| 1 | Supply, installation, commissioning and testing of LT Panel outdoor type double door , Kiosktype, CPRI approved,LT(415 Volts, 50 Hz , 3-phase, 4 wire supply) floor mounted, factory assembled, double door weather and vermin proof made out of 3.15 mm thick CRCA sheet, double door type openable from front and rear side, rubber lining, locking arrangement, painted externally and internally with powder coated paint (first quality) complete mounted on MS channel of min size 75x40 mm with PCC work and including under mention items in independent compartment with sufficient working space complete all as specified anddirected by Engineer-in-Charge :- |
| 2 | (A) INCOMING :(a) ACB 800 Amps ,4 pole, ultimate breaking capacity 100 KA 415 Volts – 01 No (b) Bus barAluminium of 1200 Amp capacity on epoxy insulators-01 Set (04Nos)(B) OUTGOING :(a) MCCB 200 Amps , 4 pole,breaking capacity 25 KA, 415 Volts – 02 Nos(b) MCCB 100 Amps 4 Pole, 25 KA, 415 V-03 Nos.(c) Suitable size of Timer analog type for street light with power contractor complete (d) Multi function meter for measuring Volt, Amp, Frequency, Kw, KVA includingCTs of suitable capacity (e) Indicator lamps RYB LED type (Set of Three) -01 No (f) Wiring of above accessory with suitable size of copper conductor cable Note :-(i) All MCCBs / instruments / MCBs / Bus Bar shall be housed in a separate housing with on- off latches in the housing. (ii) Space for provn of one extra MCCB should be provided in the panel. |
| 3 | Supply, installation, commissioning and testing of LT Panel outdoor type double door , Kiosktype,CPRI approved,LT(415 Volts, 50 Hz , 3-phase, 4 wire supply) floor mounted, factory assembled, double door weather and vermin proof made out of 3.15 mm thick CRCA sheet, double door type openable from front and rear side, rubber lining, locking arrangement, painted externally and internally with powder coated paint (first quality) complete mounted on MS channel of min size 75x40 mm with PCC work and including under mention items in independent compartment with sufficient working space complete all as specified anddirected by Engineer-in-Charge :- |
| 4 | (A) INCOMING :(a) MCCB 160 Amps ,4 pole, ultimate breaking capacity 25 KA 415 Volts – 01 No (b) Bus barAluminium of 240 Amp cap on epoxy insulators-01 Set (04Nos)(B) OUTGOING :(a) MCCB 40 Amps , 4 pole,breaking capacity 25 KA,415 Volts – 04 Nos (b) MCB 32 Amps TPN,10 KA, 415 V-02 Nos. (c) Suitable size of Timer analog type for street light with power contractor complete (d) Multi function meter for measuring Volt, Amp, Frequency, Kw, KVA includingCTs of suitable capacity (e) Indicator lamps RYB LED type(Set of Three)-01 No (f) Wiring of above accessory with suitable size of copper conductor cable Note :-(i) All MCCBs / instruments / MCBs / Bus Bar shall be housed in a separate housing with on- off latches in the housing. (ii) Space for provn of one extra MCCB should be provided in the panel. |
| 5 | Supply & Fix bus bar chamber havng IP -42 protection as per IS spections, fabicated out of CRCA sheet 3.15 mm thicksheet of size750x 400 x 200 mm ,with provision ofTPN, 415 Voltwith 200 Amp rated Aluminum busbar capcity (RYB) ,Busbar length shall be 400 mm long,mounted on PVC/ Epoxy insulator,factory made sheet metal enclosure for distribution board ,including provn with backalite sheet of size 600x300x 3 mm thick ,The Bus bar Chamber shall be front door type with 2 Nos locking arrangement, semi glossy finish with powder coated sprayed paint and baked at high temprature, incl making necessaryconnection with busbarto MCCB, inclulding grouting on ground and making good the surface complete all as specified and comprises of following :- (a) MCCB ,63 AMP,4 Pole,25 KA 415 Volts 63%-100% Adjustable, 50 HZ -1NoNote:- MCCB shall be fixed on adjustable mounting so as to accomodate operating knob projected out side the front door |
| 6 | Automatic power factor control panels fabricated out of 3.15mm thick CRCA steel sheet and other suitable size steel sections (angle iron \"T\" section, channels etc) in cubicalcompartments, free standing, floor mounted, dust and vermin proof complete all as specified and directed. Cable glands shall be provided on top as well as at the bottom of the panels. Panels shall be treated with anticorrosive process before powder coating of approved shade as per specifications. Panels shall be double door hinged type & in-built locking arrangment earthig terminals shall be provided for all distribution panels. Panels shall be suitbale for 440V, 3 phase, 4 wire and 50Hz supply system. Lifting hooks shall be provided. Approval from the Accepting Officer for the design & specificationis fo the Panel & its components shall taken by the contractor before procurement. The automatic control panel shall be of capacity as mentioned under and shall be provided duly housed/mounted with the following omponents/accessories/fittings complete in all respects as directed:- |
| 7 | (a) 250 KVAR capacitor automatic control panel with the follwing steppings:-(i)Considering 15% space for future expansion.(ii)Steps shall be 100+50+50+20+10+10+5+5(b) BR-6000 Relay of 8 steps shall be used so that in future 2 steps can be used:01 Job.(c)MCCB, FP, 400 Amp, 36KA with microprocessor based release relay: 01 No(d)96x96sqmm 0-500 digital voltmeter with selector switch-01 Set.(e)Phase indicating light protection by 2 Amps SP MCB\"s - 8 Sets.(f)Microprocessor based intelligent power factor compensating relay (including power factor meter) in 8 steps for automatic cut off or add on capacitor units to maintain the desired power factor with variation of loads. All associated auxiliary contactors/relay/timer : 01 No(g)600 Amps TPN Aluminum bus bars with coloured heat Shrinkable insualtes sleeves.(h)All steps shall be provided with discharge reactor and heavy duty power contractor through MCCB 3 Pole 25KA electronic release setting. |
| 8 | Automatic power factor control panels fabricated out of 3.15mm thick CRCA steel sheet and other suitable size steel sections (anel iron \"T\" section, channels etc) in cubicalcompartments, free standing, floor mounted, dust and vermin proof complete all as specified and directed. Cable glands shall be provided on top as well as at the bottom of the panels. Panels shall be treated with anticorrosive process before powder coating of approved shade as per specifications. Panels shall be double door hinged type & in-built locking arrangment earthig terminals shall be provided for all distribution panels. Panels shall be suitbale for 440V, 3 phase, 4 wire and 50Hz supply system. Lifting hooks shall be provided. Approval from the Accepting Officer for the design & specificationis fo the Panel & its components shall taken by the contractor before procurement. The automatic control panel shall be of capacity as mentioned under and shall be provided duly housed/mounted with the following components/accessories/fittings complete in all respects as directed:- |
| 9 | (a) 50 KVAR capacitor automatic control panel with the follwing steppings:-(i)Considering 15% space for future expasion.(ii)Steps shall be 10+10+7.5+7.5+5+5+2+2+1(b) BR-6000 Relay of 09 steps shall be used so that in future 2 steps can be used:01 Job. (c)MCCB, FP, 100 Amp, 25KA with microprocessor based release relay: 01 No(d)96x96sqmm 0-500 digital voltmeter with selector switch-01 Set.(e)Phase indicating light protection by 2 Amps SP MCB\"s -9 Sets.(f)Microprocessor based intelligent power factor compensating relay (including power factor meter) in 9 steps for automatic cut off or add on capacitor units to maintain the desired power factor with variation of loads. All associated auxiliary contactors/relay/timer : 01 No.(g)150 Amps TPN Aluminum bus bars with coloured heat Shrinkable insualtes sleeves.(h)All steps shall be provided with discharge reactor and heavy duty power contractor through MCCB 3 Pole 25KA electronic release setting. |
| 10 | M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0 mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to and including galvanised iron or steel earth strip 32 x 6 mmby means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing strip protected by galvanised iron or steel pipe 50 mm bore medium grade and connected to continuous earth wire on pole/ test point.Watering pipe shall be 20mm bore GI medium grade. The earthing shall be inclusive ofexcavation and earth work in any type of soil, charcoal, salt, funnel , PCC pit and RCC cover complete all as specified & directed by Engr-in-Charge.Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labourfor connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal, dust, common salt and ground enhacement material as required to bring the earthing resistance as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. |
| 11 | Supply and fix MCCB4 Pole, 415 V, adjustable thermal type (40% to 100%) and adjustale magenetic release TPN 415 volt, bracking capacity 50 KA, ICS =100 ICU, Adjustable type, 630 Ampscomplete all as specified and as directed by Engg-In-Charge. |
| 12 | Supply and fix MCCB 4 Pole, 415 V, adjustable thermal type(40% to 100%) and adjustale magenetic release TPN 415 volt, breaking capacity 35 KA, ICS =100 ICU,400 Amps complete all as specified and as directed by Engg-In-Charge. |
| 13 | Supply and fix MCCB 4 Pole, 415 V, fixed type,350 Amps with breaking capacity 25 KA with ICU=ICS 100%. complete all as specified and as directed by Engg-In-Charge. |
| 14 | Supply and fix MCCB 4 Pole, 415 V, fixed type,250 Amps with breaking capacity 25 KA with ICU=ICS 100%. complete all as specified and as directed by Engg-In-Charge. |
| 15 | Supply and fix MCCB 4 Pole, 415 V, fixed type,200 Amps with breaking capacity 25 KA with ICU=ICS 100%. complete all as specified and as directed by Engg-In-Charge. |
| 16 | Supply and fix MCCB 4 Pole, 415 V, fixed type,160 Amps with breaking capacity 25 KA with ICU=ICS 100%. complete all as specified and as directed by Engg-In-Charge. |
| 17 | Supply and fix MCCB 3 Pole, 415 V, fixed type,125 Amps with breaking capacity 16 KA with ICU=ICS 100%. complete all as specified and as directed by Engg-In-Charge. |
| 18 | Supply and fix MCCB 3 Pole, 415 V, fixed type,25 to 100 Amps with breaking capacity 16 KA with ICU=ICS 100%. complete all as specified and as directed by Engg-In-Charge. |
| 19 | S&Fin repairheat shrinkable endjoint (indoor/out door)for 1100 volt grade XLPE cable of size400 to 500 Sqmm, 3.5 coretocomplete all as specified. |
| 20 | All as per item no 15 above but of size 185 to 300 Sqmm, 3.5 core complete all as specified. |
| 21 | All as per item no 15 above but of size 70 to 150 Sqmm, 3.5 core complete all as specified. |
| 22 | All as per item no 15 above but of size 25 to 50 Sqmm, 3.5/4 core complete all as specified. |
| 23 | All as per item no 15 above but of size 4 to 16 Sqmm, 3.5/4 core complete all as specified. |
| 24 | S&Fin repairheat shrinkable Straight through jointfor 1100 volt grade XLPE cable of size300 to 400 Sqmm, 3.5 core complete all as specified. |
| 25 | All as per item no 20 above but of size 185 to 240 Sqmm, 3.5 core complete all as specified. |
| 26 | All as per item no 20 above but of size 70 to 150 Sqmm, 3.5 core complete all as specified. |
| 27 | All as per item no 20 above but of size 25 to 50 Sqmm, 3.5/4 core complete all as specified. |
| 28 | All as per item no 20 above but of size 10 to 16 Sqmm, 3.5/4 core complete all as specified. |
| 29 | Taking down existingunsv sign boardany type and materialand labour forInformatorysign board of size 1000mm x600mmmade out of 2mm thick Stainless steel sheetfixed onStainless steelsheet frame of ractangular shape 45mmx25mm fixed on stainless steel pipe 50mm dia 2.25mtr longvertical member-2nos ,including letter writing (100 to 150 words) , logo/drawing/schematic diagram made with computerized printing of fully retro reflective with high intensity prismatic tape pasted on sheet with single side writing includingvertical pipe emmebedded in 0.30x0.45mtr in PCC (1:3:6 ) type C-1 complete all as specified and directed by the Engineer-in-chargeNote :(i)The cost of Excavation post hole, earth work , PCC for foundation etc shall be deemed to be included in the unit rate of this item. Nothing extra shall be admissible on this account. (ii)The letter size of Main heading shall beminimum100mmx10mm and sub heading letter size shall be minimum 50mmx5mm.(iii) The drawing and colour of writing work shall be got approoved by Engineer in charge. |
| 30 | Taking down the existing deteriorated old sign board any type and repalcing with new sign board ofsize 1000mm x 600mm with 2mm thick Stainless steel sheetfixed onStainless steelsheet frame of ractangular shape 45mmx25mm, computerised retroprinting lettter writing /drawing/schematic diagram with retro reflective with high intensity prismatic tapeon one side with suitable adhesive ,fixed on wall withsuitable hanging arrangement all as directed by Engr-in-Charge.Note-The drawing and colour of writing work shall be got approved by Engineer in charge. |
| 31 | Cleaning the area of electric supply,supplyinstallations by cutting and removing jungle sturts, roots, bushes plants small trees from roots etcincl levelling of area and deposited to n.exc 50 mtr to 100 mtr out side installations as directed by Engr-in-Charge. |
| 32 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 400 sqmm . |
| 33 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 240 sqmm |
| 34 | Supply and fixing inrepair, heavy duty aluminium lugsfor LT UG cable of size 185 sqmm |
| 35 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 150 sqmm |
| 36 | Supply and fixing inrepair, heavy duty aluminium lugsfor LT UG cable of size 120 sqmm |
| 37 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 95 sqmm |
| 38 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 70 sqmm |
| 39 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 50 sqmm |
| 40 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 35 sqmm |
| 41 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 25 sqmm |
| 42 | Supply and fixing in repair, heavy duty aluminium lugsfor LT UG cable of size 16 sqmm |
| 43 | Supply and fixing in repair, heavy duty copper lugsfor LT UG cable of size 10 sqmm |
| 44 | Supply and fixing in repair, heavy duty copper lugsfor LT UG cable of size 6 sqmm |
| 45 | Note: For the purpose of arriving at lumpsum amount, the amount of credit schedule i.e Sch \"A\" section II (i.e Rs 13,679.00 shall be deducted from the total amount arrived. |
| 46 | Total of Schedule \"A\" Rs. |