| 1 | Supply, installation, testing & commissioning of diesel engine silent generator set with acoustic enclosure confirming to latest CPCB norms, water cooled capacity 82.5 KVA (generator out put should be 82.5 KVA/66 KW) 50 Hz AC supply, engine as per IS : 10001/ 10002 and alternator as IS : 13364 complete including engine alternator mounted on common base frame and canopy fabricated from steel channel of suitable size, engine and alternator shall be anti vibration mounting pads,sound proof canopy as per latest CPCB norms and foundation as per manufactures instruction / design complete all as specified directed with and including the following provision :- (a) ALTERNATOR :- Alternator of capacity 82.5 KVA/66 KW at 0.80 power factor after considering derating factor AC 3 phase , 415 volts, 50 Hz, 1500 RPM brushless type self excited, self regulated screen protected type and AVR system. (b) DIESEL ENGINE:- Diesel engine air cooled suitable for alternator of 82.5 KVA capacity considering all points for derating factor taking into account the altitude, humidity of maximum temperature of Ranikhet with the following provision :-(i) Radiatorand sound proof canopy as per latest CPCB norms and foundation etc. of capacity 82.5KVA (ii) Fly wheel(iii) Air cleaner (iv) water pump with thermostat(v) Electric starting system with the help of batteries as per manufacture\"s specification with key ignition and push button(vi) Temperature meter and oil pressure gauge(vii) Fuel tank ofmade of mild steel sheet of required capacity as per standard with inlet and out let connection, filling cap, drain valve air vent with calibrated scale on outdoor surface floor mounted with suitable angle iron support (viii) Fuel/ oil filter (ix) Battery charger as per manufacturer\"s recommendation (x) Battery maintenance free with connecting lead. Make Exide / Amaron/Luminous(xi) Foundation as permanufacturer\"sinstruction/ drawing (xii) Heating system to start engine during winter season(xiii) Engine protection device against short circuit overload low lubricanting oil high pressure water temperature and over speeding of engine (xiv) Anti vibration mounting pad - set of 6 Nos |
| 2 | (xv) Exhaust system up to required height and length(xvi) Engine warranty and test certificate(xvii) RPM meter and hour meter(xviii) Including Gen set control unit completeThe DG Set must include the following features • Compact size with Manual/ Automatic starting system. feature. • Sound Proof, Weather Proof enclosure. • Low vibration, with electronic fuel injection system • Class G3 Governing in its range, which gives better accuracy in decreasing the speed drop in transient and loweringrecovery time of the speed. • Confirms to latest Govt. CPCBIV+ emission & • The Enclosure should be of modular construction with the provision to assemble and dismantle easily. • The sheet metal components should be 9 tanks pre treated and should be polyester based powder coated (inside as well as outside) for long life. • All Nuts-bolts, hardware should be of Stainless Steel for longer life. • Battery must be provided in a tray inside the enclosure. • Doors must be gasketed with high quality EPDN gaskets to avoid leakage of sound • Optimised EATS (Exhaust After Treatment System) should be provided to control emission & exhaust noise with sound attenuators to control sound at air entry & exit points inside the enclosure• Adequate ventilation should be provided to meet air requirement for combustion & heat removal. |
| 3 | Supply, installation, testing & commissioning of diesel engine silent generator set with acoustic enclosure confirming to latest CPCB norms, water cooled capacity 100 KVA ( generator out put should be 100 KVA/80 KW) 50 Hz AC supply, engine as per IS : 10001/ 10002 and alternator as IS : 13364 complete including engine alternator mounted on common base frame and canopy fabricated from steel channel of suitable size, engine and alternator shall be anti vibration mounting pads, sound proof canopy as per latest CPCB norms and foundation as per manufactures instruction / design complete all as specified directed with and including the following provision :- (a) ALTERNATOR :- Alternator of capacity 100 KVA/80 KW at 0.80 