| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-03-2026 | Amdt2 | Date | 30-03-2026 |
| 2 | 07-03-2026 | Amdt1 | Date | 23-03-2026 |
| 3 | 07-03-2026 | Amdt1 | Date | 23-03-2026 |
| Sl. No. | Item Description |
| 1 | Phase-I (Supply, Installation, testing and commisioning of lifts and connected works) |
| 2 | Taking down of existing 16/ 20 Passenger lift from existing bays at command hospital along with all connected electrical, mechanical connections and deposited to MES store yard with suitable arrangement of transportation and provision of temporary wooden door shutter at landing door opening for safety of the users till installation of new lift complete all as specified and as directed by Engineer-in-Charge. |
| 3 | Note : (i) Contractor will make good at his own cost, in case of any damage caused to surface of lift shaft & machine room during the dismantling and no separate payment will be made on this account for civil work as directed by Engineer-in-charge.(ii) Civil work : Necessary Civil work such as scaffolding in elevator shaft, cutting, making holes, grouting/ welding barricading for all openings of elevators to avoid accidents & disturbances during pre and post erection of lift and making good disturbed surfaces, modification to landing space to suite to car size, necessary foundation to machine, plastering of lift shaft wall etc. and two coats of white wash shall be applied on the lift shaft after completion of lift installation and all as per OEM recommendation/ suggestion during execution of work.(iii) Contractor/ OEM should follow all safety precautions/ accessories as per latest IS/ safety instruction while working on elevator. Quoted Rate against item shall be deemed to include the cost of the same. |
| 4 | Design supplying, installing, testing & commissioning of electrically operated gearless 16 Passenger (1088 Kg) capacity lifts to serve 6 floors i.e. G + 5 upper floors (6 stops and 6 openings) in the existing lift well, confirming to all relevant IS, speed 1.0 metre/sec with rope technology with machine room, car and counter weight solid type automatic micro stroke button control, microprocessor based controller, simplex DX with FC control suitable for 3 phase, 415 volts, 50 Hz, AC supply, independent operation with AC Variable Voltage Variable Frequency [AC VVVF] drive control [closed loop] with power saving regenerative drive with all standard accessories, simplex automatic & manual dual controlled operation with suitable gearless motor traction type with and without attendant, suitable for synchronised operation, automatic power operated centre opening sliding type stainless steel (SS 304) doors of thickness 1.5 mm with vision panel (half glass) with vandal proof finish, door dimension shall be 1000 mm x 2000 mm integral height, Car Design shall be as per OEM, ....contd. |
| 5 | Contd....Car Panel Finish with 1.5 mm thick SS Vandal proof textured, having full curtain infrared sensor safety (3D infra red sensors for car doors along the full height), UPS based Automatic Rescue Device [ARD] system and suitable batteries, Floor position digital indicators in car and all landings with call indicating lights, built in voice announcing system without hand set, Correction drive to next level, Emergency alarm@main floor, car call backward, over load function, constant indication/buzzer, bypass load funnction, auto cut off Fan and light, Manual Rescue Operation, centralised hoisting for lesser vibration and smooth travel, pit ladder, Micro Movement LED based Buttons, Load Weighing Device (LWD) direction and position Indicator In car & Landing, contd.... |
| 6 | contd…Advance car position indication, Phase reversal functioning, signal fixtures + 10% voltage withstanding capacity, door open button, car door locking including necessary joists and beams for mounting the machine in machine room including addition/ alteration to existing lift well if any, all necessary civil works required in connection with erection of lift complete all as specified and as directed. |
| 7 | Design supplying, installing, testing & commissioning of electrically operated gearless 20 Passenger (1360 Kg) capacity lifts to serve 6 floors i.e. G + 5 upper floors (6 stops and 6 openings) in the existing lift well, confirming to all relevant IS, speed 1.0 metre/sec with rope technology with machine room, car and counter weight solid type automatic micro stroke button control, microprocessor based controller, simplex DX with FC control suitable for 3 phase, 415 volts, 50 Hz, AC supply, independent operation with AC Variable Voltage Variable Frequency [AC VVVF] drive control [closed loop] with power saving regenerative drive with all standard accessories, simplex automatic & manual dual controlled operation with suitable gearless motor traction type with and without attendant, suitable for synchronised operation, automatic power operated centre opening sliding type stainless steel (SS 304) doors of thickness 1.5 mm with vision panel (half glass) with vandal proof finish, door dimension shall be 1200 mm x 2000 mm integral height, Car Design shall be as per OEM, ....contd. |
