| 1 | Construction of Tube Well from ground level and upto 100 mtr. depth and above to accommodate housing and assembly pipe in all type of alluvium strata, unconsolidated formation such as pebbles, boulders etc. by percussion/ rotary drilling method as per IS:2800 (part 1 & 2) 1979 as amended up to date. The work will include cost of lowering of housing, strainer assembly pipes, with supply and wrapping of coir rope, wherever necessary and development of tube well as per IS specification using suitable Air Compressor but will not include cost of casing & strainer pipe. Work will be completed after obtaining sand free water. Nominal bore 250 mm dia. |
| 2 | Add 15% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 100 mtr and upto 200 mtr, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr. |
| 3 | Add 40% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 200 mtr, rate shall be applicable for only extra depth beyond 200 mtr . |
| 4 | Construction of tube well after completion of drilling by rotary or percussion method and up to 100 mtr depth in all type of rocks by DTH system as per IS 2800 Part 1and 1991 and IS 2800 Part IIand 1979 both amended up to date and technical specifications The work shall be deemed completed only after obtaining sand free water The bore well should have a throughout nominal size bore beyond casing pipe Nominal bore 200 mm dia |
| 5 | Testing verticality of tube well by plumbing system and yield test and draw down test by pumping system as per IS : 2800 (Part – II) – 1979 as amended up to date. |
| 6 | Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to date of grade Fe 410 of following sizes 250 mm dia NB (Thicknee of pipe 7.1 mm & mass of tube 46.57 Kg/m) |
| 7 | Labour charges for making slots on blank pipes made of ERW MS black pipe ISI marked of following sizes, the slotting should be as per IS:8110-1985. 250 mm dia nominal bore of 7.1mm thickness |
| 8 | Supply & Installation of 3 phase ISI marked submersible motor pump set of five star rating by BEE and as per IS: 8034-2011 (pump) and IS 9283-2013 (motor) or amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. 15 KW (20 HP) and above, head above 120 mtr. |
| 9 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay, ampere meter with CTs, volt meter, phase preventor, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 guage M.S. Sheet with powder coating. Panel should be of minimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system. The legs should be embedded in M-15 cement concrete plat form.The size of CC plateform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. Above 15 HP |
| 10 | Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. 3 core 10.00 mm2 |
| 11 | Supply & Fixing XLPE Indulate/ PVC sheathedcable of 1.1KV gradewith aluminium conductor armourd of IS 7098 Part-I approved make ingroud as per IS:1255 including excavation of 30 cm x 75cm size trench, 25cm thick under layer of sand, second class bricks covering, refilling earth, compaction of earth, making nacessary connection, testing etc. as required of size electric cable with for working voltage to Is:/IS :1554 Part-I applicable. 3.5 core 35.0 mm2 |
| 12 | Supply & Fixing tube well cover of MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both end in 80mm sizes passing through a hole in the centre of MS sheet. A 25mm socket with end plug shall also be welded over top plate (as per drawing enclosed). A GI nipple having outside thread of size 1/2\" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug. 250 mm dia |
| 13 | Providing & Lowering in tubewell ISI marked GI Pipe “B\" class as per IS:1239 or amended up to date threaded and double flanged (welded) on both ends and two number 25x3mm flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. 65 mm dia |
| 14 | Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes 65 mm dia |
| 15 | Supply & Fixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc for holding the riser pipe assembly of submersible pump set. |
| 16 | Plate Earthing as per IS3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. (B) class watering Pipe including all accessories like nut bolts reducer nipple wire meshed funnel and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 17 | Provision for new power connection (TENTIVE) |
| 18 | LumpSum Please Enable Macros to View BoQ information |