protection cover etccomplete as specified and directed.Note :(a) LT cable & joints shall be measured and paidseperately under respective items of schedule. (b)Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdownalongwith fault locating machine/manually through manpower. |
| 53 | M&L in repair of Mild steel cross arms, bracings, supports, clamps, and back plates fabricated from structural steel sections including nuts, bolts, washers , welding, bending, cold or hot , drilling holes for bolts , in any shape or size as indicated or directed and inclusive of one primer coat with red oxide Zinc Chrome and two coats of synthetic enamel paint all as specified and directed. |
| 54 | M&L in replacemet twin core 10 sqmm nominal cross sectional area multistranded aluminium conductor cable over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated complete all as specified and directed. |
| 55 | M&L for trimming of tree branches andRestreching existing LT/HT over head lines of ACSR and GI wire any size of 3/4/5 lines of ACSR conductor and tightening with aluminium binding wire of suitable size complete all as specified and directed. |
| 56 | M&L in replacement LT spacer in LT overhead line of ACSR conductor shall be made of high quality regid PVC,the spacer shall be water proof weather proof and shock proof the spacer shall also be suitable for use onboth horizental and vertically configuration of LT O/H line ACSR conductor 5 wire /4 wire system complete all as specified and directed. |
| 57 | M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end 20 dia bore GI pipe \"light grade\" as water pipe from earth chamber to upper edge of earth plate, test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1 completeall as specified and directed and testing on completion icl necessary earth work, (excavation, R&R removal also, complete all as specified and directed by Engr-in-Charge.Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 58 | Supply and erecting factory made 7 meter long hot dip galvanized (as per relevant IS with average coating thickness 65 microns) Octagonal poles conform to IS – 2062 / BSEN 10025 with 155 mm dia at bottom and 70 mm dia at top A/F made up of 3 mm thick HT sheet along with foundation type base plate of size 250x250x16 mm, foundation bolt 4 Nos of M20 x 600 mm high ‘J’ type EN8 grade, including 1 meter long hot dip galvanized single arm (swan neck) bracket made up of 40NB dia GI pipe and including excavation, earth work, PCC (1:2:4) type B1 for foundation and grouting the bolts as per manufacturer’s instructions including making pole number in letters & figures of size less than 10 cm height with red colour enamel paint complete all as specified and directed. Note : (i) Srl number will be issued by Engineer in charge. |
| 59 | Repair to LT panel by welding broken Lid including all material required for fabrication to repair LT panel including M&L forsupply andfixing with weldinghinges& locking arrangement frontsidecomplete all asspecified and directed. |
| 60 | Material and labour disconnecting faulty /burnt end or portion of cable from LT panel/LT pole /main switch/changeover etc byremoving the cable from loop including necessary excavation & earth work , cleaning the surface area not less than 1 mtr surrounding the panel/pole , provision of suitable size of thimble, LT tape , relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 16 Sqmm 3.5/4 core to 240 Sqmm3.5 core of LT cable to LT Panel/pole/main switch/changeover complete all as specified and directed. |
| 61 | M&L in replacement glow sign board sheet of size 3.00X1.00x 0.20 meter in good stencil cut including 2x20 watt LED Light inside and to be fixed on top of building/ground or angle iron structure complete all as specified and directed by Engr-In-Charge. Note: Name of subject in glow sign board to be discussed before ordering and will be as per the direction of Engr-in-Charge. |
| 62 | M&L in repair ofheat shrinkable typeend termination cable jointing kit, outdoor type, suitable for LT under ground earthed system 3.5 core XLPE cable of size 50 Sqmm to 50 Sqmm including making connections complete all as specified and directed by Engineer-in-Charge |
| 63 | All as per item No 62 above but of size 95 Sqmm to 120 Sqmm |
| 64 | All as per item No 62 above but of size 150 Sqmm to 185 Sqmm |
| 65 | All as per item No 62 above but of size240 Sqmm to300 Sqmm |
| 66 | Material and labour for cable route path indicators made out of precast PCC mark LT cable 1100 V having PCC pillar of size 700mmx220mmx80mm, embedded 300 mm below ground level with PCC 1:3:6 (Type C1 using 20mm above ground level incl colour paint for LT/HT as per rule and marking of LT/HT cable aboveground level complete excavation and earth work complete all as specified& directed. |
| 67 | Labour for repair/ servicing of air circuit breaker (ACB) of capacity 800 Amp by authorised mechanic and replace necessary items as required at site complete all as specified and directed. Note :- Spares will be measured and paid separately under appropriate items. |
| 68 | M & L in repair Air circuit breaker (ACB) of capacity 800 Amp, 50 KA complete all as specified and directed. |
| 69 | M & L in repair jaw contact of air circuit breaker (ACB) of capacity 800 Amp complete all as specified and directed. |
| 70 | M & L in repair pole assembly of air circuit breaker (ACB) of capacity 800 Amp complete all as specified and directed. |
| 71 | M&L for spreadingparaquat for destroys weeds and grasses complete all as specified and directed. |
| 72 | M&L in repair cable jointing kit for 1100 V (Earthed) grade cable for straight throughheat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor of size 16 Sqmm to 25 Sqmm including making good to all disturbed surfaces/flooring/road to match with existing specification complete all as specifiedand directed: Make: M-Seal/Birla 3M/Denson. |
| 73 | All as per item No 72 above but of size 35 Sqmm to 50 Sqmm |
| 74 | All as per item No 72 above but of size 70 Sqmm to 95 Sqmm |
| 75 | All as per item No 72 above but of size 120 Sqmm to 150 Sqmm |
| 76 | Labour only for attending the complaints/Job for interruption/defect in continuity of electric supply in electrical switchgears, LT Panels, feeder pillers, busbars, main switches etc for the following items complete all as specified and directed:-(i)Repairing of MCCB/TPN/SPN/MCB fault of any capacity(ii) Rewiring of LT panel, dressing/insulating exposed busbars & wiring, tightning of all nut bolts of bus bars connecting point etc except incoming and outgoing LT cable(iii)Internal cleaning for dust/spider web complete for smooth functioning of panel(iv) Dressing and insulating of exposed parts of incoming/outgoing LT cable end terminating joint 3.5/4 core of any capacity/type including reconnecting the same to circuit and making of incoming/outgoing feeder detail on cable byusing appropriate stencil and colour. |
| 77 | Supply, installation, commissioning and testing in replacement factory made LT feeder pillar box outdoor type CPRI approved suitable for 3 phase, 4 wire, 415 Volts AC supply, outdoor cubical type,dust and vermin proof powder coated, made out of 3.0 mm thick CRCA sheet with angle iron frame made out of MS angle 40 x 40 x 6 mm both side openable double door type with proper locking arrangements duly finished with using powder coated paint of approved colour over a coat of red oxide primer all over steel surfaces with 80 cm high angle iron legs welded on four corners of frame embedded in PCC 1:2:4 using 20 mm graded stone aggregate upto 25 cm foundation and proper glanding, lugs and nuts bolts etc for all cables and comprising of following accessories including disconnecting and taking down existing panel etc complete all as directed with sufficient working space with and including to accomodate the following accessories: -(a) Aluminium bus bar 1000 Amps current rating capacity 3 phase 4 wire system.(b) Incoming:- ACB 800 Amps 4 Pole 60 KA, 415V - 01 No.(c) Outgoings:- (i)MCCB 4 Pole 400 Amp, 415 volts with breaking capacity 50 KA - 02 Nos(ii) MCCB 4 Pole 315 Amp, 415 volts with breaking capacity 36 KA – 02 Nos. (Iii) MCCB 4 Pole 250 Amp, 415 volts with breaking capacity 36 KA – 03 Nos.(iv) MCCB 4 Pole 100 Amp, 415 volts with breaking capacity 25 KA – 01 Nos.(ii) MCCB 4 Pole63 Amp, 415 volts with breaking capacity 16 KA – 02 Nos.(d) (d)Digital multifunction meter with CTs – 01 Set.(e)LED type indicator for RYB – 01 Set |
| 78 | Supply, installation, commissioning and testing in replacement factory made LT feeder pillar box outdoor type CPRI approved suitable for 3 phase, 4 wire, 415 Volts AC supply, outdoor cubical type,dust and vermin proof powder coated, made out of 3.0 mm thick CRCA sheet with angle iron frame made out of MS angle 40 x 40 x 6 mm both side openable double door type with proper locking arrangements duly finished with using powder coated paint of approved colour over a coat of red oxide primer all over steel surfaces with 80 cm high angle iron legs welded on four corners of frame embedded in PCC 1:2:4 using 20 mm graded stone aggregate upto 25 cm foundation and proper glanding, lugs and nuts bolts etc for all cables and comprising of following accessories including disconnecting and taking down existing panel etc complete all as directed with sufficient working space with and including to accomodate the following accessories: -(a) Aluminium bus bar 300 Amps rating 3 phase 4 wire system.(b) Incoming:- MCCB 4 Pole 160 Amp 415 volts with breaking capacity 25 KA (c) Outgoings:- (i) MCCB 415 volts, 3 pole 100 Amps with breaking capacity 25 KA – 02 Nos.(i) MCCB 415 volts, 3 pole 63 Amps with breaking capacity 16 KA – 03 Nos (ii) SPN 32 Amp- 02 Nos(d) Digital multifunction meter with CTs – 01 Set. (e) LED type indicator for RYB – 01 Set |
| 79 | Supply, laying or passing through pipe, XLPE insulated armoured electric power UG cable with aluminium conductor 1100 volt grade, nominal cross-sectional area 185 Sqmm 3.5 Core including cable gland, terminal lug and testing complete all as specified anddirected. Note :-Excavation, earth work and DWC pipe shall be measured and paid separately under appropriate items. |
| 80 | Supply only copper lugs for MCCB of size 63 amp to 400 Amp of suitable size as per ground requirement for fixing LT cable of any size complete all as specified and directed. |