power factor after considering derating factor AC 3 phase , 415 volts, 50 Hz, 1500 RPM brushless type self excited, self regulated screen protected type and AVR system. (b) DIESEL ENGINE:- Diesel engine air cooled suitable for alternator of 100 KVA capacity considering all points for derating factor taking into account the altitude, humidity of maximum temperature of Ranikhet with the following provision :-(i) Radiatorand sound proof canopy as per latest CPCB norms and foundation etc. of capacity 100KVA (ii) Fly wheel (iii) Air cleaner(iv) water pump with thermostat(v) Electric starting system with the help of batteries as per manufacture\"s specification with key ignition and push button (vi) Temperature meter and oil pressure gauge(vii) Fuel tank ofmade of mild steel sheet of required capacity as per standard with inlet and out let connection, filling cap, drain valve air vent with calibrated scale on outdoor surface floor mounted with suitable angle iron support |
| 4 | (viii) Fuel/ oil filter (ix) Battery charger as per manufacturer\"s recommendation (x) Battery maintenance free with connecting lead. Make Exide / Amaron/Luminous(xi) Foundation as permanufacturer\"sinstruction/ drawing(xii) Heating system to start engine during winter season (xiii) Engine protection device against short circuit overload low lubricanting oil high pressure water temperature and over speeding of engine (xiv) Anti vibration mounting pad - set of 6 Nos (xv) Exhaust system up to required height and length (xvi) Engine warranty and test certificate (xvii) RPM meter and hour meter(xviii) Including Gen set control unit complete The DG Set must include the following features • Compact size with Manual/ Automatic starting system. feature. • Sound Proof, Weather Proof enclosure. • Low vibration, with electronic fuel injection system • Class G3 Governing in its range, which gives better accuracy in decreasing the speed drop in transient and lowering th recovery time of the speed. • Confirms to latest Govt. CPCBIV+ emission & • The Enclosure should be of modular construction with the provision to assemble and dismantle easily. • The sheet metal components should be 9 tanks pre treated and should be polyester based powder coated (inside as well as outside) for long life. • All Nuts-bolts, hardware should be of Stainless Steel for longer life. • Battery must be provided in a tray inside the enclosure. • Doors must be gasketed with high quality EPDN gaskets to avoid leakage of sound • Optimised EATS (Exhaust After Treatment System) should be provided to control emission & exhaust noise.with sound attenuators to control sound at air entry & exit points inside the enclosure• Adequate ventilation should be provided to meet air requirement for combustion & heat removal. |
| 5 | Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 160 Amps including necessary connections and fixing on wall complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply, laying, jointing and commissioning LT XLPE 1100 volts 16 sqmm 4 coregrade heavy duty underground cable PVC insulated, strandred aluminium conductor served with inner sheathing of PVC tape, armoured with GI steel or tape and over all PVC sheathing laid in trenches, floor through pipes, in duct on pole and roads etc.complete all as specified and directed. |
| 7 | Excavation in trenches in hard/dense soil not exc 1.5mtrs wide and not exc. 1.5m in depth for laying cables and getting out incl jointing bottom surface to the reqd level/slope etc complete all as specified and directed. |
| 8 | Returning filling in incl spreading, leveling, watering and well ramming in layers not exc 25 cm in hard/dense soil all as specified and directed. |
| 9 | Removing excavated material to a distance not exc 15 mtr and deposited where directed at a level not exc 1.5 mtrs above the starting point complete all as specified and directed. |
| 10 | M&L for dry clean sand filling in trenches below and around under ground cable cushioning complete all as specified and directed. Note :- Thickness of sand cushioning shall be measured after punning. |
| 11 | M&L for GI pipe25mm borelight grade with all fittings as in protection pipe for cable all as specified and directed. |