| 8 | Contd....Car Panel Finish with 1.5 mm thick SS Vandal proof textured, having full curtain infra red sensor safety (3D infra red sensors for car doors along the full height), UPS based Automatic Rescue Device [ARD] system and suitable batteries, Floor position digital indicators in car and all landings with call indicating lights, built in voice announcing system without hand set, Correction drive to next level, Emergency alarm@main floor, car call backward, over load function, constant indication/buzzer, bypass load funnction, auto cut off Fan and light, Manual Rescue Operation, centralised hoisting for lesser vibration and smooth travel, pit ladder, Micro Movement LED based Buttons, Load Weighing Device (LWD) direction and position Indicator In car & Landing, contd.... |
| 9 | contd…Advance car position indication, Phase reversal functioning, signal fixtures + 10% voltage withstanding capacity, door open button, car door locking including necessary joists and beams for mounting the machine in machine room including addition/ alteration to existing lift well if any, all necessary civil works required in connection with erection of lift complete all as specified and as directed. |
| 10 | Notes for serial item No. 2.00 & 3.00: The lift(s) shall be provided with and including the following: [a] Fireman Switch/ Drive[b] UPS based Automatic Rescue Device [ARD] during power failure including manual operation provision with suitable capacity of batteries designed for running the lift with full load. The ARD batteries shall be securely housed in a suitable battery box fabricated from 1.5 mm thick MS sheet duly powder coated for corrosion resistance, with an insulating mat provided inside to ensure electrical safety and prevent direct contact between the batteries and the metal surface including provision of suitable locking arrangement[c] Battery operated emergency light [LED Ceiling Fitting] alarm [speaker for emergency alarm system to be fixed] and stop button in car with rechargeable arrangement for battery.[d] LED light fitting, 6 Nos, square spot lights, wattage as per Manufacturer\"s recommendation recessed mounted in false ceiling. |
| 11 | Notes contd..[e] Provision of two axial flow fans suitable for recessed mounting in false ceiling.[f] Provision of premium quality 3 mmthick aluminium chequered plate as in flooring for lift car.[g] Non stop button/ independent operation.[h] Over load warning indicator in COP with voice announciation and overload protection/ tripping system having relays , etc.[i] Stainless steel door frame and sliding doors (two panel) with centre opening vision panel and front opening for all landings made of 1.5 mm thick, 304 grade stainless steel vandal proof sheet.[j] Landing door frames shall be made of 1.5mm thick 304 grade stainless steel vandal proof sheet. |
| 12 | Notes contd..[k] All the dimensions of the lift and connected items shall be designed in accordance with the existing opening size and in conformity with IS 17900 amended upto date standards and the contractor shall submit the design drawing to Accepting Officer for approval before commencement of work. Contractors are advised to visit the site before quoting the tender. The contractor shall be deemed to have visited the site whether he actually visited the site or not. No claim whatsoever shall be admissible on this account at later date.[l] Provision of built-in voice announciating system for floor announciation, direction of lift movement i.e. moving up and moving down, doors opening and doors closing announciation with background music complete all as specified, directed and approved by Engineer-in-charge/GE.[m] Provision of voice announciating system for ARD operation during power failure complete all as specified, directed and as approved by Engineer-in-charge/GE. |
| 13 | Notes contd..[n] Set of three in number limit switches at the bottom and top most position of lift hoist way as specified in IS.[o] A safety instruction plate, duly embossed or laser printed on an SS-304 grade stainless steel sheet of suitable size and thickness, shall be riveted inside the lift car at a clearly visible location, displaying the content in English and Hindi with letters of sufficient size to be easily readable by the users as directed by the Engineer-in-Charge.[p] Provision of Car Operating Panel [COP] which shall be made of silver brushed stainless steel face panel and shall run upto full height of the car cabin with LCD display, square, surface mounted button to indicate various information such as floor level, directional arrow, overload, ARD functioning and other relevant signals alongwith push buttons incorporating Braille/ raised letters in sharp contrast to the background, to aid persons with visual impairments in compliance with Clause B-6.4.5(c) of NBC of India 2016. |
