| Sl. No. | Item Description |
| 1 | COMMON ITEMS APPLICABLE FOR JOB \"A\", JOB \"B\" & JOB \"C\" |
| 2 | Excavation in trenches not exc 1.5m wide and not exc 1.5m deep and getting out in soft/loose soil complete all as specified and directed. |
| 3 | Returning, filling in,including spreading, levelling ,watering and well ramming in layers not exc 25cm thickin soft/loose soil complete all as specified and directed. |
| 4 | Removing surplus soil to a distance not exc 50m and depositing where directed at a level not ex 1.5m above the starting pointcomplete all as specified and directed. |
| 5 | M&L for sand cushioning to under ground cable with locally available dry sand for protection of cable 8cm thick before laying of cable and 15 cm thick after laying and stretching the cable below the bricks/PCC cover ,punning of sand using suitable T&P as per site requirementcomplete all as specified and directed. Note- Punned thickness of sand i.e 18 cm shall be considered for measurement purpose. |
| 6 | Supplying and laying un-reinforced precast concrete cable cover class LV, Type 1, flat, size 250x150x40 mm complete all as specified and directed. |
| 7 | Taking out unserviceable cable any type/size from trenches,pole, road,duct etc including necessary joints,U/S fittingsandpipes etc complete all as specified and directed. |
| 8 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armouredheavy duty electric cable 1100V grade with aluminum conductor of cross sectional area10 sqmm 2 core and connecting up incoming/out going cables connection with suitable size lugsandtesting complete all as specified and directed. |
| 9 | All as per item No 8.00 here-in-before but of size 10 sqmm 4 core. |
| 10 | ITEMS APPLICABLE FOR JOB \"A\" |
| 11 | All as per item No-8.00 here-in-beforebut of size 16 sqmm 3 core. |
| 12 | All as per item No-8.00 here-in-beforebut of size 25 sqmm 4 core. |
| 13 | All as per item No-8.00 here-in-beforebut of size 35 sqmm 3.5 core. |
| 14 | All as per item No-8.00 here-in-beforebut of size 50 sqmm 3.5 core. |
| 15 | All as per item No-8.00 here-in-beforebut of size 70 sqmm 3.5 core. |
| 16 | All as per item No-8.00 here-in-beforebut of size 95 sqmm 3.5 core. |
| 17 | All as per item No-8.00 here-in-beforebut of size 120 sqmm 3.5 core. |
| 18 | M&L Plain cement concrete 1:2:4 type B1(using 20mm graded crushed stone aggregate) as in benching,coping including weathering slightly rounded or chamfered angles or as per site requirement with necessary plastering work complete all as specified and directed. |
| 19 | Dismantling of unserviceable/damaged MCB/MCCB of any type/size and removal from site complete all as specified and directed. |
| 20 | S&F in replacementMCCB, 4 poles 415 Volts, 63 Amps, 16 kA, 50 Hz, AC, fixed thermal and fixed magnetic type in theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 21 | S&Fin replacement MCCB, 4 poles 415 Volts, 100 Amps, 16 kA, 50 Hz, AC, fixed thermal and fixed magnetic typein theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 22 | S&Fin replacementMCCB, 4 poles 415 Volts, 125 Amps, 16 kA, 50 Hz, AC, fixed thermal and fixed magnetic typein theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 23 | S&Fin replacementMCCB, 4 poles 415 Volts, 200 Amps, 36 kA, 50 Hz, AC, adjustable type in theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 24 | S&Fin replacementMCCB, 4 poles 415 Volts, 250 Amps, 36 kA, 50 Hz, AC, adjustable type in theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 25 | S&Fin replacementMCCB, 3 poles 415 Volts, 200 Amps, 36 kA, 50 Hz, AC, adjustable type in theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 26 | S&Fin replacementMCCB, 3 poles 415 Volts, 250 Amps, 36 kA, 50 Hz, AC, adjustable type in theexisting LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration inLT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirementand connecting up incoming/out going cables connection with suitable size lugsandtesting completeall as specified & directed. |
| 27 | Dismantling and taking out old existing unserviceable/damaged/burnt change over switch 4 pole of capacity 63 Amp to 200 Amp 50 Hz 415 Volt any make,any capacity complete all as specified & directed. |
| 28 | Supply and Installin replacement onload Changeover switch in existing LT panel 415 Volt in sheet steel enclosure 4 pole of capacity 63 Amp including connecting up incoming/out going cables connectionwith suitable lugs and testing complete all as specified & directed. |
| 29 | Supply and Installin replacement onload Changeover switch in existing LT panel 415 Volt in sheet steel enclosure 4 pole of capacity 100 Amp including connecting up incoming/out going cables connectionwith suitable lugs and testing complete all as specified & directed. |
