| 1 | Maintenance and servicing to DG set including attending faults on call basis for normal repairs including replacement of defective and worn out minor filters gaskets, V- belts, Engine oil, rubber hoses, worm drive clamps, nuts, bolts and cleaning of alternator with vaccum cleaner and attending faults of AMF panels etc, tappet settings if required and greasing of bearings of engine and alternator, checking of batteries, applying petroleum jelly to battery tereminals, adding distilled water checking the oil, coolent levels of capacity 110 KVA DG set complete all as specified and as directed by Engr- in- Charge. |
| 2 | Description all as per item No 1 here-in-before but capacity 40 KVA to 63 KVA DG set. |
| 3 | Description all as per item No 1 here-in-before but capacity 30 KVA DG set. |
| 4 | Note for item No 1,2 & 3:- (i)Spares required for maintenance will be measured and paid seprately under relevant items. (ii) Servicing to be carried out as per manufacturer’s specifications/ instructions. (iii) The work of maintenance shalll be carried out through respective authorized dealer whose certificate shall be produced to Engineer - in - charge. (iv) Work shall be carried out at site at different location. |
| 5 | Supply only Diesel filter element with \"O\" ring suitable for 110 KVA DG set, compete all as specified and as directed. |
| 6 | Supply only Diesel filter element with \"O\" ring suitable for 40 KVA to 63 KVA DG set, compete all as specified and as directed. |
| 7 | Supply only Diesel filter element with \"O\" ring suitable for 30 KVA DG set, compete all as specified and as directed. |
| 8 | Supply only Spin- on filter element with by pass filter element for luricanting oil with \"O\" ring suitable for 110 KVA DG set, compete all as specified and as directed. |
| 9 | Supply only Spin- on filter element with by pass filter element for luricanting oil with \"O\" ring suitable for capacity 40/63 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 10 | Supply only Spin- on filter element with by pass filter element for luricanting oil with \"O\" ring suitable for capacity 30 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 11 | Supply only air filter element suitable for 110 KVA DG set, compete all as specified and as directed. |
| 12 | Supply only air filter elementsuitable for capacity 40/63 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 13 | Supply only air filter element suitable for capacity 30 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 14 | Supply only Fan Belt set complete suitable for 110 KVA DG set, compete all as specified and as directed. |
| 15 | Supply only Fan Belt set complete suitable for capacity 40/63 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 16 | Supply only Fan Belt complete suitable for capacity 30 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 17 | Supply onlyBelt for battery charging alternator complete suitable for 110 KVA DG set, compete all as specified and as directed. |
| 18 | Supply onlyBelt for battery charging alternator complete suitable for 40 KVA/ 63 KVA DG set, compete all as specified and as directed. |
| 19 | Supply onlyBelt for battery charging alternator complete suitable for capacity 30 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 20 | Supply onlyRubber Hose pipe set for water circuit with clamps complete suitable for capacity 30 to 110 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 21 | Supply onlyRubber Hose pipe set for water circuit with clamps complete suitable for capacity 30 KVA DG set, compete all as specified and as directed by Engr-in charge. |
| 22 | M & L forelectronic speed control unitassembly 12 volts suitable for 30 KVA DG set to 110 KVA DG set including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 23 | S & F for Engine oil, multi grade premium Genuine oil 20W/ 40W till as per manufacturer recommendations in DG sets complete all as specified and as directed. |
| 24 | Supply and filling Petrolium Jelly (01 Kg plastic sealed container), complete all as specified and as directed. |
| 25 | Supply and filling distilled water for topping up in lead acid batteries, complete all as specified and as directed. |
| 26 | Supply and filling electrolyte of suitable specific gravity for lead acid batteries in sealed container, complete all as specified and as directed. |
| 27 | Supply and filling genuine coolant in 5 ltrs plastic sealed container for topping up in Radiator of DG set located at different locations as directed by Engr-in-Charge, complete all as specified and as directed. |
| 28 | S & F for Battery leads of PVC insulated, multistranded, copper conductor of size 70 Sqmm of 1.25 mtr long each duly fixed with brass clamps, copper lugs suitable for DG set batteries installed at different locations complete including removal of esixting unserviceable one complete all as specified and as directed. |
| 29 | S&F forbattery teriminal brass clamps including removal of existing unserviceable one compete all as specified and as directed by Engr-in charge. |
| 30 | M & L for dismantaling the radiator from DG Set of capacity 30 KVA to 110 KVA taking to work shop for overhauling & cleaning, de-scaling with acid, removal of leakage including soldering and welding, brazing as required and renewal of gaskets, nuts, bolts, mounting pads,hoses,clips, etc and refixing its original position of DG set complete all as specified and directed. |
| 31 | M & L forcanopy hinges with locking arrangements for auqastic doors with suitable bolts and nuts of DG set including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 32 | M & Lfordisconnecting all electrical connections from DG set alternator of any capacity from base plate by openingnuts & bolts keeping aside the alternator forinspection and taking out the same to work shop for rewinding includingtesting & commissioning, completeall as specified& directed. |
| 33 | M& L for Rewinding of alternator field coilwith super enamelled copper winding wire of class \"F\" insullation as per existing size and gauge including heating, varnishing and testing of of capacity 30 KVA DG set to 110 KVA DG set, complete all as specified and as directed. |
| 34 | M & L for water temperature guage including sensor and cable suitable foe 30 KVA to 110 KVA DG set complete as per sampleincluding removal of existing unserviceable one, complete all as specified and as directed. |
| 35 | M & L for repair and calibration of FIP and injectors from authorised dealer for petty repairs to make the FIP functional as per standard calibration procedure and norms including replacement of minor spares, gasket etcfor smooth functioning of FIP and refixing its original position includingtesting at site for following capacities of DG set complete all as specified and as directed.Note :- Calibration and repairs has been carried out by the authorised dealer. |
| 36 | (a) 30 KVA DG set to 63 KVA DG set |
| 37 | (b) 110 KVA DG set |
| 38 | M & L for Repair/ overhauling of self starting system of DG set including replacement of corbon brushes, bearings, bushes, rewinding of armature and field coil etc and varnishing of capacity 12/24 volts with necessary connectionsincluing testing and commissioing, complete all as specified and as directed. |
| 39 | M & L for repairing ofbattery charging alternator engine mounted with replacement of any of the unserviceable part such as rectifier with voltage regulator, diode plate, corbon brushes of capacity 12 volts including testing and commissioing, complete all as specified and as directed. |
| 40 | M & L forAVR (automatic voltage regulator)control unitassembly suitable for 30 KVA DG set to 63 KVA DG set including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 41 | M & L forAVR (automatic voltage regulator)control unitassembly suitable for 110 KVA DG set including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 42 | M & L for fuel steel braided pipe with benjo bolts and washers etc of length 45 cm long including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 43 | M & L forAnti vibration pads with suitable bolts and washers including removal of existing unserviceable one,compete all as specified and as directed by Engr-in charge. |
| 44 | Supply only for LED indicator lamps R, Y, B with holder 15 mm screw type including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 45 | S & F for time dealy relay suitable for 30 KVA DG set to 63 KVA DG set including removal of existing unserviceable one, compete all as specified and as directed. |
| 46 | S & F for time dealy relay suitable for110 KVA DG set including removal of existing unserviceable one compete all as specified and as directed. |
| 47 | M & L forsolinoid switch assembly 12 volts suitable for 30 KVA DG set to 110 KVA DG set including removal of existing unserviceable one compete all as specified and as directed by Engr-in charge. |
| 48 | M & L forSMPS (system main power supply) type control unitassembly suitable for 12 volts battery charger forincluding removal of existing unserviceable one, compete all as specified and directed. |
| 49 | M & L for DC alternator assembly 12 volts suitable for 30 KVA DG set to 110 KVA DG set including removal of existing unserviceable one, compete all as specified and as directed by Engr-in charge. |
| 50 | Taking outthe unserviceable & perished panel board fabrication of new doors/ body from the panel board fabrication of new/ replace with same size made out of CRCA sheet of 3.15/ 2.0 mm thick duly fabricated welded and including replacement ofproper locking arrangement and hinges and painted with spray painting match with existing colour over coat of red oxide, complete all as specified and directed. |
| 51 | M&L for fabrication/ welding/ Jointing work in existing LT Panel door by providing 02 Nos new hinges in place of defective hinges, replacement of locking arrangement of external door, replacement of main door gasket, completeall as specified and directed by Engr-in-charge. |
| 52 | S & F in replacement of old unserviceable/ damaged battery with new storage cell lead acid type 12 Volts, 180 AH including lead terminals and copper thimble, copper nuts, bolts for making necessary connections, complete all as specified and as directed by Engineer-In-Charge. |
| 53 | S & F in replacement of old unserviceable/ damaged battery with new storage cell lead acid type 12 Volts, 150 AH including lead terminals and copper thimble, copper nuts, bolts for making necessary connections, complete all as specified and as directed by Engineer-In-Charge. |
| 54 | S & F in replacement of old unserviceable/ damaged battery with new storage cell lead acid type 12 Volts, 90 AH including lead terminals and copper thimble, copper nuts, bolts for making necessary connections, complete all as specified and as directed by Engineer-In-Charge. |
| 55 | S & F connecting and testing MCCB inexisting DG set Panel of the following capacity, suitable for 415 volts, 50 Hz, with extended terminals type, inter locked to prevent opening when the Switch is in ON Position, connecting and testing complete including removal of exiting unserviceable all as specified and directed. |
| 56 | (a)MCCB4 pole 63 Amps with thermal magnetic release breaking capacity 16 KA, Ics=100% Icu |
| 57 | (b) MCCB 4 pole 100 Amps with thermal magnetic release breaking capacity 16 KA, Ics=100% Icu |
| 58 | (c) MCCB 4 pole 125 Amps with thermal magnetic release breaking capacity 16 KA, Ics=100% Icu |
| 59 | (d) MCCB 4 pole 200 Amps with thermal magnetic release breaking capacity 16 KA, Ics=100% Icu |
| 60 | S & F for microprocessor based multifunction relay suitable for DG sets operation of any capacity and showing the various parameters such as volt, ampere, frequency, RPM etc complete as per site requirment including removal of existing unserviceable one complete all specified and as directed. |
| 61 | S & F inreplacement of old unserviceable/ damaged Change over switch with new Change over switch, four poles, 415 Volts, AC, 50 Hz, with side handle, conforms to IS:13947 (Part-3); IEC:60947-2,including removal of exiting unserviceable complete all as specified and as directed by Engineer-In-Charge. |
| 62 | (a)Change over switch 4 pole 63 Amps |
| 63 | (b)Change over switch4 pole 100 Amps |
| 64 | (c)Change over switch 4 pole 125 Amps |
| 65 | (d)Change over switch 4 pole 200 Amps |
| 66 | M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strep 32 x 6 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earth work GI pipe 20mm dia light grade for wateringPCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to panel board as indicated including testing complete, including taking down of existing earthing, complete all as specified and as directed. |
| 67 | Design, supply, installation, testing and commissioning ofCubical type floor mounted LT panel, of minimumsuitable sizeoutdoor typefactory fabricatedmade out of CRCA sheet of 3.15 mm thick ,fully enclosedand angle iron frame of size 40 x 40 x 6mm thick and T section with front openabledouble door shutter, dust and vermin proofand rear openingcomplete with locking arrangement, having a system of bus barsof aluminiumof suitable size of 200 Amps duly insulated and mounted on Epoxy/porcelain insulators in totally enclosed chamber with three phase and neutral 415volts, AC, system prewired with suitable copper wire PVC insulated with all control accessories, provn of suitable cable glands, duly powder coated of approved quality over a coat of red primer with sufficient free space including taking down existing LT panel, complete to include the following accessories:- (a) MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity 16 KA-01 No(b) MCCB 3 Pole, 415 V, fixed type, 63 Amps with breaking capacity 16 KA-03 Nos (c) Digital 125 Amps volt meter 0 to 500 volts with selector switch-1 No (d) Digital Ammeter 0 to 350 Ampswith CTs of suitable Amps and selector switch-1 No (f) Indicator lampRYB- 01 Set |
| 68 | Excavation in trenches in soft/loose soil not exceeding 1.5 m wide and not exc. 1.5 mtr deep for laying of cables and getting out soft/loose soil, complete all as specified and directed by Engr in Charge. |
| 69 | M & L filling dry and clean sand in trenches for cable 8 cm deep below and 15 cm above for cable cushioning, complete all as specified and directed by Engr in Charge. |
| 70 | M & L for sub class \"B\" brick of size 230x115x75mm laid flat work length equal to width of brick on sand for protection of under ground cable, complete all as specified and directed by Engr in Charge. |
| 71 | Returning filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick in trenches, complete all as specified and directed by Engr in Charge. |
| 72 | Removal of surplus soil obtained from excavation to a distance not exceeding 50 mtr and depositing where directed ata level not exceeding 1.5 mtr above the starting point, complete all as specified and directed by Engr in Charge. |
| 73 | Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 185.0 Sqmm, 3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge. |
| 74 | Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 120.0 Sqmm, 3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge. |
| 75 | Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 95.0 Sqmm, 3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge. |
| 76 | Replacement of old unserviceable rubber mat with new synthetic rubber insulating mat for preventing LT shock, thickness not less than 20mm, size 2.00x1.00 m, complete all as specified and as directed by Engineer-In-Charge. |