| 14 | Notes contd..[q] Provision of suitable phase reversal relays to the controller to protect lift/ equipment against phase reversal, phase failure and low voltage.[r] Provision of 3 way Intercom system with hand set at Ground floor and machine room andbuilt in push to talk(PTT) in COP without hand set.[s] Provision of round bend hand rail made out of silver brushed stainless steel pipe of 304 Grade at rear wall.[t] Provision of Landing Operating Panel [LOP] at floors which shall be made of 7 segment display, flush mounted, siver brushed stainless steel to indicate both the floor level and directional arrow, along with push buttons incorporating Braille/ raised letters in sharp contrast to the background, to aid persons with visual impairment in complaince with Clause B-6.4.5(b) of NBC of India 2016.[u] Steel Wire rope of adequate size as per relevant IS and as per manufacturers specification. |
| 15 | Notes contd..[v] Other standard fixtures and fittings like guide rails, sheaves, counter weights with guards, buffers, gear unit brakes, control panel, car operational panel, governor, locks, power control and trailing cables complete all as per latest IS specifications.[w] Main drives and controls shall be high efficient and low power consumption.[x] Lift design, specifications, drawings, manufacturers instructions shall be got approved from Accepting Officer before placing order for procurement.[y] The contractor shall carry third party load testing for each lift installed once in every six months till defect liability period and shall submit satisfactory test results and the rate quoted shall be deemed to included for this provision.[z] The OEM shall have test tower with testing facility as specified in tender documents and OEM shall provide test report before dispatch of lifts from the factory. OEM shal issue IGBC certificate as per Green Building Concept. |
| 16 | Notes contd..[aa] Provision of CCTV Camera, 3MP, 2K, made in India with Micro SD memory card storage sufficient enough to store the 24 x 7 video recording upto 1 month, housed in a stainless steel safety grill with small padlock complete fixed in lift car. A separate UPS with battery, suitable to provide a minimum of 15 minutes backup for the CCTV system, shall be installed in the machine room and the power supply to the CCTV shall be connected from the UPS through an independent cable drawn along with the trailing cable.[ab] Cloud connected services: Lift OEM shall have a round the clock cloud connected diagnostic service which can gather operational data of lift and gather the condition of the lift equipments in real time and analyze the data to solve any potential problem before occurance. |
| 17 | Notes contd..[ac] Automated Breakdown Notification System: The lift shall be equipped with an intelligent controller capable of detecting and diagnosing faults or malfunctions in real time. In the event of any lift breakdown or critical fault, the controller shall automaticallytrigger on SMS. Upon rectification of the fault and restoration of functionality, the system shall automatically trigger a follow-up SMS indicating that the lift is operational.[ad] SMS Alert Configuration: The system shall be configured to send SMS messages to the designated personnel, including but not limited to the following:-(i) Lift Technician(ii)Executive(iii)Engineer-in-Charge[ae] After completion of installation work, The OEM shall provide documentation and training for the configuration and handling of the elevation to minimum two Nos of persons nominated by GE. In addition OEM will provide basic training for rescuing passengers entrapped in elevators. |
| 18 | [af] Directional signs indicating the location of an accessible lift to transport persons with disabilities at all usable levels shall be provided at a location that is clearly visible from the accessible building entrance. The directional signs shall incorporate a representation of the international symbol of accessibility in compliance with Clause B-6.4.1 of NBC of India 2016.[ag] Solid cast iron blocks only shall be used for Counterweight. No other castings shall be permitted.[ah] The mild steel machined guide rails shall only be permitted. the minimum thickness of guide rails shall be 16mm for the car and 10mm for the counterweight.[aj] Providing and fixing landing toe guards from the bottom of the sill support upto the next floor door header level to cover the exposed wall surfaces with 1.5 mm thick GI sheet, complete with all necessary fixing accessories, fasteners and supports to the wall surface as specified and directed by the Engineer-in-Charge. |