| 30 | Supply and Installin replacement onload Changeover switch in existing LT panel 415 Volt in sheet steel enclosure 4 pole of capacity 200 Amp including connecting up incoming/out going cables connectionwith suitable lugs and testing complete all as specified & directed. |
| 31 | Disconnecting and taking out old rusted pipe and material and labour for 25 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 25x3mm, with nut bolt and washers complete all as specified & directed. |
| 32 | Disconnecting and taking out old rusted pipe and material and labour for 50 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 50x6mm, with nut bolt and washers complete all as specified & directed. |
| 33 | M&L for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm X 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board,LT panel etc with & including adequate quantity of charcoal dust and common salt around earth plate, PCC 1:3:6 type C-1 using 20mm gradedstone aggregate for earth pit with pre cast RCC (1:2:4)type B-1 using 20mm graded stone aggregate 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh,and 40 mm dia GI light grade earth lead protection pipe, completeall as specified & directed. Note- The unit rate shall includes main earthing leadGI earth strip of size 32x6 mm with 40 mm dia GI light grade earth lead protection pipe from earth electrode to test point up to 7.5 mtr. |
| 34 | S&F GI strip 32 x 6 mm with saddles and fixing screws on poreceline insulator/ spacer fixed at every 1 mtr length as lightening conductor on roof/wall of explosive building/ connect to LT panel or main DBand joining the same with existing earth test point all complete all as specified & directed. |
| 35 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4mpa working pressure complete all as specified & directed. |
| 36 | M&L for straight through joints heat shrink type forXLPE insulated,screened, PVC bedded, galvanized steel strip or wire armouredheavy duty electric cable 1100V grade with aluminum conductor cables of size 6 sqmm to 16 sqmmby excavating earth, identifying the fault, making proper joint of cable,testing of cable after rectification & returning soil back to earth complete all as specified & directed. |
| 37 | M&L for straight through joints heat shrink type forXLPE insulated,screened, PVC bedded, galvanized steel strip or wire armouredheavy duty electric cable 1100V grade with aluminum conductor cables of size 25 sqmm to 50 sqmmby excavating earth, identifying the fault, making proper joint of cable,testing of cable after rectification & returning soil back to earth complete all as specified & directed. |
| 38 | M&L for straight through joints heat shrink type for XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armouredheavy duty electric cable 1100V grade with aluminum conductor cables of size 70 sqmm to 120 sqmmby excavating earth, identifying the fault, making proper joint of cable,testing of cable after rectification & returning soil back to earth complete all as specified & directed. |
| 39 | M&L for scrapping and removing of existing paint,dust,rust by emery paper or other means and preparation of smooth surface for painting and painting with two coat of high qualitysynthetic enamel paintwith approved colouron any size ,any type and any capacity feeder pillar box, LT panelincluding writting of incoming and outgoing location of all cables on LT panels and feeder pillar boxes with high qualitysynthetic enamel paint red colour complete all as specified & directed. |
| 40 | M&L for servicing, cleaning, dusting both side of Indoor/OutdoorLT Panel/ feeder pillar box of any size ,any type any capacity incl carrying out necessary repair to the existing panel/ feeder pillar box , replacing the unserviceable spares parts,tightening cable connections,welding the damage doors, repair/replacement of door handles/locks,hinges,glands,nut ,bolts/lugs of cable/MCCBs of any type any size,any numberreplacing the old rusted frames,and removing vegitation , debris around panel upto 2 m radius also connecting up the all incoming/outgoing cables complete all as specified & directed.Note :- Spares like voltmeter,ammeter,selector switches,indicator lamps, CTs etcshall be measured and paid seperatly under respective item of schedule. |
| 41 | S&F in replacementDigital typeammeter of range 0-600 Amp Accuracy Class 1.0 of LT panel with all connected accessories including connecting up and testingcomplete all as specified & directed. |
