| 1 | Taking down old unsv MCCB , TPN DBs , SPN DBs,& main switch/ enclosure box of any make and type from the site and making good surface complete all as specified and directed. |
| 2 | Taking down old submain wiring of any size, including coduit and make from the site complete all as specified. |
| 3 | Taking down old unsv light fitting of any size and make from the site and making good surface complete all as specified. |
| 4 | Taking down old unsv LT panel of any size & capacity complete all as specified and directed. |
| 5 | M&L for submain wiring with two single core PVCinsulated FRLSH1100 Volts unseathed stranded copper conductor cable 4.0 Sqmm in and including in and including concealed / surface PVC conduits as suitable of site(Medium grade)not less than 20 mm dia,proper colour coding Phase -red/yellow/blue, neutral- black and earth green including making good disturbed surfaces with existing colour coding matching for submain wiring and connection complete FRLS 1100 volts unsheathed stranded copper conuctor cable of 4.0 Sqmm size stranded conductor as earthwire.Note for item No.05, 06 & 07 :two runof main wirePVC insulated FRLS 1100 volts unsheathed stranded copper conductorand one run of earth wire with one run of PVC conduit will be measured and paid in one length. |
| 6 | M&L for submain wiring with two single core PVCinsulated FRLSH 1100 Volts unseathed stranded copper conductor cable 6 Sqmm in and including concealed / surface PVC conduits as suitable of site(Medium grade) ofnot less than 20 mm dia, proper colour coding Phase -red/yellow/blue, neutral- black and earth green including making good disturbed surfaces with existing colour coding matching for submain wiring and connection complete FRLS 1100 volts unsheathed stranded copper conuctor cable of6.0 Sqmm size stranded conductor as earthwire. Make: Gloster/Havells/ Polycab/Finolex (Premium)/RR Kabel |
| 7 | M&L for submain wiring with two run of singlecore PVCinsulated FRLSH 1100 Volts unseathed stranded copper conductor cable 10 Sqmm in and including concealed / surface PVC conduits as suitable of site(Medium grade) ofnot less than 20 mm dia, for submain wiring and connection complete FRLS 1100 volts unsheathed one run of stranded copper conductor cable of 10 Sqmm size stranded conductor as earthwire. Note:- two runof main wirePVC insulated FRLS 1100 volts unsheathed stranded copper conductorand one run of earth wire with one run of PVC conduit will be measured and paid in one length. |
| 8 | Supply and fix 35/40 W High efficient LED Street light fitting with pressure die cast LM6 Aluminum housing and has lenses specially designed for Street Lighting with polycarbonate cover.System level efficacy of the Luminarie > 100lm/W with a life class of 25,000 burning hours at L70. The color temperature is around 6500 K with a color rendering index of 70.The luminaire is IP:66 protected with IK05 impact resistance.It has an electronic driver complaint to IEC safety standards with a power factor>.0.9, voltage variation range 150-270V, THD<20%, High and low protection along with a surge protection of 2.5 KV including provision of suitable size ofGI light grade pipe 1.5 meter length bend to shape and necessary clamps etc for fixing the light fittings on pole fixed complete. |
| 9 | Supply and fixMCB DB SPN 8 way Horizontal, IP - 30 Protection double door 240 V AC 50Hz with for MCBSPN as incomer and SP MCBs as out going with tinned copper bus bar ,neutral link earth link complet Notefor item No 09, 10 & 13 :- Rates are inclusive of cutting / chases for mounting DB box concealed in wall and making good to the disturbed surfaces with existing colour codingby proper plastering work all well as OBD / colour wash / white wash and wall putty where ever is required all as specified directed by Engineer -in-Charge. |
| 10 | Supply and fixMCB DB SPN 12 way Horizontal, IP - 30 Protection double door 240 V AC 50Hz with for MCBSPN as incomer and SP MCBs as out going with tinned copper bus bar ,neutral link earth link complet. |
| 11 | M&L MCB SPN 40 Amp \"C \" curve all as directed. |
| 12 | M&L MCB SP 6 to 32 Amp \"C\" curve all as directed. |
| 13 | Supply & fix in repair factory made epoxy powder coated Distribution Board VTPN-4 ways (IP-30 protection), mechanical impactstrength IK - 07, with cement spill protector double doorfabricated from minimum 1.6 mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 200 Amp copper bus bar, neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one MCCB 125/160 Amp as incomer and 40 to 63 Amp SP MCBs outgoing complete all as specified Note :- MCCB & MCB will be measured & paid separately Note : |
| 14 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/pipe or fixed to VTPN DB or any other indicated situation for loop earthing etc 4 mm dia galvanised or steel wirecomplete all as specified. |
| 15 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/pipe or fixed to VTPN DB or any other indicated situation for loop earthing etc 25 x 4 mm dia galvanised irin strip complete all as specified. |
| 16 | Supply, installation, testing & commissioning, fabricated wall mountedLT panel board indoor type of suitablesize made out of 2 mm thick CRCA sheet suitable for 415 volts, 3 phase, 4 wire duly painted with two coats of synthetic enamelled paint including fixing of of 200 Amps rated copper bus bar for 3 phase and neutral duly fixed on suitable size of insulator, two Nos earth terminal test point, 3 Nos indicator lamp comprising of the following installed complete all as specified & directed by Engineer-in-Charge(a) INCOMING(i) MCCB 4 pole63Amps,25 KAbreaking capacity-01 No.(ii) digital Voltmeter with inbuiltselector switch, Range 0 to 500 Volts -01 Nos(iii) digital Ammeter 0 to 150 Amp with inbuilt selector switch, alongwith sutiable size of CTs set (b) OUTGOING(i) MCB SPN 40 Amps 10 kA breaking capacity duly fixed on DIN rail channel-04 Nos ( Outgoing for each qtr)(ii) MCB SPN 10 Amps 10 kA breaking capacity duly fixed on DIN rail channel-01 No ( Outgoing for staircase and security light)(iii) Provision & install for new electricmeter install inside the LT panrl - 04 NosNote- (i) Marking of Building No&quarter Noson outgoing feeders of LTpanel.(ii) Contractor before placing order, LT panel drawing shall be got approved by the GE. |
| 17 | Supply onlyin repairs MCCB 160 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting. |
| 18 | Supply onlyin repairs MCCB 125 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting. |
| 19 | Supply only in repairs MCCB 100 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting. |
| 20 | S&F sheet metal enclosure single pole and Neutral with a two pin earth plug and socket complete with a MCB SP 20 Amp 230 volts, 50 Hz, 10KA breaking capacity complete. |
| 21 | Supply & Fixing in replacement modular mini AC box with MCB 20 Amp complete with metal box and 3 Pin, 15 Amps plug top complete all as specified and directed. Make : Indo Asian/Havells/Legrand/ABBNote : Rates are inclusive of cutting / chases for mounting Modular metal box concealed in wall and making good to the disturbed surfaces with OBD / colour wash / white wash and wall putty where ever is required. |
| 22 | M & L for earthing complete with galvanized steel earth plate 600x600x6mm thick buried vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of the plate not less than 1.50 mtr below normal ground level, connected to earth lead GI 4 mm dia by means of bolts, nuts,check nuts and washers of galvanized iron and connection to main switch board of panel, including watering pipe GI 20 mm bore light grade 15mm bore for earthing lead, wire mess, funnel, salt, charcoal dust, excavation and refilling pit with PCC 1:2:4 type B1(using 20mm dia stone aggregate) reinforced with 6mm dia round bar @ 75mm cement concrete both always with MS handle 12mm dai and frame all as shown in electric plate No 3 in page 497 of SSR Part I (2009) including testing ion completion all as directed |
| 23 | M & L for earthing complete with galvanized steel earth plate 600x600x6mm thick buried vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of the plate not less than 1.50 mtr below normal ground level, connected to earth lead GI strip 25x4 mm dia earth lead by means of bolts, nuts,check nuts and washers of galvanized iron and connection to main switch board of panel, including watering pipe GI 20 mm bore light grade 15mm bore for earthing lead, wire mess, funnel, salt, charcoal dust, excavation and refilling pit with PCC 1:2:4 type B1(using 20mm dia stone aggregate) reinforced with 6mm dia round bar @ 75mm cement concrete both always with MS handle 12mm dai and frame all as shown in electric plate No 3 in page 497 of SSR Part I (2009) including testing ion completion all as directed |
| 24 | M & L for UL certified earthing electrode 17.2 mm dia 3 mtrs long of low carbon steel electrode withcopper bonding of thickness 250 micron, black-fill earthing enhancing compound AXIS ULTRA/AXIFILL type carbon based compound conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per clouse 14.5 D of IEEE:80 complete standard. Black fill compound should be electronically conductive(like in metals)and should bedepend on moisture for conduction. Black-fill compound should be environment friendly & should be solidify when mixed with water set like concrete and should not letch/diffuse into the ground. Black - fillcompound shall not be mixed with any soil whiling pouring in the bore hole. Test certificate as per IEC:62561-7 for black fill compound shall be submitted along with the material including SS clamp to be provodeboth side and PVC EARTH PIT 300 X 300 MM WITH PLASTIC LID , incl copper strip of size 20x3 mm from earthing toLT panel/TPN DB/SPN DB or any other important machinery complete all as specified. Note : (i)Earth electrode shouldbe applicable standards IS : 3043, IEC62561-2 & IEC 60364 -5 ans made of High Tensile steel rods copper bounded, High Tensile strength, good electrical conduction & effective performance and suitablefor all types of soil and provided minimum distance 3 mtrs. (ii) Black-fill compound should be Complianceto the standardsIEEE: 80, IS -3043,BS 7430, IEC 62561-7, ANSI/NSF 60 Certification . (iii) Positive low resistance electrical connection to the earth . (iv) Does not contain hazardous chemicals.(v) Electrinically conductive (like in metals) and is not dependent on moisture(vi) Provide the desire valueofearthresistanceas per required specified values. (vii) Provide the Exothermicwelding joints to entire gridsystem joints of earthing electrode (viii) Test certificateto be provide of each electrode. |
| 25 | Supplying& Fix in replacement1100volts grade 6 sqmm heavy dutystranded cablePVC insulated aluminium conductor, served with inner sheathing of PVC tape andoverall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apartincluding4 mm suspensionwire, one twin core cable flat or circular |
| 26 | Supply, installation, testing & commissioning, fabricated wall mountedLT panel board indoor type ofsuitable sizemade out of 2 mm thick CRCA sheet suitable for 415 volts, 3 phase, 4 wire duly painted with two coats of synthetic enamelled paint including fixing of of 200 Amps rated copper bus bar for 3 phase and neutral duly fixed on suitable size of insulator, two Nos earth terminal test point, 3 Nos indicator lamp comprising of the following installed complete all as specified & directed by Engineer-in-Charge (a) INCOMING :(i) MCCB 4 pole 100 Amps, 25 kA breaking capacity-01 No.(ii) digital Voltmeter with inbuiltselector switch, Range 0 to 500 Volts -01 Nos(iii) digital Ammeter 0 to 150 Amp with inbuilt selector switch, alongwith sutiable size of CTs set (b) OUTGOING (i) MCB SPN 40 Amps 10 kA breaking capacity duly fixed on DIN rail channel-08 Nos ( Outgoing for each qtr)(ii) MCB SPN 10 Amps 10 kA breaking capacity duly fixed on DIN rail channel-02 Nos ( Outgoing for staircase and security light)(iii) Provision & install for new electricmeter install inside the LT panrl - 08 NosNote- (i) Marking of Building No&quarter Noson outgoing feeders of LTpanel.(ii) Contractor before placing order, LT panel drawing shall be got approved by the GE. |
| 27 | Clening & servicing of LT panel ofboard indoor type of size & any type, made out of 2 mm thick CRCA sheet suitable for 415 volts, 3 phase, 4 wire,duly painted with two coats of synthetic enamelled paint and checking of all MCCB/MCB and connected wiringall as specified and as directed by Engineer-in-Charge Note : If require MCCB/MCB to be measured & paid separately under relevent items of works. |
| 28 | Supply, installation, testing & commissioning, fabricated wall mountedLT panel board indoor type ofsuitable sizemade out of 2 mm thick CRCA sheet suitable for 415 volts, 3 phase, 4 wire duly painted with two coats of synthetic enamelled paint including fixing of of 200 Amps rated copper bus bar for 3 phase and neutral duly fixed on suitable size of insulator, two Nos earth terminal test point, 3 Nos indicator lamp comprising of the following installed complete all as specified & directed by Engineer-in-Charge :(a) INCOMING (i) MCCB 4 pole125Amps,25 KAbreaking capacity-01 No.(ii) digital Voltmeter with inbuiltselector switch, Range 0 to 500 Volts -01 Nos(iii) digital Ammeter 0 to 150 Amp with inbuilt selector switch, alongwith sutiable size of CTs set (b) OUTGOING (i) MCB SPN 40/63 Amps 10 kA breaking capacity duly fixed on DIN rail channel-08 Nos ( Outgoing for each qtr)(ii) MCB SPN 10 Amps 10 kA breaking capacity duly fixed on DIN rail channel-02 Nos ( Outgoing for staircase and security light)(iii) Provision & install for new electricmeter install inside the LT panrl - 08 Nos Note- (i) Marking of Building No&quarter Noson outgoing feeders of LTpanel.(ii) Contractor before placing order, LT panel drawing shall be got approved by the GE. |