| 19 | Additional Notes for Ser item Nos. 2.00 & 3.00: (i) The Contractor shall upload with the documents under cover I \"Memoradum of Understanding\" (MOU) on non-judicial stamp paper of Rs. 100 with OEM of lift/ elevators which meets the QR criteria mentioned in MOU format for Supply, Installation, Testing and Commissioning of lifts and provision of attending any defect during liability period of 02 years. format of MOU has been attached at serial page No. 139 to 148 of tender documents.(ii) The Contractor along with Lift Manufacturer/ OEM shall arrange and conduct a comprehensive presentation at Accepting officer’s premises in presence of user after bid submission end date and as per time and date decided by Accepting officer covering all points as mentioned in MOU failing which the bid will be summarily rejected and the Financial Bid shall not be opened. |
| 20 | additional notes contd..(iii) The pre-dispatch factory inspection of the complete lift shall be carried out at the manufacturer\"s premises by a rep nominated by the Accepting Officer. A report shall be prepared and submitted duly signed by authorised signatory of OEM, the contractor and the rep of the Accepting Officer and shall be approved by the Accepting Officer before dispatching the material from the manufacturer\"s factory. The contractor in liason with the manufacturer shall make all necessary arrangements for the inspection and intimate the department at least 15 days prior to the date of inspection.(iv) Comprehensive maintenance of all the lifts to be provided under this contract is also to be carried out during the defect liability period of two years. All the clauses of particular specifications applicable for Comprehensive Maintenance post defect liability period under Sch ‘A’ shall be applicable to Comprehensive Maintenance during defect liability period of 02 year also and quoted rates shall include the cost of comprehensive maintenance during defect liability period and nothing extra shall be admissible on this account. |
| 21 | additional notes contd..(v) Since lifts are to be installed in hospital building, the first two lifts shall start its service to the hospital immediately after their commissioning. Comprehensive maintenance for the first two lifts shall start from the day of their commissioning. Contractor’s quoted rates against the supply, installation, testing and commissioning of the lift item shall be inclusive of comprehensive maintenance to these two lifts upto the completion of phase-I and all the four Nos of lifts installed under this contract during the defect liability period after completion of Phase-I of the contract.(vi) The contractor shall provide all necessary tools, plants & Machinery to move the material upto the machine room (G+6) without any extra cost.(vii) The drawing for lifts shall be provided by the contractor from OEM before execution of work and same to be approved by the GE. |
| 22 | Supplying, laying and commissioning of XLPE insulated, screened, PVC bedded, galvanized steel stranded armoured, electric power cable (Heavy duty) with stranded Aluminium conductor, 1100 Volt graded, 16 sqmm, 4 Core, including necessary fixtures like clamp, screws, saddles etc., to fix in wall/ floor/ chases etc. complete all as specified and as directed by Engineer-in-Charge. |
| 23 | S&F sheet metal enclouser for Distribution Board (DB), VTPN, 4 way for MCCB as incomer, metal door, ready to use DBs provided with shrouded Neutral Bar, Mechanical Impact Strength IK-09 certified, fully Insulated busbar assembly, 2 neutral bar, 2 earth bar, cable ties, blanking plates, PU Gasket suitable for 4 pole MCCB\"s upto 160 Amp as Incomer and MCBs (TP/ TPN/ SP/ SPN) as outgoing, IP 54 protection, conforming to IEC 61439-3 complete all as specified and as directed. |
| 24 | S&F MCCB, 63 Amp, 4 Pole, 415 Volt, Ics=100% of Icu=100% of Icw,16 kA with microprocessor based thermal magnetic release complete all as specified and as directed. |
| 25 | S&F MCB, triple Pole andneutral (TPN), 40-100 Amps, 415 Volt, \"C\" Curve with rupturing capacity not less than 10 kA all as specified and directed by Engineer-in-Charge. |
| 26 | S&F MCB, Single Pole (SP), 06-32 Amps, 240 Volt, \"B\" Curve with rupturing capacity not less than 10 KA all as specified and directed by Engineer-in-Charge. |
| 27 | Taking down carefully old unserviceable aluminium/ copper point wiring for light/ fan/ socket or power point complete including all fittings such as switches, ceiling rose, pendents,regulators, sockets, bell, distribution boards and MCB\"s etc., and making good disturbed surface of walls. floors etc to match with the existing surface complete all as specified and as directed. |