| 12 | M&L for brick protection covers laid over cables of sub class B bricks old size (230X115X75)mm complete all as specified and directed. |
| 13 | Supply, installation, testing and commissioning of 40-50 KLD water treatment plant with pressurized multigrade sand dual media filtration system for 6m3/h flow in 10 MT lifting capacity having following items:-(a) Raw water open well pump 1.5/2 HP having discharge capacity- minimum 7 m3/h -01 Nos (b) Pressurized Multi Grade dual media filter with 250 Kg FRP Vessel having top to bottom opening dia-18 inch, height- 65 inch, min testing pressure- 10 Kg/Cm2 -01 NosMultiport single lever valve/05 BFV header system, down flow with 2-4 Bar working pressure, size-1.5-2.0 inch, max flow rate-6000 LPH - 02 NosMedia- for FRP vessel, multi grade sand size- 01 inch to 32 mm- 250 Kg(c) Pressurized Multi Grade dual media filter with 200 Kg ACF media FRP Vessel having top to bottom opening dia-18 inch, height- 65 inch, min testing pressure- 10 Kg/Cm2 -01 NosMedia- Activated carbon media - 200 Kg(d) Dosing pump having metering injector 6 LPH pump with adjustable flow rate diaphragm type including HDPE chemical tank of capacity 100 Ltr- 01 Nos(e) Necessary control instruments as per requirement at site- flow meter- 01 Nos, pressure gauge- 05 Nos Note:-Necessary electrical control panel of suitable size for auto/manual operation, CPVC connection pipes, transportation and civil foundation work required for above system installation rates are deemed to be included quoted rate by contractor. |
| 14 | Supply and Fix PVC tank rotational moulded water storage tank of capacity 1000 Ltrs including closed top cover fixed in position on existing staging all as specified & directed by Engr in Charge. |
| 15 | M&L for earthing complete with galvanised steel,earth plate electrode 600x600mm x 6mm thick burried directly in ground verticaly (earth pit not less than 2.25 mtrs belowground level ) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanised strip 32x6mm as earth leadby means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electrical plate No 3 on page 497 of MES schedule 2009 part - I connected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in hard/dense soil common salt and charcoal dust mixed and packed 150mm thick all round the GI earth plate, watering pipe 20mm dia GI medium grade. GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150c/c both ways and pit/chamber in PCC 1:3:6 type C1 with suitable lifting handleto cover, GI protection pipe 40mm dia light grade up to 7.5mtr from electrode GI pipe to be fixed with complete all as specified and directed. Note :- (i) Earth lead beyond 7.5 mtr from electrode to earth terminal point/main switch & GI pipe light grade 40mm dia for protection against mechanical damage to lead shall be measured separately. (ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost. |
| 16 | Supply, install & testing of pressed GRP Panel Tank/NEERCO SMC tank of brand SINTEX, AMITEX, HP ENGINEERS as per BIS: 14399, (4x4x2m) of capacity 31200 Ltrs with HDG side supports SS-304 Bolts including HDG pedestal grillage of size 4x4x0.6m. The panel should with stand hydrostatic pressure of at least 4 times the working load. Tank shall be erected on steel /MS which must be kept at RCC base foundation at site as per manufacturer\"s specifications & design for installation at roof/ground level . Provn of holes for inlet and outlet, overflow should be made as per direction of Engr-in-charge. The tank panel must be printed with ISI logo, ISI certification number, CML number, Batch number etc.Note:- Foundation/civil work including necessary excavation, required pipe/pipe connections, PCC 1:3:6 type C-2, 40 mm aggregate in foundation, mass concrete, RCC 1:2:4 type B-1, 20mm grounded stone aggregate. MS work as in base MS frame of water storage tank using channell rates shall be deemed to be included in quoted rate by the contractor. |
| 17 | Supply and fix electric driven 1 ph, AC 220-240V, 50Hz , direct cool energy efficient refrigerator of capacity 210 Litres, single door having built-in stabilizer, digital inverter compressor with accessories, BEE 5 star rated complete all as specified and directed by Engr in charge. |