| 42 | S&F in replacementDigital type Voltmeter of range 0-500 Volts Accuracy Class 1.0of LT panel with all connected accessories including connecting up and testingcomplete all as specified & directed. |
| 43 | S&F in replacement LED indicator lamp 240 V set of three (R,Y,B) of LT panel with all connected accessories including connecting up and testingcomplete all as specified & directed. |
| 44 | S&F in replacement Curent transformer (CT) 300/5A , accuracy class 1.0, burden 10 VA , resin cast wound type of LT panel including connecting up and testing complete all as specified & directed. |
| 45 | S&F in replacement Curent transformer (CT) 250/5A , accuracy class 1.0, burden 10 VA, resin cast wound type of LT panel including connecting up and testing complete all as specified & directed. |
| 46 | S&F in replacement Curent transformer 100/5A , accuracy class 1.0, burden 5 VA , resin cast wound type of LT panelincluding connecting up and testingcomplete all as specified & directed. |
| 47 | S&F in repairs 3 polePower contactor MNX type AC, 415V, 50Hz 3MNX 95 Contactor2 NO+ 2 NC including taking down unserviceable and connecting up ,testingcomplete all as specified & directed.Make - L&T CS94136 or Techno-commerically equivalent in LEGRAND,C&S,STANDRAD, SCHNEIDER |
| 48 | S&F in repairs 3 polePower contactor MNX type AC, 415V, 50Hz 3MNX 110 Contactor2 NO+ 2 NC including taking down unserviceable and connecting up ,testingcomplete all as specified & directed. Make - L&T CS94137 or Techno-commerically equivalent in LEGRAND,C&S,STANDRAD, SCHNEIDER |
| 49 | Supply, installation,commisioning and testing Weather proof busbar chamber 600x450x300MM made out of 2 MM thick CRCA steel sheet & 40x5 MM angle iron frame suitable for mounting 1 mtr above ground level with locking arrangements incl. Provn of 4 Nos aluminium busbar of 600 Amps rating mounted on insulated frames 2 Nos incl. connecting up incoming & outgoing cables completewith glands,lugs incl.painted with two coats of powder coated paint over a coat of red oxide primer, including necessary PCC 1:3:6 type C1 in foundation for mounting complete all as specified & directed. |
| 50 | M&L for excavation any type soil up to 60 cm depth and 45 cm width to find the fault of LT UG cable any size any place at HQTC area, taking out carefully cable cover, locate the pin point fault of cable,repairing the cable using cable jointing kits and by adding extra LT cable if required at site, testing and relaying the cable cover and returning, filling in,including spreading, levelling ,watering and well ramming including removing surplus soil to a distance not exc 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified & directed.Note- LTjoints/LT cable(if reqd)shall be measured & paid separately under respective item of schedule. |
| 51 | ITEMS APPLICABLE FOR JOB \"B\" |
| 52 | Taking down existing defective/unservicable street light fittings/security light fittings/Flood light fittings of any capacity,any description,any wattage, any type and in any position from poles/pipes/ walls of buildings of any height complete after disconnecting the electrical connection replacement of un-serviceable/damaged/ broken spare parts/ brackets etc, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in same position, connecting to electric supply and its testing on installation complete all as specified and directed. |
| 53 | Taking down existing defective/unservicable post top lanterns/Gate lights /Garden lightsfitting of any capacity,any description,any wattage, any type and in any position fixed at a height not more than 4 mtr from ground level complete after disconnecting the electrical connection replacement of un-serviceable/damaged/ broken spare parts,accessories etc, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in same position, connecting to electric supply and its testing on installation complete all as specified and directed. |
| 54 | Lowering of and lifting of carriage ofhigh mast lights fitting with wire rope motorised or manuallyexisting defective/unservicable high mast lights fittings of any capacity,any description,any wattage, any type,any position and any heightafter disconnecting the electrical connection replacement of un-serviceable/damaged/ broken spare parts/ accessories etc,including servicing of High mast of any height and description , opening the mechanical hoisting / lowering assy , steel wire bobbin , replacing the unservieable meshing gear, easying the steel rope movements, checking the locking mechanism , replacing of oil ,greasing complete and checking for smoothing operation of the mast, re-assembling the high mast lights fittings and making the high mast lights fittings serviceable, fixing the fittings in same position, connecting to electric supply and its testing on installation complete all as specified and directed. |