| 28 | M&L for Point wiring complete with 1.5 sqmm, PVC insulated, unsheathed, multi-stranded FRLSH copper conductor cable, 1100 Volts grade, ISI marked, drawn through in and including suitable dia of in stove enmelled steel conduit, medium grade and conduit accessories, concealed in concrete/ brick masonry walls, roofs, floors etc., by means of saddles and clips etc., including provision of modular metal flush boxes of thickness not less than 1.2 mm with modular frame plate and white cover of required modules for housing switches, sockets, regulators etc., including 1.5 sqmm, PVC insulated, unsheathed, multi-stranded, FRLSH copper conductor cable as earth continuity conductor for One light point controlled by one modular switch and connecting to common earth dolly complete all as specified and as directed by Engineer-in-Charge. |
| 29 | NOTE: (a) The quoted rate shall deemed to include the cost of metal flush boxes, modular white cover plate, provision of blank plates as per site requirement etc.,(b)Quoted rate shall also deemed to include cost of making necessary chases in walls/ floor for inserting steel conduit/ metal boxes/ DBs and making good the disturbed surfaces to match with existing. |
| 30 | S&F Modular switch, 1 way, 6 Amps, 1 module and conforming to IS 3854 complete all as specified and directed by Engineer-in-Charge. |
| 31 | Supply and fixing of flameproof cum water proof LED Bulk Head light fitting, 15 Watt, cast Aluminium alloy material and heat and Impact resistance, IP-66 protection, toughen \"A\" clear glass having anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and as directed by Engineer-in-Charge. |
| 32 | M&L for earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32 x 6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 40 mm dia GI pipe, light grade, earth plate shall be surrounded by alternate layer of coal dust and common salt 15 cm thick each layer all as per electrical plate and connected to pole structure/ panel board/ earthing test point all as shown in electrical plate No. 3 of SSR Part-I (2009) and testing on completion includingexcavation, earth work in any type of soil, provision of earth pit in plain cement concrete 1:3:6 mix, Type C-1, earth pit cover, 40 mm thick RCC 1:2:4 mix type B-1 reinforced with 8 mm dia TMT bars @ 150 mm C/C both ways, GI funnel with 20 mm bore GI pipe, medium grade watering pipe, wire mesh, protection pipe, earth strip upto 7.50 metre long complete including taking down of old unserviceabe earthing complete all as specified and as directed by Engineer-in-Charge. |
| 33 | Note:(a) Rate quoted shall deemed to include cost of excavation in any type of strata, Returning filling and removal upto 50 mtr, PCC pit, funnel and RCC cover etc.,(b) Rate quoted shall deemed to include GI earth strip upto 7.5 metres.(c) Alternate bed of charcoal/ salt to be done in 3 x 15 cm depth of salt and 3 x 15 cm depth of charcoal.(e) PVC type DC insulators with screws, nuts, bolts etc to be used in surface/walls/floors for mounting of strip and distance between two insulator shall not be more than 1.0 metre.(f) The strip will be measured and paid separately beyond 7.5 metre for each earthing. |
| 34 | M&L for galvanised iron strip of size 32 x 6 mm as earth continuty conductor or main earthing lead, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or any other indicated situation for loop earthing etc., as required including PVC saddles with necessary nut & bolt, screws etc., complete all as specified and as directed by Engineer-in-Charge. Note(i) PVC type DC insulators with screws, nuts, bolts etc to be used in suface/wall/floor for mounting of strip and distance between two insulator shall not be less than 1.0 mtr.Rate quoted shall deemed to be included the PVC DC insulators.(ii) The strip will be measured and paid separately beyond 7.5 metre for each earthing. |
| 35 | Demolition of stone slabs and tiles of any description or thickness in floors, aprons etc., Laid, bedded and pointed in any mortar complete all as specified and as directed by Engineer-in-Charge. |
| 36 | M&L for 18-20 mm thick Granite (of any type) work, (table rubbed and polished) in vertical surface steps, jambs, pillars, window cills, cooking platforms and like in cement mortar (1:4) including pointing in white cement (1:2) using marble dust with admixture of pigment to match with shade of granite over and including 15 mm thick cement mortar 1:4 complete all as specified and directed by Engineer-in-Charge. |
| 37 | Extra over Granite or marble slabs as in rounding to edges of stone slabs one edge, such as in steps, cooking platform, and other similar situations etc., complete all as specified and directed by Engineer-in-Charge. |
| 38 | M&L for Marble work of baroda green 18 to 20 mm (table rubbed and polished) in steps, jambs, pillars, window cills, shelves, cooking platforms and like in cement mortar (1:4) including pointing in white cement (1:2) using marble dust with admixture of pigment to match with marble shade over and including 15 mm thick cement screed 1:4 complete all as specified and directed by Engineer-in-Charge. |
| 39 | Demolition of cement concrete (un-reinforced) of any description and in any position not otherwise specifically provided for complete all as specified and directed by Engineer-in-Charge. |
| 40 | M&L for PCC 1:2:4, type B-1 (using 20 mm graded stone aggregate) overroof slab to fill depressions of existing roof slab, roof kerbs or mud stops, rounded or chamfered on edges including cleaning/ removing all dust from existing roof surfaces before placing concrete complete all as specified and as directed by Engineer-in-Charge. |
| 41 | M&L for 25 mm thick Cement Conrete 1:2:4, type B–0 (using 12.50 mm graded stone aggregate) in flooring, finished even and rough to receive topping layer complete all as specified and as directed by Engineer-in- Charge. |
| 42 | Taking down cement plaster on brick or stone walls, etc. including raking out joints, hacking for key, scrubbing down with water, etc. complete all as specified and as directed by Engineer-in-Charge. |
| 43 | M&L for rendering 10 mm thick on fair faces of brick work or concrete surfaces in Cement Mortar 1:6, finished even & smooth without using extra cement complete all as specified and as directed by Engineer-in-Charge. |
| 44 | M&L for preparation of newly plastered surfaces of wall and applying two coats of oil bound distemper over and including 01 mm thick cement based wall care putty complete all as specified and as directed by Engineer-in-Charge. |
| 45 | S&F Solid PVC Wall Lining consisting of 5 mm thick Plain colour PVC sheet inclusive of solvent cement and fixing at site on PVC frame as per specifications and drawing including necessary fillets, all accessaries complete including dismantling of existing wall lining complete all as specified and as directed. |
| 46 | M&L for Wall panelling including connected work for hospital building as per following specification:(a) Wall panel/ Cladding : Material and labour for pre-fabricated wall panelling made of Stainless Steel 304 Grade with 50 to 60 mm thick puff insulation with pressure injected rigid polyurethane foam minimum density 40 kg/cum, sandwiched between inner and outer stainless steel sheeting having 0.80 mm thickness. The wall panels shall be fixed on and including metal Grid frame work, sufficient enough to withstand the entire wall panelling work including making/ cutting necessary opening if any, required as per site conditions for fixing switch boards/ gas pipeline/ electrification works and equipment etc., (b) Joints. The individual wall panel shall use the tongue and groove/ suitable technology for joining two panels with minimum number of junctions. No welding shall be allowed. Contd...27.00 |
| 47 | Contd...27.00The gaps between Wall Panels to be filled with metalic epoxy filler and sanded flush giving seamless appearance and finished to fine grain surface to the entire wall panelling. The angular corners to be made with 130-140 degree angular modular element.(c) Anti Bacterial Paint : The stainless steel wall Panelling to be painted with dryfilm thickness of minimum 300 microns over primer. The paint shall be Anti-bacterial/ Anti-microbial/ Antifungal, resistant to UV lights, disinfactants, steams, fumigation agents etc., Painting to be applied by approved applicator with airless spray gun, Color and tint of paint to be approved by the User. the painting protection and preventation of the growth of mould, bacteria and yeasts for 5 years be given by the manufacturer. The wall Panels shall be CE/ UL/ ETL/ US FDA/ BIS/ DIN 1.4301 Certified/ Listed. Test report from Govt certified lab for anti-microbial, Stainless steel & properties of paint will be submitted by the contractor. |
| 48 | Material & Labour for providing and fixing stainless steel (Grade 304) railing/ Angles made of hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, including fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of floor or the side of waist slab with suitable arrangement complete all as specified and as directed by Engineer-in-Charge. |
| 49 | Phase-II (Comprehensive Maintenance) |
| 50 | M&L for Comprehensive Maintenance of Electrically operated electrically operated lifts suitable for serving passengers/ patients/ load carrying lifts (20 Passenger/ 1360 Kg capacity) to serve 6 floors i.e. G + 5 upper floors installed at Command Hospital (WC) Chandimandir as mentioned under revelent items of Phase-I with collective/ selective control by carrying out periodical checks, attending the breakdown of lifts if any, repairing the lifts including replacement of defective spares/ accessories etc. and testing as specified and as recommended by the OEM to ensure smooth, safe and efficient functioning during first year after expiry of defects liability period complete all as specified and as directed by Engineer-in-Charge. |
| 51 | Notes for Serial Item No. 29.00 above:(a) Contractor will conclude AMC for contract with OEM and copy of the agreement will be submitted to Engineer-in-Charge and GE before commencement of AMC.No payment will be made to contractor without submission of valid AMC agreement.(b) The rate quoted is deemed to be inclusive of supply and fixing of all Major and Minor Spares viz. Mechanical/ Electrical/ Electronic/ LED Lights etc.,as and when required for trouble free, smooth and efficient functioning of lifts including overhauling as and when required to all mechanical parts of lifts, Rewinding of Electric Motors, repair/ maintenance of Gear Unit, repair/ maintenance of Door Drive, Controllers, Pulleys, Limit Switches, Relays etc. complete all as directed by the Engineer-in-Charge.(c) All the safety measures including ARDs shall be ensured for serviceable condition round the clock and nothing extra shall be paid on these accounts. |
| 52 | [c] The rate quoted shall be deemed to be inclusive of testing of each lift by Licensed Lift Inspector of State Government twice in a year in every six months for worthiness of the Lift in respect of safety. Certificate issued by the Licensed Lift Inspector shall be submitted to the Engineer-in-Charge and a copy of Certificate shall be displayed in all Lift Cabins as directed by Engineer-in-Charge.[d] Monthly, Quarterly maintenance registers shall be maintained and signed by the site engineer and contractor.[e] Load testing shall be arranged by the contractor to the Lift for which repairs were carried out as and when directed by Engineer-in-Charge.[f] Necessary items required for maintaining functionality will be deemed to be included in the cost and shall be borne by the contractor till completion of comprehensive maintenance. |
| 53 | All as per description of Serial Item No. 29.00 but for Second year after expiry of defects liability period. |
| 54 | All as per description of Serial Item No. 29.00 but for Third year after expiry of defects liability period. |
| 55 | M&L for Comprehensive Maintenance of Electrically operated electrically operated lifts suitable for serving passengers/ patients/ load carrying lifts (16 Passenger/ 1088 Kg capacity) to serve 6 floors i.e. G + 5 upper floors installed at Command Hospital (WC) Chandimandir as mentioned under revelent items of Phase-I with collective/ selective control by carrying out periodical checks, attending the breakdown of lifts if any, repairing the lifts including replacement of defective spares/ accessories etc. and testing as specified and as recommended by the OEM to ensure smooth, safe and efficient functioning during first year after expiry of defects liability period complete all as specified and as directed by Engineer-in-Charge. |
| 56 | Notes for Serial Item No. 32.00 above:[a] The rate quoted is deemed to be inclusive of supply and fixing of all Major and Minor Spares viz. Mechanical/ Electrical/ Electronic/ LED Lights etc.,as and when required for trouble free, smooth and efficient functioning of lifts including overhauling as and when required to all mechanical parts of lifts, Rewinding of Electric Motors, repair/ maintenance of Gear Unit, repair/ maintenance of Door Drive, Controllers, Pulleys, Limit Switches, Relays etc. complete all as directed by the Engineer-in-Charge.[b] All the safety measures including ARDs shall be ensured for serviceable condition round the clock and nothing extra shall be paid on these accounts. |
| 57 | [c] The rate quoted shall be deemed to be inclusive of testing of each lift by Licensed Lift Inspector of State Government twice in a year in every six months for worthiness of the Lift in respect of safety. Certificate issued by the Licensed Lift Inspector shall be submitted to the Engineer-in-Charge and a copy of Certificate shall be displayed in all Lift Cabins as directed by Engineer-in-Charge.[d] Fortnight, Quarterly maintenance registers shall be maintained and signed by the site engineer and contractor.[e] Load testing shall be arranged by the contractor to the Lift for which repairs were carried out as and when directed by Engineer-in-Charge.[f] Necessary items required for maintaining functionality will be deemed to be included in the cost and shall be borne by the contractor till completion of comprehensive maintenance. |
| 58 | All as per description of Serial Item No. 32.00 but for Second year after expiry of defects liability period. |
| 59 | All as per description of Serial Item No. 32.00 but for Third year after expiry of defects liability period. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail