| 1 | ITEMS APPLICABLE FOR JOB \"A\" |
| 2 | Supply, Installation, tesing and commisssioning in replacement of Hepa filters frame with CRCA Steel casing with epoxy powder coated / aluminium with imported micro fibre glass media with efficiency of 99.97 down to 0.3 micron of size 915mm x 610mm x 150mm, Flange type including taking down old/unsv one complete all as specified and directed (Half yearly 2 x 20 Nos=40 Nos)(Location - OT Complex) |
| 3 | All as per Item No 1.00 but Hepa filters of framesize 610mm x 305mm x 150mm, Flange type (Half yearly 2 x 10 Nos=20 Nos) complete all as specified and directed.(Location - OT Complex) |
| 4 | All as per Item No 1.00 but Hepa filters of framesize 610mm x 610mm x 75 mm, Flange type (Half yearly 2 x 8 Nos=16 Nos) complete all as specified and directed.(Location - OT Complex) |
| 5 | All as per Item No 1.00 butHepa filters of framesize 610mm x 292mm x 203mm, Box type (Half yearly 2 x 6 Nos=12 Nos) complete all as specified and directed. (Location - CTVS OT) |
| 6 | All as per Item No 1.00 but Hepa filters of framesize 610mm x 610mm x 305mm, Flange type (Half yearly 2 x 8 Nos=16 Nos) complete all as specified and directed.(Location - ART Centre (12 Nos) and Labor room Family Wing (04 Nos) |
| 7 | All as per Item no 1.00 butHepa filters offramesize 610mm x 610mm x 150mm, Flange type (Half yearly 2 x 9 Nos=18 Nos complete all as specified and directed.(Location - BMT Centre Family Wing) |
| 8 | All as per Item no 1.00 butHepa filters offramesize 610mm x 305mm x 300mm, Flange type (Half yearly 2 x 3 Nos=06 Nos complete all as specified and directed.(Location -Labor room Family Wing) |
| 9 | All as per Item no 1 butHepa filters frame of size 305mm x 305mm x 300mm, Flange type (Half yearly 2 x 1 Nos=02 Nos complete all as specified and directed.(Location -Labor room Family Wing) |
| 10 | Notes for Item No 1.00 to 8.00 above:- 1) Make of filter: AEROSOL / MAF / DYNA / JOHNFLOWER2) The replacement of filters shall be carried out on Half yearly basis. |
| 11 | S&F in replacement Discharge (fine) filter, 5 micron of size 500X500X150 mm for AHUs at different locations of 2 x 120 TR capacity complete all as specified and directed(Location - OT Complex) |
| 12 | S&F in replacement Discharge(fine) filter, 5 micron of size 600X500X150 mm for AHUs at different locations of 2 x 120 TR capacity complete all as specified and directed.(Location - OT Complex) |
| 13 | S&F in replacementSuction filter(pre),10 micron of size 500x500x50 mm for AHUs at different locations of 2x120 TR capacity complete all as specified and directed (Location - OT Complex) |
| 14 | S&F in replacement Suction filter(pre),10 micron, of size 600x600x50 mm for AHUs at different locations of 2x120 TR capacity complete all as specified and directed (Location - OT Complex) |
| 15 | S&F in replacement Pre filter (Rough) box type, 20 micron,of size of 610x305x150 mm for AHUs at different locations of plant capacity 2 x 5.5 TR complete all as specified and directed.(Location - ART Centre Family wing) |
| 16 | S&F in replacement Pre filter (Rough) box type, 20 micron,of size of 610x610x150 mm for AHUs at different locations of plant capacity 2 x 5.5 TR complete all as specified and directed. (Location - ART Centre Family wing) |
| 17 | S&F in replacement Pre filter (Rough) box type, 20 micron,of size of 610x610x50 mm for AHUs atdifferent locations of plant capacity 3 x 12.5 TR complete all as specified and directed (Location - Labor room Family wing) |
| 18 | S&F in replacement Pre filter (Rough) box type, 20 micron,of size of 610x305x50 mm for AHUs at different locations of plant capacity 3 x 12.5 TR complete all as specified and directed (Location - Labor room Family wing) |
| 19 | S&F in replacement Pre filter (Rough) box type, 20 micron,of size of 305x305x50 mm for AHUs at different locations of plant capacity 3 x 12.5 TR complete all as specified and directed (Location - Labor room Family wing) |
| 20 | S&F in replacementAir filter (Carbon filter) box type, 5 micron ofsize 610x305x50 mm for AHUs at different locations of plant capacity 2 x 5.5 TR and 3x12.5 TR complete all as specified and directed (Location - ART Centre (02Nos) and labor room Family Wing (03 Nos) |
| 21 | S&F in replacement Air filter (Carbon filter) box type, 5 micron of size 610x610x50 mm for AHUs at different locations of plant capacity 2 x 5.5 TR and 3x12.5 TR complete all as specified and directed (Location - ART Centre (02Nos) and labor room Family Wing (02 Nos) |
| 22 | S&F in replacement Air filter (Carbon filter) box type, 5 micron of size 305x305x50 mm for AHUs at different locations of plant capacity 3 x 12..5 TR complete all as specified and directed (Location -Labor room Family wing) |
| 23 | S&F in replacement Discharge (Fine filter) flange type, 5 micron of size 610x305x305 mm for AHUs at different locations of plant capacity 2 x 5.5 TR and 3x12.5TR complete all as specified and directed (Location - ART Centre (02 Nos) ,Labour room(03Nos) Family wing) |
