| 1 | Items : |
| 2 | Excavating over areas,n. exc. 1.5 m deep and getting out in soft/loose soil as per SSR and as dir. by E in C. |
| 3 | Excavating over areas in soft /loose soil, add to items03004for each additional 1.5 m orpart therof in depth beyond the first 1.5 m and getting out as per SSR & as dir by E in C. (max depth 0.75 mtr for earth pit) |
| 4 | Excavating over areas,n. exc. 1.5 m deep and getting out in hard/dense soil as per SSR and as dir. by E in C. |
| 5 | Demoliton and desmantling cement concrete unreinforced in ground floors and pavingexc. 15 cm thickness but above ground floors complete with all labour & accessories as per SSR & as dir by E in C. |
| 6 | Shinglefilling in floor or pavings in layers n exc. 15 cm thick, spread, levelled, and blinded with earth and rammed including watering as per SSR and As Dir. by E in C. |
| 7 | Laid dry bricks, sub class ‘B\" laid flat, in floors, old size brisks as per SSR & as dir by E in C. |
| 8 | Returning and filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm as per SSR and as dir. E in C. |
| 9 | Tubes, \" medium grade\", galvanised with all fitting; laid in trenches, bore of tube in40 mmas per SSR & as dir by E in C. |
| 10 | Tubes, \"medium grade\" galvanised, with all fittings;laid in trenches bore of tube in 150 mm as per SSR & as dir by E in C. |
| 11 | S & Lof reinforced concrete pipes, class NP2, laid and jointed complete with collars bore of pipe250 mm as per SSR & as dir by E in C. |
| 12 | M & L of Earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6 mm thick, burried directly in ground (earth pit not less than 2.25 meter deep below ground level ) with top edge of the plate not less\" than 1.5 mtrs below normal ground level, connected to galvanised iron strip25x4 mm as earthing leadby means of bolts, nuts, checks nuts and washers of galvanised iron or steel all as shown in elecrtical plate No. 3 connected to earthing test point all as specified or indicated including testing on completionas per SSR & as dir by E in C |
| 13 | Formwork to sides of pillers, posts, struts, piers, colums & stanchions square, rectangular or polygonal rough finished surfaces of concrete as per SSR & as dir by E in C. |
| 14 | TMT bars8 mm dia andover, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends & binding with & including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips as per SSR & as dir by E in C. |
| 15 | M&L of 4core PVCinsulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 300 sq.mm as per SSR & as dir by E in C. |
| 16 | M&L of 4core PVCinsulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 sq.mm as per SSR & as dir by E in C. |
| 17 | Providing of cement concrete type C2 1:3:6 40 mm graded aggregated in foundations, filling & mass concrete as per SSR & as dir by E in C. |
| 18 | S & F of framed brackets of angles or tees with web and flanges cut to shape, drilled and countershunk for srew, including bending and welding angles as necessary, gusset plates, riveting etc. n. exc. 10 kg each brackets confirming to Fe 290Gde -E-165 (Brackets over 10 kg each to be measured under \"Structural Steel\") as per SSR & as dir by E in C. |
| 19 | Supply Erection & commissioning ofweather proof , vermin proof M.S. fabricated outdoor electrical panelcubicle type , powder coated, duly painted with siemens grey color RL-7032, floor mounted with double door locking arrangement made up of M.S. Sheet 2 mm thick, having electrolytic grade copper BusBar of rating 400 Amp. Capacity duly wired & comprising ofsuitable ratings :- Incomer -1) 3 pole MCCB400 Amp, 50 KAwith thermal magbetic release with adjustable O/L & S/C setting - 01 No2) Digital multifunction meter with 3 CT class 1- 01 No. and RYB 3 ph. LEDindication controlled through 1 amp. mcb.Outgoing -1) 3 pole MCCB 160 Amp 36 KA with thermal magbetic release with adjustable O/L & S/C settingout going- 02 Nos. 2) 3 pole MCCB 100 Amp 36 KA with thermal magbetic release with adjustable O/L & S/C setting - 06 Nos. All switchgears make having L&T, Havells, Siemens or its substantially equivalent and conforms to IS/IEC-60947-2 complete with power and control wiring. Panel should be mounted on a suitable M.S angle standduly black painted with proper height from ground. GA drawing should be approved by OFV before fabrication of panel. |
| 20 | Termination of 3 1/2 core 300 sq.mm, LT PVC /XLPE armoured cable complete with M&L of required size of Aluminium Lug & cable gland as dir. byE in C. |
| 21 | Termination of 3 1/2 core 185 sq.mm, LT PVC /XLPE armoured cable complete with M&L of required size of Aluminium Lug & cable gland as dir. byE in C. |
| 22 | Credit for desmantled material i.e. PVC armoured/unarmoured cables and wires aluminium |
| 23 | Credit of old dismantled HG/MS/GI materials i.e. clamps/ channels/angles etc. |