| 1 | Material & labour in replacement oflaying, jointing and testing Ductile iron water pipes 150mm bore class K-7 conforming to IS 8329, in any length including jointing with push on rubber tyton joints, as in trenches of following bore in new or old locations. (Excavation, earth work & DI specials shall be measured and paid separately. However, the rate of Rubber tyton joints shall be included in the unit rate quoted). |
| 2 | Material & labour for laying, jointing and testing Ductile iron water pipes 100mm bore class K-7 conforming to IS 8329, in any length including jointing with push on rubber tyton joints, as in trenches of following bore in new or old locations. (Excavation, earth work & DI specials shall be measured and paid separately. However, the rate of Rubber tyton joints shall be included in the unit rate quoted). |
| 3 | Supply & Laying, Jointing Galvanized steel water tubing, medium grade of 15 mm bore, screwed and socketed joints with and including all required fittings as in trenches, floors, on walls etc and making good the disturbed surface complete all as directed. (Excavation and earth work for fixing in old location already considered in items for taking out and for new locations if required the same shall be paid separately). |
| 4 | Supply & Laying, Jointing Galvanized steel water tubing, medium grade of 20 mm bore, screwed and socketed joints with and including all required fittings as in trenches, floors, on walls etc and making good the disturbed surface complete all as directed. (Excavation and earth work for fixing in old location already considered in items for taking out and for new locations if required the same shall be paid separately). |
| 5 | Supply & Laying, Jointing Galvanized steel water tubing, medium grade of 25 mm bore, screwed and socketed joints with and including all required fittings as in trenches, floors, on walls etc and making good the disturbed surface complete all as directed. (Excavation and earth work for fixing in old location already considered in items for taking out and for new locations if required the same shall be paid separately). |
| 6 | Supply & Laying, Jointing Galvanized steel water tubing, medium grade of 40 mm bore, screwed and socketed joints with and including all required fittings as in trenches, floors, on walls etc and making good the disturbed surface complete all as directed. (Excavation and earth work for fixing in old location already considered in items for taking out and for new locations if required the same shall be paid separately). |
| 7 | Supply & Laying, Jointing Galvanized steel water tubing, medium grade of 50 mm bore, screwed and socketed joints with and including all required fittings as in trenches, floors, on walls etc and making good the disturbed surface complete all as directed. (Excavation and earth work for fixing in old location already considered in items for taking out and for new locations if required the same shall be paid separately). Note for item No.1 to 7 :-(i) Rate for making good the damaged surface such wall,concrete floor,road etc shall be deemed to be included in unit quotaed rates. |
| 8 | Supply and fix Cast iron/ ductile iron fittings of size upto 300 mm bore for spigot and socketed pipes e.g. Bends (any type, radius and angle). Tapers any type (Straight, end, increasing, decreasing or double socket etc). Tee pieces single branch, \"Y\" junctions double branches, crosses (all sockets or socket and spigot) collars caps and plugs conforming to Is complete all as specified and directed. (Excavation, earth work,& joints shall be measured and paid separately). |
| 9 | Excavation in trenches in soft/loose soil not exc 1.50 mtrs wide and not exc. 1.5 mtr deep and getting out for taking out/laying DI/GI pipe lines and for laying of cableetc complete all as specified and directed by Engineer-in-Charge. |
| 10 | Returning, filling in, including spreading levelling, watering and well ramming in layers not exc. 25 cm thickcomplete all as specified and directed by Engineer-in-Charge. |
| 11 | Removal of excavated surplus soil to a distance not exc. 50 mtr away and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 12 | Supply, installation, testing & commissioning in LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) : -Incoming :(a) Aluminum busbar 4 Pole, of rating 400 Amps.- 01 Set(b) MCCB , 4 pole, 50 KA, 200 Amps, adjustable type with spreader link - 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set.(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No.Outgoing:-(a)MCCB 415 V, 16 KA, 4 Pole, 63 Amps, adjustable type with spreader link - 10 Nos(For Qtr Blocks)(b)MCB , 2 pole, 10KA, 32 Amp- 02 No.(For Street Light) |
| 13 | Supply, installation, testing & commissioningof LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) :-Incoming :(a) Aluminum busbar 4 Pole, of rating 400 Amp.- 01 Set(b)MCCB , 4 pole, 25 KA, 250 Amp, adjustable type with spreader link - 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No .Outgoing:-(a)MCCB 415 V, 16 KA, 4 Pole, 63 Amp, adjustable type with spreader link - 13 Nos(For Qtr Blocks)(b)MCB , 2 pole, 10KA, 32 Amp- 02 No.(For Street Light) |
| 14 | Supply,installation, testing & commissioningof LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) :-Incoming :(a) Aluminum busbar 4 Pole, of rating 400 Amp.- 01 Set(b)MCCB , 4 pole, 25 KA, 250 Amp, Adjustable type with spreader link - 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No .Outgoing:-(a)MCCB 415 V, 16 KA, 4 Pole, 63 Amp, adjustable type with spreader link - 10 Nos (For Qtr Blocks)(b)MCB TPN 10 KA,32 Amp, adjustable type with spreader link - 02 Nos(For Blocks)(c)MCB , 2 pole, 10 KA, 32 Amp,Double Pole - 02 Nos (For Street Light) |
| 15 | Supplying, laying, jointing , testing and commisssioning underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 400 Sqmm 3.5 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/floors/across road etc as per site condition including taking out old unsv cable complete all as specified and directed. |
| 16 | Supplying, laying, jointing , testing and commisssioning underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 300 Sqmm 3.5 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/floors/across road etc as per site condition including taking out old unsv cable complete all as specified and directed. |
| 17 | Supplying, laying, jointing , testing and commisssioning underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 240 Sqmm 3.5 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/floors/across road etc as per site condition including taking out old unsv cable complete all as specified and directed. |
| 18 | Supplying, laying, jointing , testing and commisssioning underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 185 Sqmm 3.5 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/floors/across road etc as per site condition including taking out old unsv cable complete all as specified and directed. |
| 19 | Supplying, laying, jointing , testing and commisssioning underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 25 Sqmm 4 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/floors/across road etc as per site condition including taking out old unsv cable complete all as specified and directed. |
| 20 | Supplying, laying, jointing , testing and commisssioning underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cable (heavy duty) 1100 volt grade with size of 10 Sqmm 2 core confirming to IS: 7098 part-I ammended upto date, laid in trenches, along pole/wall/floors/across road etc as per site condition including taking out old unsv cable complete all as specified and directed.Note for item No.15 to 20 :-(i) Exacavation/Earth work , brick & sand protection shall be measured and paid saperately.(ii) Rate for making good the damaged surface such wall,concrete floor,road etc after laying LT Cable shall be deemed to be included in quotaed rates. |
| 21 | Material and labour for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable ie total 23 cm and after punning down sand cushioning will be 18 cm complete all as specified and directed by Engineer-in-Charge. Note : 18 cm thick only will be considered for pryment purpose. |
| 22 | Supply and laying common burnt clay bricks, sub class \"B\" grade laid in trenches for protection of UG cables perpendicular to the direction of the cables complete all as specified and as directed by Engr-in-Charge |
| 23 | Dismantling of insulators any type, any size complete all as specified & directed. |
| 24 | Dismantling of ACSR or AAC overhead conductors complete all as specified & directed. |
| 25 | Dismantling of cross-arms of MS channel or angle sections etc. complete all as specified & directed. |
| 26 | Dismantling GI wire of any size complete all as specified and as directed by Engr-in-charge. |
| 27 | Material and Labour for boring holes under the road/pavement/hard standing with the help of trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 100mm dia suitable for 0.4 mpa working pressure not less than one metre below ground level complete all as specified and directed. (The cost of HDPE pipe shall be deemed to be included in quoted rate). |
| 28 | Material and Labour for LT Kiosk boxfor security/street lights weather proof made out of PVC fire retardant, non fusing, shock & dust proof, one piece moulded SMC base and SMC cover with hinged Door, pole mounting type comprising of aluminum busbar DP rating 63 Amps with MCB SP 6 Amp of size 300 x 200x100mm, fixed on pole with MS, clamps 20 x 3mm with necessary nuts, washer and incl applying two coats of synthetic enamel paint over ared oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5 cms with letter and conventional skull and bones in signal red colour on front face of kiosk box complete all as directed. |
| 29 | Supply, installation, testing & commissioning in replacement of LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) : -Incoming :(a) Aluminum busbar 4 Pole, of rating 1000 Amps.- 01 Set(b) ACB , 4 pole, 50 KA, 630 A,- 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set.(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No.Outgoing:-(a)MCCB , 4 pole, 25 KA, 250 Amp, Adjustable type with spreader link - 01 Nos (For feeder piller)(b)MCCB , 4 pole, 25 KA, 400 Amp, adjustable type with spreader link - 02 Nos. (For feeder piller)(c)MCCB , 4 pole, 25 KA, 63 Amp, adjustable type with spreader link - 01 Nos (Blank) |
| 30 | Supply,installation, testing & commissioningof LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) : -Incoming :(a) Aluminum busbar 4 Pole, of rating 600 Amp.- 01 Set(b) MCCB , 4 pole, 25 KA, 400 Amp, - 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set.(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No.Outgoing:-(a)MCCB 415 V, 16 KA, 4 Pole, 63 Amp, adjustable type with spreader link - 19 Nos (For Qtr Blocks)(b)MCB, TPN 10 KA,32 Amp, adjustable type with spreader link - 01 No (For Qtr Blocks)(c)MCB , 2 pole, 10 KA, 32 Amp,DP - 02 No.(For Street Light) |
| 31 | Supply, installation, testing & commissioning of LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) : -Incoming :(a) Aluminum busbar 4 Pole, of rating 600 Amp.- 01 Set(b) MCCB , 4 pole, 25 KA, 400 Amp, - 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set.(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No.Outgoing:-(a) MCCB 415 V, 16 KA, 4 Pole, 63A, adjustable type with spreader link - 08 Nos(For Qtr Blocks)(b)MCB,TPN 10 KA,32 A, adjustable type with spreader link - 07 Nos (For Qtr Blocks)(c) MCB , 2 pole, 10 KA, 32 A,DP - 02 No. (For Street Light) |
| 32 | Supply, installation, testing & commissioning of LT panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,outer body made out of 3.15 mm thick & inner shell made out of 2.00 mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated , The cubicle shall have frame work, bottom & 45 CM long four legs of size 50 x 50 x 6 mm Angle iron, aluminium main busbar duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 SQMM, complete comprisingwith following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder pillar box shall be mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed.The cost of the PCC foundation, cable gland and Danger notice plate 02 Nos shall be deemed to be included in the unit rate quoted for the item) : -Incoming :(a) Aluminum busbar 4 Pole, of rating 400 Amp.- 01 Set(b) MCCB , 4 pole, 25 KA, 200 Amp, - 01 No.(c) Digital type Amp meter &Vol meter,3 Phase with CT- 01 Set.(d) LED indicating lamps three Nos (RYB)-01 Set.(e) Street Light Timer- 01 No.Outgoing:-(a) MCCB 415 V, 16 KA, 4 Pole, 63 Amp, adjustable type with spreader link - 08 Nos (For Qtr Blocks)(b)MCB,TPN 10 KA,32 Amp, adjustable type with spreader link - 03 Nos (For Qtr Blocks)(c) MCB , 2 pole, 10 KA, 32 A,DP - 02 No. (For Street Light) |
| 33 | Supply and laying of 90/76 mm outer dia/ inner dia, double walled, corrugated DWC duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed. |
| 34 | Material and labour forEarthing with Galvanisedsteel pipe electrode shall be of medium grade 40 mm dia and 2.5 m in length. Pipe electrode shall be cut tapered at the bottom and is provided with 12 mm dia holes (staggered) at 75 mm centre to centre upto 2 m of length from bottom. The electrode shall be buried directly in ground vertically with its top edge not less than 1.25 m below ground levelconnected to main earth lead 4.0 sqmm galvanised iron wire by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.2 of MES Schedule pt-I 2009, GI earth lead shall be protected by GI pipe 15 mm dia medium grade and connected to distribution board includingexcavation in any type of soil,returning filling, disposal of soil, providing alternate layer ofcharcoal dust and common salt upto top edge of electrode, construction of PCC pit with RCC cover, funnel,including testing on completion complete including dismantling of old UNSV earthing all as specified and as directed. Note- : (i)GI strip beyond 7.5 metre will be measured and paid sepeartely.(ii)Test report shall be prepared and submitted by the contractor in triplicate duly obtaining signatures of MES JE / AGE & user.(iii)The earth resistance should be less than 5 Ohm. |
| 35 | For Credit Schedule refer tender documents. The amount of credit schedule shall be deducted in total quoted amount of BOQ to arrive contract sum. |