| 55 | S&F high energy efficent constant currentelectronic driver suitable for LED street light fitting 35 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 56 | S&F high energy efficent constant currentelectronic driver suitable for LED street light fitting 45 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 57 | S&F high energy efficent constant currentelectronic driver suitable for LED street light fitting 90 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 58 | S&F high energy efficent constant currentelectronic driver suitable for LED street light fitting/ Flood light fitting 100 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 59 | S&F high energy efficent constant currentelectronic driver suitable for LED Flood light fitting 30 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 60 | S&F high energy efficent constant currentelectronic driver suitable for LED Flood light fitting 50 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 61 | S&F high energy efficent constant currentelectronic driver suitable for LED Flood light fitting 200 Watts, LEDluminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 62 | S&F opening the LED street light/Flood light fittings ofcapacity 30 watts to 60 watts ,any type and in any position,taking out the LED motherbaord,checking the power LED\"s, replacing the unserviceable motherboard,electronic driver, power LED\"s and soldering or any item as per requirement and making the light fittings serviceable in any way andfixing the fittings in same position including testing,complete all as specified and directed. |
| 63 | S&F opening the LED street light/Flood light fittings ofcapacity 90 watts to 200 watts ,any type and in any position,taking out the LED motherbaord,checking the power LED\"s, replaceing the unserviceable motherboard,electronic driver, power LED\"s and soldering or any item as per requirement and making the light fittings serviceable in any way andfixing the fittings in same position including testing,complete all as specified and directed. |
| 64 | Dismantling thethree phase motor upto 5 HP,440 Volt ,50Hz, ACof High mast lights fittings and taking out to workshop for re-winding,removing the burntout windings, re-winding the same with super enamelled copper wire of existing guage,varnishing and oven drying , and replacing any item as per requirement ,assemblingthe motor including testing, making the motor serviceable in any way andfixing the motor in same position complete all as specified and directed. |
| 65 | Disconnecting and taking out old rusted/ unserviceable light fitting’s bracket incl FI clamps of any description and in any position and supplying and fixing brackets made out of 50 mm dia light grade GI pipe 1.50 mtr long bent to shape and size as per site requirement for fixing ofstreet light fitting on poles/ walls including Flat Iron clamps=02 Nos of size 30x5mm made to shape incl nuts,bolts & washers complete all as specified and directed. |
| 66 | Disconnecting and taking out old rusted pipe and material and labour for 40 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 30x5mm, with nut bolt and washers complete all as specified & directed. |
| 67 | Disconnecting and taking out old existing unserviceable PVC cable loop box andsupplying and fixing with pole PVC cable loop box, size not less than 145 mm x 145 mm x 95 mm, out door type, IP 65includingporcelain insulated connectors for incoming and outgoing 4 core cables with oneMCB SP 6 amps 230 volts connected to street light fitting sub main wire and usingFI clampsof size 20mm x3 mm for fixing of PVC cable loop boxwith pole,including nuts,bolts & washers and connecting thecables to connectors withusing suitable size GI nut, bolts and washers and aluminum lugs etc andcomplete all as specified & directed. |
| 68 | M&L forsub main wiring from street light fitting to junction box with two single core PVC insulated cable with copper conductor multistranded 1100 volts grade 1.5 sqmm in and including heavy grade PVC conduitand itsaccessories with fixing arrangements on pole surface, wall, ceiling etc including 1.5 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and directed.Note : One run of earth continuity conductor,one run of PVC conduitand two runs of copper conductor together shall be taken as one length for measuring unit length. |
| 69 | S&F in repairs single core PVC insulated FR cable with multistranded copper conductor of size 2.5 sq.mm cross sectional area, 1100 Volts grade, complete all as specified and directed. |
| 70 | S&F MCBSP, 6-32A, 240V,50Hz ,10kA, \"B\" type, for street lightfittings complete all as specified and directed. |
| 71 | S&F MCBSPN 32A, 240V,50Hz ,10kA, \"B\" type,suitable for existing timer control board complete all as specified and directed. |
| 72 | S&F MCBTPN,63A, 415V,50Hz ,10kA, \"B\" type,suitable for existing timer control board complete all as specified and directed. |
| 73 | S&FMCCB, 4 poles 415 Volts, 63 Amps, 16 kA, 50 Hz, AC, fixed thermal and fixed magnetic type including connecting up incoming/out going cables connection with suitable lugs and testing completeall as specified & directed. |
| 74 | S&F in repairs, 3 pole Power Contactors 415 volt 50 HzML3 type 40 Amps AC3 rating with 2 NO +2NC Aux contacts,includingtaking out old existing unserviceable completeall as specified & directed.Make : L&T Cat No. SS 90721 or or Techno-commerically equivalent in LEGRAND,C&S,STANDRAD, SCHNEIDER |
| 75 | S&F in repairs Digital Multi function time switch with programmable fuction with battery backup and current carring capacity 16 Amps with 1 changeover including takingout the unserviceable time switch, completeall as specified & directed.Make L&T 67DDT0 or or Techno-commerically equivalent in LEGRAND,C&S,STANDRAD, SCHNEIDER |
| 76 | S&F in repairs LED flood light fitting 30 watts,240 Volt, single phase, AC, outdoor type,aluminium pressure die-cast housing with IP66 protection with 4 Kv in-built surge protectioncomplete with driver,motherboard and LED including taking down unserviceable fitting, connecting and testing completeall as specified & directed.Make Bajaj BJFL 30W LED or Techno-commerically equivalent in Havells/Philips/Wipro. |
| 77 | S&F in repairs LED flood light fitting 50 watts,240 Volt, single phase, AC, outdoor type,aluminium pressure die-cast housing with IP66 protection with 4 Kv in-built surge protectioncomplete with driver,motherboard and LED including taking down unserviceable fitting, connecting and testing completeall as specified & directed. Make Bajaj BJFL 50W LED or Techno-commerically equivalent in Havells/Philips/Wipro. |
| 78 | S&F in repairs LED flood light fitting 100 watts,240 Volt, single phase, AC, outdoor type, with pressure die-cast housing, toughened glass with IP66 protection with 4 Kv in-built and 10 Kv external surge protectioncomplete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing completeall as specified & directed. Make Bajaj PRAZE F 120L WH NB-A5 TG SDor Techno-commerically equivalentin Havells/Philips/Wipro. |
| 79 | S&F in repairs LED flood light fitting 200 watts,240 Volt, single phase, AC, outdoor type, withsuperior polycarbonate optics pressure die-cast housing, with IP66 protection with 4 Kv in-built and 10 Kv external surge protectioncomplete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing completeall as specified & directed.Make Bajaj GLEAM F 220L WH SY PC SD V2 or Techno-commerically equivalent in Havells/Philips/Wipro. |
| 80 | S&F in repairs LED street light fitting 45 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing with IP66 protection,high performance polycarbonate optics, 4 Kv in-built surge protection with top opening driver cover complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing completeall as specified & directed.Make Bajaj ENXT P 54L WH PO PC SD MTor Techno-commerically equivalent in Havells/Philips/Wipro. |
| 81 | S&F in repairs LED street light fitting 90 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing, toughened glass with IP66 protectionwith 4 Kv in-built and 10 Kv external surge protectioncomplete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing completeall as specified & directed. Make Bajaj ZELA P 108 L WH PO TG SDor Techno-commerically equivalentin Havells/Philips/Wipro. |
| 82 | S&F in repairs LED street light fitting 100 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing, toughened glass with IP66 protectionwith 4 Kv in-built and 10 Kv external surge protectioncomplete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing completeall as specified & directed. Make Bajaj ZELA P 120 L WH PO TG SDor Techno-commerically equivalentin Havells/Philips/Wipro. |
| 83 | S&F in repairs LED post-top light fitting 25 watts made in die-cast aluminium bottom housing and spun aluminium top reflector with decorative clear acrylic diffuser and IP 65 protection with 25 watt LED bulb including taking down unserviceable fitting, completeall as specified & directed. Make Bajaj BGCTN 25 W LED WH or Techno-commerically equivalent make of Havells,CG. |
| 84 | S&F in repairs of LED Bulbs 23 Watts, BEE star rated energy efficient Retrofit bulb, including taking down unserviceable lamp, completeall as specified & directed. |
| 85 | S&F in repairs LED Bulbs 10 Watts, BEE star rated energy efficient Retrofit bulb, including taking down unserviceable lamp, completeall as specified & directed. |
| 86 | Material & Labour for plain cement concrete1:4:8 type D-2( using 40mm graded crushed stone aggregate) as in foundation,filling and mass concrete in foundation of poles and stay assembly for bed concrete or as per site requirementcomplete all as specified and directed. |
| 87 | ITEMS APPLICABLE FOR JOB \"C\" |
| 88 | S&F in repair galvanised water tubes, 100 mm dia light grade including all fittings as per site requirement complete laid in trenches including taking down old unserviceable rusted pipecomplete of following sizes all as specified and as directed. |
| 89 | All as per item No 85.00 here-in-before but 80mm dia |
| 90 | All as per item No85.00 here-in-before but 50mm dia |
| 91 | All as per item No85.00 here-in-before but 40mm dia |
| 92 | All as per item No85.00 here-in-before but 25mm dia |
| 93 | All as per item No85.00 here-in-before but 20mm dia |
| 94 | All as per item No85.00 here-in-before but 15mm dia |
| 95 | S&F in repair Gun-metal, globeor gate valves, 100 mm diaheavy duty, with iron wheel head, screwed both ends (ISI marked)of following size including all fittings nuts, bolt& washers etc includingtaking down old complete all as specified & directed. |
| 96 | All as per item No 92.00 here-in-before but 80 mm dia |
| 97 | All as per item No92.00 here-in-before 50 mm dia |
| 98 | All as per item No92.00 here-in-before 40 mm dia |
| 99 | All as per item No92.00 here-in-before 25 mm dia. |
| 100 | All as per item No92.00 here-in-before 20 mm dia. |
| 101 | All as per item No92.00 here-in-before 15 mm dia |
| 102 | S&F CI fittings, heavy duty, such as bends, tapers, tees,collars,tail pieces, reducers, etc laid and jointed with suitable push on joints complete upto 150 mm dia all as directed and specified. |
| 103 | S&F CI fittings, heavy duty, such as bends, tapers, tees,collars,tail pieces, reducers, etc laid and jointed with suitable push on joints complete upto 200 to 300 mm dia all as directed and specified. |
| 104 | S&F CI sluice valve of pressure Class PN - 1.6 flanged, 200 mm dia and drilled at both ends with ISI mark, having steel spindle and gunmetal rings including wheel for operation all as specifedand all jointing materials, bolts, nuts, washers, and necessary civil works such as Demoltion,Excavation, Removing and returning filling etc, all as specifed and as directed including dismantling and taking up unserviceable of the following sizes complete:- |
| 105 | All as per item No.101.00 here-in-before but 150 mm bore |
| 106 | All as per item No.101.00 here-in-before but 100 mm bore |
| 107 | All as per item No.101.00 here-in-before but 80 mm bore |
| 108 | S&F Run lead joints for CI spigot and socket pipes 200 mm dia complete all as specified and as directed. |
| 109 | All as per item No 105.00 here-in-before but 150 mm dia |
| 110 | All as per item No 105.00 here-in-before but 100 mm dia |
| 111 | All as per item No 105.00 here-in-before but 80mm dia |
| 112 | S&F in repairs Non return valve, heavy duty, ISI Marked, PN –1.0, both end flanged, suitable to fix with 150mm dia pipe lineincluding nuts, bolts,washer,fittings,as per site requirement items taking down existing unserviceable non return valve complete all as specified and as directed. |
| 113 | Supply and laying of CPVC pipe SDR 11 of size 25mm outer dia with all fittings on walls /ceiling/floors complete all as specified and directed. |
| 114 | Supply and laying of CPVC pipe SDR 11 of size 32mm outer dia with all fittings on walls /ceiling/floors complete all as specified and directed. |
| 115 | Supply and laying of CPVC pipe SDR 11 of size 40mm outer dia with all fittings on walls /ceiling/floors complete all as specified and directed. |
| 116 | Supply and laying of CPVC pipe SDR 11 of size 50mm outer dia with all fittings on walls /ceiling/floors complete all as specified and directed. |
| 117 | S&F in repair bib tap strandard of PTMT any colour high pressure screwed for iron pipe of size 15mm dia minimum weight 90 grams complete all as specified and directed. |
| 118 | S&F in repair bib tap strandard of PTMT any colour high pressure screwed for iron pipe of size 20mm dia minimum weight 125 grams complete all as specified and directed. |
| 119 | M&L cement concrete type B- 1, 1:2:4 using 20mm grade aggregatein mass concrete complete all as specified and directed complete all as specified and directed. |
