| 1 | Supply and Installation in repair of Motorised Industrial Roller Shutters. The curtain shall be made of 1.25mm thick and 110mm wide galvanized steel slats confirming to 15:277. The guide channel shall me made of 2mm galvanized steel conforming to 15:277 attached with rubble strip for noiseless operation. The pipe shaft shall be made of galvanized steel, and it shall have spring attachments. The shutter shall be fitted with industrial shutter motor with a capacity of 400kg to 1500kg depending on shutter size Make DuraUltima. Dura Shakti |
| 2 | Taking down steel rolling shutter of any description and size as per site requirement with all accessories, complete all as specified and directed. |
| 3 | Servicing/repairs to existing steel rolling shutters of size 6000 mm (W) x 6000 mm (H) (Approx), with top cover, hasp and staple, push pull or manual type/ gear operated type with bevel gear box and crank handle by greasing of guide channels, hasp and staple,roller springs,bearings etc., including replacement of unserviceable nuts,bolts & washers in roller pulley and top cover,alignment of laths etc. for smooth operation of shutter, complete all as specified and directed. Notes:- (i) Height considered from the bottom of the lintel to the finished floor cill level. Width considered inclusive of the width of the side guides. (ii) Cost of materials such as lubricants,screws, nuts, bolts & washers etc.shall be deemed to be inclusive in the quoted rate. |
| 4 | Supply and fix safety lever locks mild steel with 4 levers for rolling shutters, complete all as specified and as directed. |
| 5 | Demolition of Cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for, complete all as specified and as directed. |
| 6 | Material and labour for 75 mm thick plain cement concrete (1:3:6) type C2 (using 40 mm graded crushed stone aggregate) as in floor/sub floor etc, complete all as specided and as directed. |
| 7 | M & L 25mm thick cement concrete type B-0, 1:2:4 (using 12.5 mm graded crushed stone aggregate) as in levelling course in floor, complete all as specified and directed. |
| 8 | Material and labour for Vitrified Ceramic tiles light shade 9-10 mm thick (square/ rectangular) polished, area of each tiles (800x800)mm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match of tiles, laid over screed bed or bedding layer 20mm thick in cement mortar 1:6 including Dismantling floor, hearth tiling including cement mortar bedding ( but not backing ), removing rubish of the premises, complete all as specified and as directed. |
| 9 | S & F prepainted galvatume aluminium zinc coated GI based corrugated steel sheet 0.50 mm thickness of an colour having tensile strength of 550 Mpa as in roof covering / clading to wall fixed with self tapping screwand bent to curve of any radiusincluding dismantling plain or corrugated steel sheeting, any gauge thickness complete all as specified and as directed. |
| 10 | Material and Labour for complete removal of existing treatment by mechnical process Machine as directed by manfucaturer through authorised applicator of manufacturer and apply two coat of 100% Acrylic Exterior Emulsion paint in camouflage pattern (three to five colours asapproved by GE) (Nerolac Excel total paint, Berger Weather coat Advanced XP, Asain Paints: Apex Ultima Brand ICl:Dulux Weather shield Max, J&N:Safeguard Optima Brand) painting over a coat of suitable primer and including one coat of 1 mm thick wall care putty to old plastered or unplastered surfaces on walls (including chajja, facia & ceiling surface) including preparation of surfaces, up to 18 Mtr height including all necessary scaffolding and safety measures complete all as specified and directed.Note - (Work shall be executed through authorised applicator which shall be got approved from the GE before comencement of the work). |
| 11 | M&L for rendering 15 mm thick on fair faces of brick or concrete surfaces with cement mortar 1:4 mixed with liquid water proofing compound @ 0.25% by weight of cement or as per manufacturer instruction and finishing the surface even & smooth without using extra cement, including taking down cement plaster on brick or stone wall etc including racking out joints hacking for key scrubbing down with water etc complete all as specified and as directed.Note:- Liquid water proofing comound shall be measured & paid separately under respective items |
| 12 | M & L Preparation of new or previously untreated steel and iron surfaces of any description and applying two coat of synthetic enamel paint in camouflage pattern (Three to five colour as approve by GE) over and including a coat of red oxide or zinc chrome primer on steel sufaces over 10cm width or girth including preparation of surfaces, up to 18 Mtr height including all necessary scaffolding and safety measures, complete all as specified and directed. |
| 13 | Material and labour for complete removal of existing treatment and applying two coat of synthetic enamel paint in camouflage pattern (Three to five colour as approved by the GE) over and including a coat of red oxide or zinc chrome primer on old steel sufaces over 10cm width or girth including preparation of surfaces, up to 18 Mtr height including all necessary scaffolding and safety measures, complete all as specified and directed. |
| 14 | Supply and installHeavy duty Industrial motor operated shutters weigh up to 1250 KG motor speed 1150 RPM, power consumption 750watt, 230V, 50 HZ (custom option available) motor length 626mm weight 32.3 kg and supplied with a smart control panel for smooth and safe operation integrated push button station for easy manual control of the shutter designed for continuous duty cycles equipped with thermal overload protection robust build, complete all as specified and directed. Make: Dura Ultima or Equivalent |
| 15 | Materials and Labour for point wiring with 1.50 Sq. mm (nominal area) FRLSH PVC insulated and unsheathed, multi stranded copper conductor cable 1100 Volts grade, single core, laid in and including PVC casing and capping complete with all fittings and accessories, fixed to walls/ceiling, including sunk type pressed steel terminal boxes 60 mm deep, conforming to IS-5133 (Part-I) with 3 mm thick plastic laminated sheet cover (ISI Marked) for mounting switches/ regulator /bell push etc and including 1.50 Sq. mm (nominal area) FRLHS PVC insulated and unsheathed multi stranded copper conductor cable 1100 Volts grade, single core, earth continuity conductor connected to common earth dolly for one light/fan point controlled by one switch including taking down carefully existing copper/ aluminium point wiring (light, fan, socket or power) complete including fittings such as switches, ceiling roses, pendent, regulators, sockets, light fittings etc, removing materials from site and making good disturbed surfaces of walls, floors etc., complete all as specified and directed. |
| 16 | Materials and Labour for point wiring with 1.50 Sq. mm (nominal area) FRLSH PVC insulated and unsheathed, multi stranded copper conductor cable 1100 Volts grade, single core, laid in and including PVC casing and capping complete with all fittings and accessories, fixed to walls/ceiling, including sunk type pressed steel terminal boxes 60 mm deep, conforming to IS-5133 (Part-I) with 3 mm thick plastic laminated sheet cover (ISI Marked) for mounting switches/ regulator /bell push etc and including 1.50 Sq. mm (nominal area) FRLHS PVC insulated and unsheathed multi stranded copper conductor cable 1100 Volts grade, single core, earth continuity conductor connected to common earth dolly for one 3 Pin 5 Amps socket outlet independent including taking down carefully existing copper/ aluminium point wiring (light, fan, socket or power) complete including fittings such as switches, ceiling roses, pendent, regulators, sockets, light fittings etc, removing materials from site and making good disturbed surfaces of walls,floors etc.,complete all as specified and directed. |
| 17 | Supply and fix copper winding exhaust fan, steel body, AC single Phase. 230V of size 380mm sweep, heavy duty with, blades, frame and louvers,all as specified and directed by Engr-in-Charge. |
| 18 | Supply and fix copper winding Wall mounted fan, speed 1400 RPM, Air delivery 110 CUM (Heavy Duty), steel body AC single Phase. 230V of size 450mm sweep with, blades, and frame complete all as specified. Model : V3 Wall of Havells or equIvalent make. |
| 19 | Supply and fix switch socket combination 2 in 1, 3 pin 5 Amp flush type universal, complete all as specified and as directed. |
| 20 | Supply and fix switch piano, flush button single pole one way 5 Amp, complete all as specified and as directed. |
| 21 | Materials and Labour for two single core FRLSH PVC insulated unsheathed cable 4.00 Sqmm (Nominal area) with stranded copper conductor cable, 1100 Volts grade, drawn in and including PVC casing & capping and continuous earth wire of single core FRLSH PVC insulated, unsheathed cable 4.00 Sq. mm (nominal area) with stranded copper conductor cable, 1100 Volts grade for circuit/sub main wiring, complete all as specified and directed. |
| 22 | Materials and Labour for two single core FRLSH PVC insulated unsheathed cable 6.00 Sqmm (Nominal area) with stranded copper conductor cable, 1100 Volts grade, drawn in and including PVC casing & capping and continuous earth wire of single core FRLSH PVC insulated, unsheathed cable 6.00 Sq. mm (nominal area) with stranded copper conductor cable, 1100 Volts grade for circuit/sub main wiring, complete all as specified and directed. |
| 23 | Supply and Fix Double Door Sheet Metal Enclosure for DBs for mounting of MCB for 240 Volts, 8 way, with 200 Amps rated bus bar, Single Pole & Neutral, complete all as specified and directed. |
| 24 | Supply and fix miniature circuit breaker (MCBs) single pole, 240 Volts, 10KA,\"C\" curve, 6 to 32 Amps complete all as specified and directed. |
| 25 | Supply and fix miniature circuit breaker (MCBs) single pole and neutral, 240 Volts, 10KA,\"C\" curve, 6 to 32 Amps complete all as specified and directed. |
| 26 | S&F of cubical housing cabinet type LT feeder pillor box outdoor type, CPRI Approved for 35 MVA rupturing capacity at 415 volts, The degree of ingress Protection of outer shell shall be IP-54 and The degree of ingress protection for inner shell shall be not less than IP-42, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side, the outer shell shall be made out of 3.15mm thick CRCAMS Sheet and inner shell shall be made out of 2.0mm thick CRCA sheet, platform mounted factory made, totally enclosed dust and vermin proof openablefrom both front and rear side made out of 3.15mm thick CRCAMS Sheetof overall size 1200 mm (height) x 1000 mm(width) x 600 mm (depth)and built upon suitable size angle ironframe work , having front and rear hinged doors,GI earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers.The cabinet and all members should be chemically treated with MSR solution for anticorrosive treatment and apply powder coated paint (RAL-7032) The panel should be suitable for 415 volts , 50Hz, 3 phase4 wire systemand internal connection should be provided with aluminium strips of suitable size and necessary foundation workand comprisingfollowing: - |
| 27 | BUS BAR CHAMBER |
| 28 | (a) Electrolytic grade high conductivity TP&N solid aluminium bus bars, rated 400 amps supported at required intervals sleeved with heat shrinkable PVC sleevings.The bars shall be colour coded at required intervals for identification - SET OF 4 - 1 No. |
| 29 | INCOMER |
| 30 | (a) MCCB of 4 poleof capacity 320 ampswith breaking capacity of 36 KA (Thermal setting 100%, Magnetic setting upto 70%) |
| 31 | OUTGOING FEEDERS |
| 32 | (a) MCCB of 4 poleof capacity 63 ampswith breaking capacity of 25 KA (Thermal setting 100%, Magnetic setting upto 70%) - 7 No. (6 No. Outgoing & 01 No. Spare) |
| 33 | (b) MCB 32 Amps \"C\" curve SPN with breaking capacity 10KA - 3 No. |
| 34 | INDICATING DEVICES |
| 35 | (a) LED Indicating lamps for Main Supplyindicating R\", Y\" B\" - Set of 3. |
| 36 | (b) Digital Voltmeter (96mmx96mm) 0-500 Volt with selector switch of 10Amps -1No. |
| 37 | (c) Current Transformer havingRatio 200/5, 5 VA rated burden - 3 Nos(Make: AE/RISHABH/L&T) |
| 38 | (d) Digital Ammeter 0 to 400 Amps, square type (96mmx96mm) - 01 No.(Make: AE/RISHABH/CONZERV/L&T) |
| 39 | (e) Voltmeter Selector switch (6A) 3 position with \"OFF\" - 01 No.(Make : KAYCEE/L&T) |
| 40 | (f) Ammeter Selector switch (6A) 3 position with \"OFF\" - 01 No.(Make : KAYCEE/L&T) |
| 41 | M&L for Earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI earth strip of size 32 x 6 mm earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel,protected by galvanized iron pipe 40mm bore (Medium grade) allas directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel,wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed after taking down old earthing. (Cost of GI strip upto 7.5m including testing is deemed included in this item). |
| 42 | Materials and Labour for rendering 8 mm thick, cement plaster, in cement mortar (1:4) mixed with water proofing compound as per manufactures instructions over and including 12 mm thick backing coat in cement mortar (1:4) on fair faces of brick work or concrete surface in walls, complete all as specified and directed.Note: - (Water proofing compound will be measured and paid separately) |