| 24 | S&F in replacementDischarge (Fine filter) flange type, 5 micron of size 610x610x305 mm for AHUs at different locations of plant capacity 2 x 5.5 TRand 3 x 12.5TR complete all as specified and directed. (Location - ART Centre (02 Nos) ,Labour room(02Nos) Family wing) |
| 25 | S&F in replacementDischarge (Fine filter) flange type, 5 micron of size 610x610x305 mm for AHUs at different locations of plant capacity 2 x 5.5 TRcomplete all as specified and directed (Location - Labour room Family wing) |
| 26 | S&F in replacementPre filter (Rough) flange type, 10 micron of size for AHU 610x610x50 mm at different locations of plant capacity 1 x 5.5 TR and 2X8.5TR complete all as specified and directed.(Location - BMT Centre Family wing and CTVS OT) |
| 27 | S&F in replacement Pre filter (Rough) Flange type, 10 micron of size for AHU 610x305x50 mm at different locations of plant capacity 1 x 5.5 TR and 2X8.5TR complete all as specified and directed.(Location - BMT Centre Family wing and CTVS OT) |
| 28 | S&F in replacement Discharge Air filter (Fine filter) Flange type, 5 micron of size for AHU 610x610x300 mm at different locations of plant capacity 1 x 5.5 TRand 2X8.5TR complete all as specified and directed.(Location - BMT CentreFamily wing and CTVS OT) |
| 29 | S&F in replacementDischarge Air filter (Fine filter) Flange type, 5 micron of size for AHU 610x305x300 mm at different locations of plant capacity 1 x 5.5 TR and 2X8.5 TR complete all as specified and directed. (Location - BMT Centre Family wing and CTVS OT) |
| 30 | S&F in replacement SSsemi Perforated plenum sheet of thickness 3mm and size of915mmX610mm for HEPA filter housing including necessary fabrication work ,fittings ,bolts nuts as per existing complete all as specified and directed. (Location - Main OT) |
| 31 | S&F in replacement SS semi Perforatedplenum sheet of thickness 3mm and size of610mmX305mm for HEPA filter housing including necessary fabrication work ,fittings ,bolts nutsas per existing complete all as specified and directed.(Location - Main OT) |
| 32 | S&F in replacement SS semi Perforatedplenum sheet of thickness 3mm andsize of 1800mmX610mm for HEPA filter housing including necessary fabrication work ,fittings ,bolts nutsas per existing complete all as specified and directed. (Location - ART Centre Family wing) |
| 33 | S&F in replacement SS semi Perforatedplenum sheet of thickness 3mm and size of610mmX610mm for HEPA filter housing including necessary fabrication work ,fittings ,bolts nuts complete all as specified and directed.(Location - BMT Centre Family wing) |
| 34 | S&F in replacement SS semi Perforated (SS304)plenum sheet of thickness 1mm andsize of 305mmX305mm for exhaustAir housing including necessary fabrication work, fittings, bolts nuts of different locations complete all as specified and directed.(Location - OT, BMT, ART Centre, Labor room Family wing) |
| 35 | S&F Nozzel assemblyof 75mm as in existing make/ type/size of FRP cooling tower suitable for 3x12.5 TR capacity including removing of unserviceable nozzle set with fittings/fixtures complete all as specified and directed. |
| 36 | S&F in replacement Dehumidifer controlleras per existing complete all as specified and as directed. |
| 37 | S&F in replacement Power contactor withbuilt-in conventional coil 230 V / 415 V of Compressor motor starter of Cap upto 215 A type for 2x120 TR AC Plant complete all as specified and directed. |
| 38 | S&F in replacement synthetic rubber insulating mat of size 3m x 1m x 3mm all as specified and directed. |
| 39 | S&F in replacement Air Pressure cut off switch as in existing make/type, operates between 30-90 PSI for Air compressor plant complete all as specified & directed |
| 40 | S&F in replacement Air filter as in existing make/size operates between 30-90 PSI for Air compressor plant all as specified and directed. |
| 41 | S&F Power contactor MNX 12 of 12 Amp, 415 V AC rating, 03 pole,Coil230 V, 50 Hzand making all electric connection including taking down of unserviceable contactor complete all as specified and directed. |
| 42 | S&F Power contactor MNX A1 of 09 Amp 415V AC rating, 03 pole, with 2NO+2NC Aux Contacts, Coil230 V, 50 Hz and including taking down of unserviceable contactor and making all electric connection, complete all as specified and directed. |
| 43 | S&F Printed circuit board (PCB) for inverter compressor 6.5 TR model No : VZH044CGANB of existing make Including taking down of unserviceable PCB and making all electric connection complete all as specified and directed. |
| 44 | S&F in replacement of Exhaust Air Unit Blower motor assembly including centrifugal Fan blade with all the necessary fixing arrangments suitable for central AC Air Handling Unit all as specified and directed. |
| 45 | S&F in replacement of AHU Blower motor assembly including centrifugal Fan blade with all the necessary fixing arrangments suitable for central AC Air Handling UnitModel No RDH 280 R complete all as specified and directed. |
| 46 | S&F in replacement of 3 Way mixing valves of size 65/50 mm with modulating actuator withthermostat control M912 B, companion flanges, nuts, bolts, washers and gaskets etc complete all as specified and directed. |
| 47 | ITEMS APPLICABLE FOR JOB \"B\" |
| 48 | Comperehensive maintainence and servicing of following mentioned OT Light fittings including Control Panel and all connected items and carrying out routine check of OT lights for smooth functioning all as per manufacturer\"s instructions as and when directed incl entire satisfaction of Engr-in-charge complete all as specified and directedNotes : (i) Unserviceable spares which are required to be replaced shall be measured and paid seperately under relevant items of schedule.(ii) Authorized personnel shall repair the unit.(iii) Clean the light housing and arm using mild soap and water mixture. Apply this mixture to a clean cloth and wipe down the light head and arm. (iv) Check front lens and optics to assure there are are no chips,cracks,or other. (v) Check that all mounting and attachment screws washers etc. are in place and securely tightened. Replace any missing screws and re-tighten as required . (vi)Ensure that casters are seated properly on the base assembly. (vii)Check to make sure all moving joints function properly along the mounting system and head & arm system. |
| 49 | OT-I (Two Lights) |
| 50 | OT-II (Two Lights) |
| 51 | OT-III (Two Lights) |
| 52 | OT-IV (Two Lights) |
| 53 | OT-V (Two Lights) |
| 54 | OT-VI (Two Lights) |
| 55 | OT-CTVS (Two Lights) |
| 56 | Gynic OT Labour Room |
| 57 | Minor OT Mortuary OT |
| 58 | Vascular OT |
| 59 | Dismantling the Square arm from ceiling, removing of spring arms and replacement of old rusted base plates, foundation bolts, nuts and make necessary and proper alignment of complete OT light fittings and reinstallation of the complete OT light fitting including accessories complete all as specified and directed |
| 60 | S&F in replacement of Control Board (PCB) of OT light fitting as per existing complete all as specified and directed. |
| 61 | S&F in replacement of Switching mode power supply (SMPS) complete all as specified and directed. |
| 62 | S&F in replacement of Reusable sterile handle complete all as specified and directed. |
| 63 | S&F in replacement of Lower Arm Assembly complete all as specified and directed. |
| 64 | S&F in replacement of LED 50 US FDA Registered round shaped Double Dome OT light with following specifications complete all as specified and directed :-(a) Light Intensity in 1 m distance - 00000-160000 lux (b) Colour Temp- 4500 K (c) Colour Rendition Index (Ra)-95 (d) Colour Rendition Index (R9) - 95 (e) Spot Diameter (mm) - 130-300 mm (adjustable) (f) No of LEDs - 48 (g) Ambient light Intensity 300 lx (h) Service Life of LEDs - Approx 50000 Hrs (j) Temp at Surgeon\"s Head - < 1 degree (Make-KLS Martin / Hospedia or techno-commercially equivalent as approved by GE) |
| 65 | S&F in replacement of sub main wiring with Two single core PVC insulated FRLSH cable with copper conductor multistranded 1100 volts grade 10 sqmm in and including heavy grade PVC casing and capping of suitable size and itsaccessories with fixing arrangements on surface, wall, floor or ceiling etc including 10 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and directed. (Note : One run of earth continuity conductor, one run of PVC casing cappingand two runs of copper conductor together shall be taken as one length for measuring unit length) |
| 66 | All as perserial item No 63.00 above but for 2 x 6 sqmm copper conductor cable with one run of 6 sqmm pvc insulated unsheathed copper earth continuity conductor. (Note : One run of earth continuity conductor, one run of PVC casing cappingand two runs of copper conductor together shall be taken as one length for measuring unit length) |
| 67 | All as perserial item No63.00 above but for 2 x 4 sqmm copper conductor cable with one run of 4 sqmm pvc insulated unsheathed copper earth continuity conductor. (Note : One run of earth continuity conductor, one run of PVC casing cappingand two runs of copper conductor together taken as one length for measuring unit length) |
| 68 | All as perserial item No 63.00 above but for 4 x 6 sqmm copper conductor cable with one run of6 sqmm pvc insulated unsheathed copper earth continuity conductor.(Note : One run of earth continuity conductor, one run of PVC casing cappingand four runs of copper conductor together shall be taken as one length for measuring unit length) |
| 69 | M&L for detecting/attending faults complaints of OT lights as and when directed for rectifiying the defects and make functional OT lights complete all as specified and directed.Notes :- (i) Items required to be replaced shall be measured and paid under respective item of schedule.(ii) Essential material like, insulation tape, screws and all tools required for carrying out the works and instruments to detect the fault shall be deemed to be included in the quoted rate of this item. |