| 1 | Taking down/ Removing ofSplit ACs indoor and outdoor accessories and voltage stabilizers of any size from existing site and kept in MES store complete all as specified and directed. |
| 2 | Disconnecting all electric connections and dismantling the unsv package Air conditioners 11 ton / 8.75 ton capacity from the building including all ducts and accessories from site and transporting to E/M store all as specified and directed. |
| 3 | Taking down carefully unserviceable sub main wiring of any size and type including making good the disturbed surfaces of walls, ceilings etc including two coats of white /colour washing/ distempering etc to match the existing complete all as directed by EIC. |
| 4 | Supply and install hi wall split units air conditioner indoor/outdoorof capacity 2.0 TR complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2 complete all as specified and directed. (Make :- Blue Star/Carrier/Voltas) |
| 5 | Supply and install hi wall split units air conditioner indoor/outdoorof capacity 1.5 TR complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2 complete all as specified and directed.(Make :- Blue Star/Carrier/Voltas) |
| 6 | S&F Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA |
| 7 | S&F Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4 KVA |
| 8 | M & L for sub main wiring complete with two runs of 4 Sqmm single coreFRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories in surface of wall, roofs etc with one run of PVC insulated copper conductor 4Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed. |
| 9 | All as Srl item No. 8 but two single core 6 Sqmmand 6 Sqmm for earth continuous earth wire.(Note :- 2 runs of 6 sqmm single cable and one run of 6 sqmm earth wire cable incl PVC conduit 20/25 mm dia shall be considered as one unit/1RM |
| 10 | Taking down and S&Fdouble pole and neutral enclosure with two pin and earth plug and socket including 1NosMCB 20 Amps capacity complete all as specified and directed by Engr-in-charge |
| 11 | M&L for mild steel stand duly painted suitable for fixing 2/1.5 TR AC out door unit fixing in wall / floor, including making bore required size for copper pipe & copper cable with sweating pipe required size and length upto ground level complete all as spcecified and directed. |
| 12 | Supply and Fixing Air conditioning Changeover Timer Complete all as specified and directed. Note:(a) Timer should suitable for two Ac load upto 20 A. (b) Timer should available in two modes. (c) In Auto mode gap time 30 Minute, 1hr, 2hr,3 hrs, 4hrs. (d) Din channel mounting for easy installation. |
| 13 | Supplying and Fixing Copper refrigerant pipe Copper tube 5/8 \" x 1/4\" dia and connecting along with insualtion sleeves incl leak testing complete all as specified and directed. |
| 14 | Supply and fixing copper power cable of insulated, PVC sheathed , multistranded copper cable of 2.5sqmm 3 core, ISI marked, 1100 volts gradebetween indoor and outdoor unit along with necessary accessories complete all as specified and directed. |
| 15 | Supplying and Fixing PVC flexible Conduit pipe 25mm dia medium grade including all accessories for drain out pipe all as directed. |
| 16 | Supplying and Fixing Copper refrigerant pipe Copper tube 1/2 \" x 1/4\" dia and connecting along with insualtion sleeves incl leak testing complete all as specified and directed. |
| 17 | Dismantling of wall ceiling boards ( fibre, plup, insulation, etc) nor insulation boards/slabs/blamkets, any thickness, including cover fillets. |
| 18 | S & F 605 mmx605 mm Anodised aluminium snap grid frame work for false ceilingHangers 6 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long andexpansion hold fasteners 12.5mm dia. 40mm long, (frame work shall made as per site requirement for any type , shape ) complete all as specified ®all as specified and dircted. |
| 19 | S & F 600 mm x 600 mm x 12 mm thick Acoustic Calcium silicatepanels of siliceous and calcarireous material reinforced with cellous fibre fixing to 600 x 600 mm aluminium grid work grid work by screwing 150 mm C/C as in false ceiling (Frame work for False ceiling shall be measured and paid separately in respective item) complete all as specified and directed. |
| 20 | Dismantling of existing false ceiling board and Aluminium snap grid , put a side safely without breaking or damage the 600 mm x 600 mm x 12 mm thick Acoustic Calcium silicatepanels of siliceous and calcarireous material reinforced with cellous fibre and600 x 600 mm aluminium grid work grid work ,and refixing the same in new or old position where ever sutable after removing/dismantling theof AC Ducts from ceiling complete all as specified and directed. |
| 21 | SITC of Early Streamer Emission (ESE) lightning protection system, NFC 17- 102:2011 compliant. Tested in ICMET high voltage labarotary. Protection radius 107 mtrs at level -IV. ESE Air Terminal of external wide area protection system based on proactive Early Steamer Emission (ESE) Technology, ESE terminal is capable to withstand Current Impulses of 40 KA (5 shots of 8/20us wave shape ). outer body capturing rod which is made of non–corrosive SS ( XL 304) and having capturing rod dia of 25mm. to be mounted on existing roof of the E/M installations on PCC block of size 30cmx30cmx30cm having a bore of suitable size for inserting of 50mm pipe complete all as specifed and directed.The lightening protection system should consists of following items with specifications:-(a) Lightning Event Counter:Rated operating current from 1KA to 100KA/(max) in IP65 ENCLOSURE(b) Down Conductor:Single core 70 sq.mm PVC insulated flexible cable as per Indian Stadards.( POLYCAB/ ANY ISI MAKE )(c) Advance Earthing Electrode (Maintenace free CPRI tested): UL listed 17.2 mmx3mtr length copper bonded 250 microns sold rod & Advanced earthing compound 25Kgs x 2 bags & square polymer earthpit chamber(d) GI MAST: GI mast of 5mtr length, 60mm rod,coated with zinc with attached collar & base plate, guy wires, Nut bolts etc(e) Test Link Box: Supply of Test link box of suitable size and dimension in poly carbonate explosureNote: Quoted rate should be inclusive of Installation charges for Lightning terminal, mast & test link & digging , installation & connection to earth pit for normal soil conditions etc |
| 22 | M/Lforearthing complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI earth strip 25 x 4 mm diaby means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSRPt I.The work is inclusive of necessary earth work and PCC chamber in RCC (1:2:4) Type B-1using 20mm crushed stone aggregate with 8 CTD bar reinforcement both ways at 140 mm centre to centre complete all as directed by Engr-in-Charge. Note:- (i) GIearth leadbeyond 7.5M shall be measured and paid separately. (ii) The rate include measuring earth resistance |
| 23 | Supply and fixing GI earth strip of size 25x4 mm in ground not exceeding 40cm deep /fixing towall / structureincluding earthwork and necessary insulators, clamps, bolts, nuts etc., |
| 24 | supply & layingthe High density polyethylene (HDPE) pipe of50mm bore complete including necessary fittings. |
| 25 | Material & labourfor Aluminium strip 25 x3 size fixed to wallwith insulatorto over head tank / Storage shedor any other indicated situation all as specified and directed by Eng -in - charge . Note : The rate include Scaffloding ,/ Cradles etc . necessary for execution of work and protectivemeasures. |
| 26 | S&F LED Aviation Obstruction light withand accessoriesall as specified and directed by Engineer-in-Charge.Make - Bajaj / Havells/ Crompton |
| 27 | S&F Busbar supporting Insulator M10 Type for fixing of lightining arrestor connecting strip aluminium/ copper / GI strip on walls , building , roof of buildingfixing with screws and nut bolts all as per site requirement and all as directed by Emgr- In - Charge |
| 28 | M & L Air termination , single pointed, aluminium rod 12mm dia and 300mm long incl metal base plate with nut & bolt for fixing arrangement all as specified. |
| 29 | M & L for Test pointterminalblock made of gun metal or phosphourus bronze size 75 x 75 x25 mm drilled and screwed including 3 Nos 8mm dia 25mm long hex, head screw in repairs all as specified. |
| 30 | M/Lforearthing complete with copper earth plate electrode 600X600X3.15mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to copperearth strip 20 x3 mm diaby means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSRPt I.The work is inclusive of necessary earth work and PCC chamber in RCC (1:2:4) Type B-1using 20mm crushed stone aggregate with 8 CTD bar reinforcement both ways at 140 mm centre to centre complete all as directed by Engr-in-Charge. Note:- (i)copper earth leadbeyond 7.5M shall be measured and paid separately. (ii) The rate include measuring earth resistance |
| 31 | Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 x3 mm copper strip complete all as specified and directed. |
| 32 | S& F Display board (Earth pit marker) made out of25 mm angular frame rectangluar shape with 80 cm heightone side welded with 2mm thick MS sheet, frame work of size 30 cm x 20 cm boardincluding excavation , PCC foundation and duly painted with redoxide & two coatsblack enamel paint with following letterdisplay with white paint earth pit marker.a) Earthing pit No:- b) Earthing resistance:- c) E-N volt:-d) Check done on:- e) Check due On:- |
| 33 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 70 sqmm 3.5 core with all fixing & connecting accessories such as Alluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed. (Make: Havells/ Polycab/Grandlay) |
| 34 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables etc getting out and forming bottom surface to required gradient complete all as specified and directed |
| 35 | Supply, laying riddled earth soil conformed IS-1255, cushioning to cables with a layer of riddle earth soil 15cm deep before laying the cable and 8 cm depth after laying of cable, complete all as specified. Note: Punned Thickness shall be measured |
| 36 | Brick protection cover on cable with sub class \"B\" brick,laid dry and flat adjacent to each other complete all as specified and directed. |
| 37 | Returnings, filling in,including spreading levelling watering and well ramming to excavated soil in layers not exc 25 cm thick complete all as specified. |
| 38 | Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point in soils complete all as specified. |
| 39 | Supply & fixing GI earth wire 4.00 mm dia for interconnecting of earth electrodes all as specified. |
| 40 | Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 M below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt , earth lead GI wire 4mm dia ( 8 SWG) connectd to GI earth plate elcectrode by means of bolts, nuts, check nuts and washers of galvanised iron and thimbles and other end of earth wire connected to main switch board and protected by galvanised iron pipe medium grade 15mm bore and20mm bore light gradeGI pipewith funnel and wire mesh for watering including necessaryexcavation and earth works. PCC Chamber in cement concrete 1:3:6 type C-2 & RCC cover in M-20 (Design mix ) and all as shown in Electrical Plate No. 3 of SSR( Part-I) of 2009. |
| 41 | S & F MCCB DB Vertical TPN 8 way \"A\" frame,including MCCB TPN 100 Amp breaking capacity 16 KA- 02 nos, double door flush to wall including all cutting etc on wall including making good the disturbed surfaces to match complete all as specified and directed. Make- Havells or equivalent |
| 42 | M & L for sub main wiring complete with two runs of6 Sqmm single coreFRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories in surface of wall, roofs etc with one run of PVC insulated copper conductor 1x 6Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed. |
| 43 | S & F MCB SP 6-32 Amps, \"C\" series, 240 V complete incl making conections all as specified and directed. |
| 44 | S&F single pole and neutral enclosure with two pin and earth plug and socket including 1 No. MCB 20 Amp capacity complete all as specified and as directed |
| 45 | M & L point wiring with 1.5 sqmm nominal cross sectional area, single core, 1100 Volts FRLS grade, stranded, PVC insulated, unsheathed copper conductor cable drawn through PVC casing& caping of suitable size, complete with all PVC casing &caping accessories/ fittings, brass screws, washers etc, including metal flux boxes of suitable size and modular white plate with frame for mounting modular switches, sockets and regulators etc,including all cutting/chases etc in wallsand including continuousearth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed for the following:-(a)One light point controlled by one switch. |
| 46 | (b)One Bell point controlled by one push button. |
| 47 | Supply & fixing modular switch 06 Amps 1 module complete all as specified & directed |
| 48 | Supply & fixing Modular bell push 6 Amps 1 module complete all as specified & directed. |
| 49 | S & F Door bell AC, 230 volts, single pole complete all as specified and directed. |
| 50 | S&F 0.5 watt, 240 volts Basic round B22 LED bulb (IN &OUT light) complete all as specified and directed. |
| 51 | Supply & fixing ceiling rose surfacethree terminals complete all as specified & directed. |
| 52 | Supply and fixing Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed. |
| 53 | Supply and install hi wall split units air conditioner indoor/outdoorof capacity 2.0 TR complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2 complete all as specified and directed.(Make :- Blue Star/Carrier/Voltas) |
| 54 | S&F Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA |
| 55 | M & L for sub main wiring complete with two runs of 6 Sqmm single coreFRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories in surface of wall, roofs etc with one run of PVC insulated copper conductor 6 Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed. |
| 56 | S&Fdouble pole and neutral enclosure with two pin and earth plug and socket including 1NosMCB 20 Amps capacity complete all as specified and directed by Engr-in-charge |
| 57 | M&L for mild steel stand duly painted suitable for fixing 2/1.5 TR AC out door unit fixing in wall / floor, including making bore required size for copper pipe & copper cable with sweating pipe required size and length upto ground level complete all as spcecified and directed. |
| 58 | Supplying and Fixing Copper refrigerant pipe Copper tube 5/8 \" x 1/4\" dia and connecting along with insualtion sleeves incl leak testing complete all as specified and directed. |
| 59 | Supply and fixing copper power cable of insulated, PVC sheathed , multistranded copper cable of 2.5sqmm 3 core, ISI marked, 1100 volts gradebetween indoor and outdoor unit along with necessary accessories complete all as specified and directed. |
| 60 | Supplying and Fixing PVC flexible Conduit pipe 25mm dia medium grade including all accessories for drain out pipe all as directed. |
| 61 | Supply and Fix Fe 410-W (Grade E-250) quality A/MS Motorised sliding gate with rail as per the following specificationsa) The Gate system should have electromechanical operation with motor specification as follows : speed of the motor could be fixed / adjustable as per the requirement of user with a minimum speed of 12 meter per minute. It should be ideal for fast operation and continous duty. The control panel of motor should be integrated and protected by metal housing and fiber cover for all weather operation.b) The gate should be supported by adjustable upper guide bracket with bearing guide post with safety strike.c) The gate should be coated with epoxy primer.d) Technical specifications of the motor -use temperature -10 to 55 degree celcius power supply 230 V (=/- 5% percentage), 50 Hz protection class IP 44 or better.Note : Demolition of gate providing the rail making good concrete finish . The gate must be replica of gate 2 all these inclusive in the above rate. |