| 120 | M&L for preventive maintenance of 60 HP motor pump sets by cleaning stator, rotor and servicing of pumpsets by replacing old gland packing, greasing in bearings etc and preparation of old painted surface and applying one coat of painting,complete including dismantling/separating of motor from pump and rexing the same after servicing complete all as specified and as directed. |
| 121 | All as per item No.117 above but 20/12.5 HP pump set complete all as directed and specified. |
| 122 | All as per item No 117.00 here-in-before but 10 HP pump set complete all as directed and specified. |
| 123 | All as per item No.117.00 here-in-beforebut 7.5/5 HP pump set complete all as directed and specified. |
| 124 | All as per item No.117.00 here-in-beforebut 3 HP pump set complete all as directed and specified. |
| 125 | M&L for taking out old burnt winding of centrifugal motor rewinding with approved quality super enamel insulated copper winding wire, replacing old insulating materials for 60 HP motor and reassembling the motor,testing and commissioning and inclusive of any transport form worksite to work shop and bring back all as directed. |
| 126 | All as per item No.122.00 here-in-before but 20 HP complete all as directed and specified. |
| 127 | All as per item No.122.00 here-in-beforebut 12.5 HP complete all as directed and specified. |
| 128 | All as per item No.122.00 here-in-before but 10 HP complete all as directed and specified. |
| 129 | All as per item No.122.00 here-in-beforebut 7.5 /5 HP complete all as directed and specified. |
| 130 | All as per item No.122.00 here-in-beforebut 3 HP complete all as directed and specified. |
| 131 | All as per item No 122.00 here-in-before but 1.0 /0.5 HP single phase complete all as directed and specified. |
| 132 | S&F in repairs Foot valve, in UG sump 150mm bore, CI body and hard rubber gasketcomplete all as specified and as directed. |
| 133 | S&F in repairs Foot valve, in UG sump 100mm bore, CI body and hard rubber gasketall as specified and as directed. |
| 134 | S&F in repairs Foot valve, in UG sump 80mm bore, CI bodyand hard rubber gasketall as specified and as directed. |
| 135 | Labour and machinery for lifting defective /unserviceable submersible pumpfrom bore well vertical type multi stage, capacity 2 HP to 10 HP for repair / replacement of unserviceable parts such as bowls, Diffursers, impellors, stainless strainer, NDE/DEbearing, rotor fitted shaft, thrust washers , elastic rings , diaghragm , pump shaft coupling etc. and re assembling the same after replacing any unserviceable spares as specified and necessary transport to workshop and bringing back, complete and installing & testing at the same location all as specified and as directed.Note : All the spare parts includingand rewinding shall be measured and paid separately. |
| 136 | M&L for taking out old burnt winding of submersible motor rewinding with approved quality super enamel insulated copper winding wire, replacing old insulating materials for 10 HP submersible motor and reassembling the motor,testing and commissioning and inclusive of any transport form worksite to work shop and bring back all as directed. |
| 137 | All as per item No 133.0 here-in-before but motor 7.5 HPall as directed. |
| 138 | All as per item No 133.0 here-in-beforebut motor 5 HPall as directed. |
| 139 | All as per item No 133.0 here-in-before but motor 3 HPall as directed. |
| 140 | All asper item 133.0 here-in-before but 2 HP all as directed. |
| 141 | M&L for supply, install testing and commissioning of DOL starter for the motors of capacity of 5 HP including dismantling existing old motor starter from its location by removing all cable connections complete all as specified and as directed. |
| 142 | M&L for supply, installation, testing and commissioning of DOL starter for the motors of capacity of3/2 HP including dismantling existing old motor starter from its location by removing all cable connections complete all as specified and as directed. |
| 143 | M&L for supply, installation, testing and commissioning of fully automatic star/Delta starter in sheet steel enclosure suitablefor 60 HP,3 phase, 415 volts, 50HZ, AC complete including dismantling existing oldstarter form its position complete all as directed & specified. |
| 144 | All as per item No.140.00 here-in-before but20 HP all as directed. |
| 145 | All as per item No.140.00 here-in-before but12.5/10 HP all as directed. |
| 146 | All as per item No.140.00 here-in-before but up to 7.5 HP all as directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail