| Sl. No. | Item Description |
| 1 | Disconnecting and taking down existing any type of street/ security/flood lights fitting of any make or any capacity for repairs or replacement ofburnt / worn out accessories (LED driver, SPD etc) by using ladder or any other system fromGI bracket of LT pole/ of any height, size or decorative swan neck type pole/ bracket and refixing the same after cleaning, general overhauling ,repairing and making serviceable and refixed the same in same location or any other location and testing with replacement of cable if required complete all as specified and directed.Note :- (a) Contractor should have to recevied complaint through day to day from MES Power House and attend the complaint within 24 hrs.(b) Spare parts and connection cable will be measured and paid seperetly on relevant items as under this BoQ. |
| 2 | Disconnecting and taking down existing any type of Solar Panel type LEDlights fitting of any make/type or capacity for repairs or replacement ofburnt / worn out accessories (MPPT Charge controller or PIR sensor or Lithium Ferro Phosphate Battery or connecting the loose or burn out wire ) by using ladder or any other system from the pole of any height, size and refixing the same after cleaning, general overhauling ,repairing and making serviceable and refixed the solar panel in the same location or any other location and testing with replacement of wire if required complete all as directed. Note :- (a) Contractor should have to recevied complaint through day to day complaint from MES Power House and attend the complaint within 24 hrs. (b) The site for repair of Solar panel will not provide at a time and same will be provide during the currency of contract period as and when repair works required(c) Spare parts and connection cable will be measured and paid seperetly on relevant items as under this BoQ. |
| 3 | Supply only Surge Protection device (SPD) 10 KV, 5KA 240 volts water seal type suitable for LED industrial and outdoor street/security light fitting above 90 watt complete all as specified and directed. |
| 4 | Supply only LED outdoor drivers of capacity 60/72/75 watt 240 volts suitable for outdoor street/security/flood light including all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed. Note : Make of driver shall be same as per make of light fitting. |
| 5 | Supply only LED outdoor drivers of capacity 80/90 Watt 240 volts suitable for outdoor street/security/flood light including all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed. Note : Make of driver shall be same as per make of light fitting. |
| 6 | Supply only LED outdoor divers of capacity 100/120/140 Watt 240 volts suitable for outdoor street/security/flood light including all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed.Note : Make of driver shall be same as per make of light fitting. |
| 7 | Supply only LED outdoor divers of capacity 150/200 Watt 240 volts suitable for outdoor flood light including all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed. Note : Make of driver shall be same as per make of light fitting. |
| 8 | Supply only PVC Sheathed multi stranded unarmed copper conductor cable LT 1100 volt grade Conforming to IS 7098 FRLS (inner sheet) of size 1.5 Sqmm 3 Core (Nominal Area) from pole junction box to light fitting with suitable size copper cable lugs and connector all complete as specified and directed. |
| 9 | Supply and erecting steel tubular pole, swaged in replacement of old damage PCC pole/ steel tubular pole complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9.0 meter long) complete Including dismantling of old one all as complete and directed. Note : Excavation & Earth work andPCCfoundation/baseshall be measured and paid separately under relevant items of this BoQ. |
| 10 | Taking down old unserviceable solar power security/street/flood light fittings of any type/modelincluding associated accessories from 8.5/9 mtr pole/Top of the building/ other similar situation and keep in safe costudy for depositing the in MES store yard complete all as specified and directed. |
| 11 | Supply and fixing LED light fitting for street/security lighting energy saving & environmental friendly long life versatile pressure die-cast aluminium housing with toughened glass and individual high lumen LED with secondary optics of capacity 60 Watt with minimum 120 Lm/watt, 240 volts AC 50 Hz , IP 66 protection suitable for 40 mm dia GI pipe bracket including five years on site warranty from manufacturer complete all as specified and directed. |
| 12 | Supply and fixing LED light fitting for street/security lighting energy saving & environmental friendly long life versatile pressure die-cast aluminium housing with toughened glass and individual high lumen LED with secondary optics of capacity 70/72 Watt with minimum 120 Lm/watt, 240 volts AC 50 Hz , IP 66 protection suitable for 40 mm dia GI pipe bracket including five years on site warranty from manufacturer complete all as specified and directed. |
| 13 | Supply and fixing LED light fitting for street/security lighting energy saving & environmental friendly long life versatile pressure die-cast aluminium housing with toughened glass and individual high lumen LED with secondary optics of capacity 90 Watt with minimum 120 Lm/watt, 240 volts AC 50 Hz , IP 66 protection suitable for 40 mm dia GI pipe bracket including five years on site warranty from manufacturer complete all as specified and directed. |
| 14 | Supply and fixing LED flood light fitting energy saving & environmental friendly long life versatile pressure die-cast aluminium housing with toughened glass and individual high lumen LED with secondary optics of capacity 150 Watt with minimum 120 Lm/watt, 240 volts AC 50 Hz, IP 66 protection including five years on site warranty from manufacturer complete all as specified and directed. |
| 15 | Supply and fixing LED light fitting for street/security lighting energy saving & environmental friendly long life versatile pressure die-cast aluminium housing with toughened glass and individual high lumen LED with secondary optics of capacity 200 Watt with minimum 120 Lm/watt, 240 volts AC 50 Hz , IP 66 protection suitable for 40 mm dia GI pipe bracket including five years on site warranty from manufacturer complete all as specified and directed. |
| 16 | Refixing of Security/street/flood light fittings of any type/model including associated accessories to 8.5/9 mtr pole/Top of the building/ other similar situation obtained from item no 10.00 complete all as specified and directed. |
| 17 | Supply andfixing LED Post top light fittting luminaires 40/45 Watts IP 65 type made in die-cast aluminium housing with decorative opal/clear polycarbonate diffuser complete with control gear box suitable for 50 mm dia post and all accessories duly prewired and connecting to junction box and testing complete all as specified and as directed. |
| 18 | M & L for decorative type single arm street light bracket made out of mild steel medium grade MS pipe 125 mm dia 0.40 mtr length suitable for fixing into top of the steel tubular pole and mild steel medium grade 40 mm dia 1.40 mtrs length and shape by cutting, welding and well finishing with drilling, hole, jointing of neccessary6 mm sheet metal corner support top cover and also inside the pipe and fixing with 12 mm dia 03 nos nuts & bolts duly welded at bottom parts for tightening bracket on pole including necessary painting with two coats aluminium paint over a coat of red oxide primer and necessary cutting/hole to existing pole and dismantling of old unserviceable bracket of any size and shape complete all as specified and as directed. Note : Design and drawing of street light bracket may required to submit before fabrication for approval of accepting officer. |
| 19 | M & L for decorative type single arm street light bracket made out of mild steel medium grade MS pipe 80 mm dia 0.40 mtr length suitable for fixing into top of the steel tubular pole and mild steel medium grade 40 mm dia 1.40 mtrs length and shape by cutting, welding and well finishing with drilling, hole, jointing of neccessary6 mm sheet metal corner support top cover and also inside the pipe and fixing with 12 mm dia 03 nos nuts & bolts duly welded at bottom parts for tightening bracket on pole including necessary painting with two coats aluminium paint over a coat of red oxide primer and necessary cutting/hole to existing pole and dismantling of old unserviceable bracket of any size and shape complete all as specified and as directed. Note : Design and drawing of street light bracket may required to submit before fabrication for approval of accepting officer. |
| 20 | M & L for decorative type double arm street light bracket made out of mild steel medium grade MS pipe 125 mm dia 0.40 mtr length suitable for fixing into top of the steel tubular pole and mild steel medium grade 40 mm dia two nos 1.40 mtrs length each arm and shape by cutting, welding and well finishing with drilling, hole, jointing of neccessary6 mm sheet metal corner support top cover and also inside the pipe and fixing with 12 mm dia 03 nos nuts & bolts duly welded at bottom parts for tightening bracket on pole including necessary painting with two coats aluminium paint over a coat of red oxide primer and necessary cutting/hole to existing pole and dismantling of old unserviceable bracket of any size and shape complete all as specified and as directed. Note : Design and drawing of street light bracket may required to submit before fabrication for approval of accepting officer. |
| 21 | Supply and fixing pole mounted SMC junction box/bus bar chamber for loop IN/OUT connection of street light cable of size 295x195x100 mm high heat distoration temperature, non-fusing , shockproff, rustproof, 100 % weatherproof, fire retardant- class FV-O as per IS 11731 Part-II and suitable locking arragement with three phase and neutral aluminium busbar of size 20X3 mm of length 170 mm wrapped with PVC sleeves with maintained the colour code, MCB DIn rail channel for mouting of one no MCB SP and provision of making holes with GI nuts, bolts & washers for cable connections mounted on hydrograpic insulators with nuts & bolts at both ends of busbar and fixed on pole steel/PCC with suitable two nos flat iron clamp 25x4 mm with nuts and bolts (duly painted with two coats of aluminium paint over a coat of red oxide primer) and dismantling of old unserviceable one complete all as specified and as directed.complete all as specified and directed. |
| 22 | Supply and fixing in repair PVC Sheathed multi stranded unarmed copper conductor cable LT 1100 volt grade Conforming to IS 7098 FRLS (inner sheet) of size 2.5 Sqmm 3 Core (Nominal Area) from pole junction box to light fitting with suitable size copper cable lugs and connector all complete as specified and directed. |
| 23 | Supply and fixing in repair of three phase 8 KW automatic street light control switch using Infrared Sensor based NATURE SWITCHfor automatic switching of street lights. Nature switch operation should bebased on Natural Light Lux level. Switching off illuminance level should be of minimum 30 Lux and Switching on illuminance should be less than or equal to 10 LUX. The sensor should also have part night operation facility of min 4 hrs to maximum 12 hrs. The circuit shall have a provision for manual over ride operation. The sensor along with suitable power contactors and incoming-outgoing MCBs should be enclosed in a pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC junction box conforming to IP 66 complete all as directed by GE. |
| 24 | S & F in replacement power contactor 3 pole, 40 Amps capacity panel mounting with entry terminals complete all as specified and directed. |
| 25 | Supply and fixing in repair MCB TPN 50 to 63 amps 10 KA ,C-seriesincluding connection with suitable size aluminium / copper lugs complete all as specified and directed . |
| 26 | Supply,laying & fixing in repair double wall corrugated (DWC) pipes ofsize 63 mm outer dia conforming to IS 16205 (Part-24) including all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc allas specified and directed by GE. |
| 27 | Relaying of old serviceablebrick as in cable protection completeall as specified and directed. |
| 28 | M&L for taking out old unserviceable cable of any size , GI pipe protection, bricks including separating serviceable bricks & set aside and removing un-serviceable bricks from position allcomplete as specified and as directed. |
| 29 | Labour for drillinghole under the road with the help of bock / by manual or by machinefor crossing GI tubingof any size 100 mm pipefor cable protection complete all as specified and directed. |
| 30 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 10 sqmm4 core with all fixing & connecting accessories such as aluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed. (NOTE: Earthwork & Excavation, GI pipe brick protection etc shall be measured and paid separately under relevant items of this schedule \"A\" part). |
| 31 | All as per item no.30.00 but Size 16 Sqmm X 4 core |
| 32 | Relaying of old serviceable UG cable of any size obtained from item no 28.00 complete as specified and as directed. |
| 33 | Excavation in trenches not exceeding 1.5 mtrs wide & not exceeding 1.5 mtr in depth in soft or loose soil & getting out complete all as specified and as directed. |
| 34 | Excavating in trenchesexceeding 1.5 m wide and not exceeding 3 m depth and not less than 1.5 min depth for laying of cables & foundation of poles , stay assembly and getting out in any type of soil complete all as specified and directed . |
| 35 | Returning filling including spreading levelling watering & well Ramming in layers not exc 25 cm complete all as specified and as directed. |
| 36 | Removing excavatedmaterial not exceeding 50 mtr & deposited where direceted at a level not exceeding 1.5 mtr above the ground level complete all as specified and as directed. |
| 37 | M/L for bricks common burnt sub class B designation for protection of cable complete all as specified and as directed. |
| 38 | Supply and lay dry river sand filling for under ground cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed. |
| 39 | M&L for cement concrete1:4:8type D2, using 40mm graded stone aggregate as in foundations filling and mass concrete complete all as specified and directed. |
| 40 | M&L for cement concrete1:3:6type C2,using 40mm graded stone aggregate as in foundations filling and mass concrete complete all as specified and directed. |
| 41 | M & Lforcement concrete 1:2:4 type B-1 using 20mm graded stone aggregate in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete. |
| 42 | M&L for RCC(Nominal mix) type B1, 1:2:4 (using 20mm graded crushed stone aggregate) as in foundation of octagonal street light / decorative pole, including rafts, footings, foundation beams plinth beams bases for columns etc. complete all as specified and directed. |
| 43 | M&L for formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams,sides and soffits (if any) of foundation and plinth beams; and similar work; vertical to rough finished surface complete all as specified and directed. |
| 44 | M&L forTMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed. |
| 45 | M&L forTMT bars5mm dia and over upto and including 10mm dia in stirrups, spacers and binders cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed. |
| 46 | Supply & fix LT straight through Cable joining kitheat shrinkabale complete with jointing materials suitable for LT Armoured cable 4 core of size10 to 16 sqmm Sqmm all as directed. |
| 47 | S&F polyolefin LT Cable sleeves heat shrink with colured coding (Red, Yellow, Blue and Black) suitable for 1100 volt grade 3.5 / 4 core XLPE armoured, aluminium conductor of cable size 6 Sqmm to 10 sqmm all as specified and directed |
| 48 | M&L fordecarbonisation and tightening the loose connection of end terminalsand pole junction box of street light fitting, Flood light, Post top lanten of any size/capacity at any height and refixing the same with PVCbrass 3 way connector after the cleaning refreshing the join etc and make the light functional complete all as specified and directed. Note : (i) Cost of PVC connector measured and paid separatelyon relevant items of BOQ. (ii) Complaint of decarbonisation raised within 30 days from the dt of repair of the same will be repairedby the contractorwithout anyextra r cost. |
| 49 | Supply only three way PVC brass 3 way10 Amp connector to coneect the street light with service wire size for1.5 sq mm wire multistrandercopper conductor complete all as specified and directed . |
| 50 | S&F in repair of sensor (NS-02E) for three phase existing nature switch nincluding taking down old onecomplete all as specified and directed. |
| 51 | Labour only for taking down the mono crystaline solar panel of solar street light and cleanining the same with water after the cleaning refixng in positionand connect all the connection properly tofunctioning the same complete all as specified and directed. |
| 52 | Supply and fixing high efficiency-premium solar integrated street light capacity with 30 Watt built in Mono Crystalline Panel, Lithium Ferro Phospate (LiFePO 4) Battery, MPPT Charge controller and PIR sensor with colour temperature 6000-6500K,2 days autonomy with dimming profilefixing on existingpoles, If the same is not fixed on existing pole then all the aceesoories required for modified the pole provide by contractor on the quoted rate no extra payment made for modification of polecomplete all as specified and directed. |
| 53 | Supply and fixing Hot dip Galvanised Iron octagonal pole of height 5 mtrs made of HT steel of grade S355 with 130 mm bottom A/F & 70 mm top A/F made up of 3 mm thick Galvanised Iron sheet along with base plate of size 225 x 225 x16 mm thick and 04 nos foundation \"J\" Bolts, nuts and washer as per manufactuer specification with inbuilt Sleek terminal box with required sizes studs for 4 core 16 sq mm Al cable termination as required for each out going including proper locking arrangement for fixing the Solar panel street light/ street light of any capacity all in one type including all fixing accessories complete all as directed and as specified. NOTE: Excavation & Earth work andPCCfoundation/baseshall be measured and paid separately under relevant items of this BoQ. |
| 54 | Supply only MPPT Charge Controller suitable for solar street light panel for capacity 20/30 watt LED light including all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed. |
| 55 | Supply only Lithium Ferro Phosphate4e (LiFePO4) Battery suitable for existing solar panel street light of capacity 20/30 watt including all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed. |
| 56 | Supply only PIR sensorwith colour temperature 6000-6500Ksuitable for existing solar street light capacity 20/30 wattincluding all necessary fixing accessories complete as per site existing make and model of light fitting complete all as specified and directed. |
| 57 | Supply andfixing decorative LED light fittting luminaires 80 Watts IP 65 type made in die-cast aluminium housing with decorative opal/clear polycarbonate diffuser complete with control gear box suitable decorative street light pole and all accessories duly prewired and connecting to junction box and testing including taking down complete all as specified and directed. Note: (a) Design of light fitting got approve form accepting officer before placing order with make and cat No. |
| 58 | Supply and fixing decorative Street Light Pole of any design and of size 03 Mtrs minimum height with its accessories, made by aluminium die pole plate with cast iron decrative base frame , bolts, nuts, washer and screws with minimum pole weight is 48 Kgs complete including black powder coated painting with design paint after necessary preparation ofsurfaces including one coat of red oxide primer complete with cable control box complete all mas specified and directed.Note: (a) Design and drawing of pole submit to office before manufacturing/Placing of order and got approve form accepting officer. (b) PCCfor foundation/baseshall be measured and paid separately under relevant items of this BoQ) (c) Weight of complete pole is minimum 48 Kgs. |
| 59 | M&L earthing complete with galvanised steel earth plate electrode 60×60cm×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron 25x4mm earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 connected to earthing test point including testing on completion including watering GI pipe 20mm bore medium grade, 40 mm bore light grade GI pipe for protection of earth lead including provision ofconcrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm including 8mm dia TMT bars both ways @ 15cm centre to centre with one handle for lifting made out of8mm dia MS bar, funnel & wire mesh, excavation and earth work in any type of soil complete including dismantling existing all as specified & directed. |
| 60 | Taking down carefully copper / aluminium point wiring (light, fan, switch,socket or power, Bell & Two way point) complete with fitting such asswitches, sockets, ceiling rose,sketch light fittings etc, and making good the disturbed surface ofwalls and floors etc complete all as specified and directed. |
| 61 | Taking down carefully main switches DB\"s/ MCB DB\"s and making good the disturbed surfaces of wallsetc complete all as specified and directed. |
| 62 | Taking down carefully copper / aluminium sub mainwiring including teak wood batten / conduit and making good the disturbed surface of walls directed. |
| 63 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor drawn through and incuding medium grade PVC conduit with all accessories such as elbow, tee, bend etc, ISI marked,concealed on wall/ceiling and incuding provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including or modular metal flush box for fixing modular switch, socket etc and mild steel sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly and coated of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover for housing the switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light point controlled by one way switch complete all as specified and directed. Note :- Switches, socket and fan regulators and modular box inner and outer cover plate to be measured and paid separately. |
| 64 | All as per item no 63.00 above but one bell point controlled by one bell Push |
| 65 | All as per item no 63.00 above but one 5 Amps socket out let point controlled by one switch on same board with other switches. |
| 66 | All as per item no 63.00 above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 67 | All as per item no 63.00 above but one light point controlled by one, two way switch 5 Amps |
| 68 | All as per item No 63.00 above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. |
| 69 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor drawn through and non metallic rigid PVC casing caping double lock system with all accessories such as elbow, tee, bend etc, ISI marked on wall/ceiling and incuding provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly and coated of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover for housing the switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light point controlled by one way switch complete all as specified and directed. Note :- Switches, socket and fan regulators to be measured and paid separately. |
| 70 | All as per item no 69.00 above but one bell point controlled by one bell Push |
| 71 | All as per item no 69.00 above but one 5 Amps socket out let point controlled by one switch on same board with other switches. |
| 72 | All as per item no 69.00 above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 73 | All as per item No 69.00 above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. |
| 74 | Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor drawn through in existing conduit on wall/ceiling and incuding provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly and coated of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover for housing the switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light point controlled by one way switch complete all as specified and directed. Note :- Switches, socket and fan regulators to be measured and paid separately. |
| 75 | All as per item no 74.00 above but one bell point controlled by one bell Push |
| 76 | All as per item no 74.00 above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 77 | All as per item No 74.00 above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. |
| 78 | Supply and fixing switch piano flush button single pole one way 5 amps, AC 240 Volts complete all as specified and directed. |
| 79 | Supply and fixing in repair switch piano flush button single pole one way 5 amps, AC 240 Volts complete all as specified and directed. |
| 80 | Supply and fixing socket outlet flush type 5 Amps, 5 pin, AC 240 Volts complete all as specified and directed. |
| 81 | Supply and fixing in repair socket outlet flush type 5 Amps, 5 pin, AC 240 Volts complete all as specified and directed. |
| 82 | Supply and fixing switch piano flush button single pole one way 15 Amps AC 240 volt complete all as specified and directed. |
| 83 | Supply and fixing in repair switch piano flush button single pole one way 15 Amps AC 240 volt complete all as specified and directed. |
| 84 | Supply and fixing socket outlet flush type multipurpose 2 in1, 3 pin 5 and 15 Amps, AC 240 volts complete all as specified and directed. |
| 85 | Supply and fixing in repair socket outlet flush type multipurpose 2 in1, 3 pin 5 and 15 Amps, AC 240 volts complete all as specified and directed. |
| 86 | Supply and fixing bell push single pole, 6 Amps, AC 240 Volts, flush type complete all as specified and directed. |
| 87 | Supply and fixing in repair bell push single pole, 6 Amps, AC 240 Volts, flush type complete all as specified and directed. |
| 88 | Supply and fixing celing rose surface bakelite 63.5 mm dia three terminal complete all as specified and directed. |
| 89 | Supply and fixing in repair celing rose surface bakelite 63.5 mm dia three terminal complete all as specified and directed. |
| 90 | Supply and fixing electronic Fan regulator 450 watt 2 module, with 5 step type regulator complete all as specified and directed. |
| 91 | Supply and fixing in repair for electronic Fan regulator 450 watt 2 module, with 5 step type regulator complete all as specified and directed. |
| 92 | Supply and fixing ding dong Bell, AC 240 Volts,single pole complete all as specified and directed. |
| 93 | Supply and fixing Bell multi music typeAC 240 Volts, single pole complete all as specified and directed. |
| 94 | Refixing paino switch of any capacity 5 /15 amps obtained from respective item of BOQ. |
| 95 | Refixing socket 5 amps or 15 amps capcaity obtained from respective item of BOQ. |
| 96 | Supply and fixing in repair PVC rectangular block for mountingswitches, sockets ,fan regulatoretc with 3 mm thick plastic laminated sheet cover of size 350 x 300 x 50 mm complete all as specified and directed. |
| 97 | All as per item no 96.00 above but of size 250 x 200 x 50 mm. |
| 98 | All as per item no 96.00 above but of size 200 x 150 x 50 mm. |
| 99 | All as per item no 96.00 above but of size 175 x 100 x 50 mm. |
| 100 | All as per item no 96.00 above but of size100 x 100 x 50 mm size. |
| 101 | Supply and fixing in repair pressed steel terminal rectangular sunken boxes made out of 1.6 mm thick mild steel sheet metal with earth dolly for mounting, switches, sockets, fan regulator etc including 3.00 mm thick plastic laminated sheet cover of suitable size for MS box size of 250 x 300 x 50 mm with brass screws and brass washers complete all as specified and directed. |
| 102 | All as per item no 101.00 above but of MS box size of 200mm X 250 mm |
| 103 | All as per item no 101.00 above but of MS box size of 200mm X 150 mm |
| 104 | All as per item no 101.00 above but of MS box size of150mm X 100 mm |
| 105 | All as per item no 101.00 above but of MS box size of 100mm X 100 mm |
| 106 | Supply and fixing in repair plastic laminated bakelite sheet cover of Hylam brand 3.00 mm thick including cutting holes for switches, sockets etc as per requirement including fixing with brass machine screws and washer for size 275 mm X 325 mm complete all as specifed and directed. |
| 107 | All as per item no 106.00 above but of size225 mm X 275 mm |
| 108 | All as per item no 106.00 above but of size 225 mm X 175 mm |
| 109 | All as per item no 106.00 above but of size175 mm X 125 mm |
| 110 | All as per item no 106.00 above but of size125 mm X 125 mm |
| 111 | Supply and fixing double door TPN DBs 4 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral & DB\"s will be fitted concealed in wall / surface as per site required complete all as specified and directed. |
| 112 | Supply and fixingdouble door SPN DBs 12 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 113 | Supply and fixingdouble door SPN DBs 8 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 114 | Supply and fixing double door SPN DBs 4wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 115 | Supply and fixing single door SPN DBs 2 wayof powder coated DB\"s suitable for MCB\"s fitted with bus bar,Neutral link,Earth bar and Din ral as per existing finishing complete all as specified and directed. |
| 116 | Supply and fixing MCB SPN 5 to 40 amps 10 KA ,C-series including connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 117 | Supply and fixingMCB SPN 40 to 63 amps 10 KA ,C-seriesincluding connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 118 | Supply and fixingMCB SP 240 volts 5 to 32 Amps, 10 KA breaking capacity,\"C\" type including connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 119 | Supply and fixing MCB TPN 50 to 63 amps 10 KA ,C-seriesincluding connection with suitable size aluminium / copper lugs complete all as specified and directed. |
| 120 | Refixing MCB TPN/SPN/SP any size, capacity obtained from respective item of BOQ. |
| 121 | Supply and fixing LED tube light batten box type with decorative end caps suitable single tube 1x 18/20 watt T8 lamps type complete with both end bi-pin holder and all accessories internally pre wired and fixed to wall/ceiling incl fittings accessories and connecting with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 122 | supply and fixing LED tube rod 18/20 watt230 volt T8 type complete with electric electronic driver incl fittings accessories and connecting with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 123 | Supply and fixing in repair Energy Savings Long Life 15 Watt 230 Volts50 Hz, IP20 rating recessed mounting downlight withaluminium housing and heat sink for better thermal performance and morden and minimalist design with flushed diffuser and as per site requirement ceiling cutout fitting for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 124 | Supply and fixing in repair Energy Savings Long Life 12 Watt 230 Volts50 Hz, IP20 rating recessed mounting downlight withaluminium housing and heat sink for better thermal performance and morden and minimalist design with flushed diffuser and as per site requirement ceiling cutout fitting for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 125 | S&F recessed mounting fitting 1 x 36/42 watt ultra modern design Natural white/ Warm white architectural LED luminaire (2X2) feet which provides soft-light and glare free symmetrical illumination suitable for Armstrong / Grid Ceiling including LED driver and 36/42 watt LED for cool/warm or natural white light options as required including electronic driver of suitable capacity with PF>0.9 complete all as specified and directed. |
| 126 | S & F in replacement Building security LED light luminaire 1X25 W, pressure die cast housing with toghned glass, 240V, efficacy Min 110 Lm/Watt, IP-66, 5 KV external SPD , THD<10%, PF>0.95, CCT-5700K, High power SMD LEDs with LDR sensor working 10 Lm visibility for automatic ON/OFF operation and including cable for connection from celling rose with 1.5 Sqmm 3 CorePVC insulated stranded copper conductor (FRLS) cable including GI bracket medium grade bent to shape etc all as specified and directed. |
| 127 | Supply and fixing LED Batten light Aluminium Housing 18/20 watt230 volt T8 type complete with electric electronic driver incl fittings accessories and connecting with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 128 | Refixing LED tube light fittings any type, wattage and any size obtained from respective item of BOQ. |
| 129 | Supply and fixing LED batten tube light fitting 1x 10 watt 230 voltwall/ ceiling mounted luminaire with polycarbonate hoiusing and integrated electronic driver with all accessories internally pre wired and incl connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. |
| 130 | Supply and fixing LED bulk head 10 watt fittings environmental friendly ultra modern energy saving surface mounted decorataive bulk head fitting with driver and prewired and necessary electric connection with PVC insulated twin twisted flexible copper wire of size 0.75 Sqmm complete all as specified and directed. |
| 131 | S&F in replacement Lamp holder , PVC / Polycarbonate type with back plate suitable for B22 lamp including LED Bulb 9W complete all as specified anddirected. |
| 132 | M&L for Sub main wiring two run single core PVC insulated unsheathed cable FRLSH 1100 volts grade, 6.00 Sqmm size with multistranded copper conductor, drawn in but excluding non metallic rigid PVC conduit including one run of 4.00 Sqmm single core PVC insulated, unsheathed cable FRLSH 1100 volts grade with multi stranded copper conductor green colour as earth continuity conductor cable connected to earth dolly complete all as specifed and directed. |
| 133 | All as peritem No 132.00 but with two single core 4.0 Sqmm sizewith 2.5 Sqmm cable as earth conductor complete. |
| 134 | All as peritem No 132.00 but with two single core 2.5 Sqmm sizewith 2.5 Sqmm cable as earth conductor complete. |
| 135 | All as peritem No 132.00 but with two single core 1.5 Sqmm sizewith 1.5 Sqmm cable as earth conductor complete. |
| 136 | M&Lfor Rigid non metallic PVC conduitISI marked, medium grade, inclusive of all fitting such as tees,bends. Junction boxes, elbows saddles. Pipe hooks,couples and lock outs etc 25 mm external dia, fixed on surface mounted complete and making good disturbedsurfaces in repairs all directed. |
| 137 | M&Lfor Rigid non metallic PVC casing capingISI marked, medium grade,not less than 25 mm base size inclusive of all fitting such as tees,bends. Junction boxes, elbows saddleshooks,couples and lock outs etc fixed on surface mounted complete and making good disturbedsurfaces in repairs all directed. |
| 138 | Supply & fixing Sheet metal earth plug, socket, single pole and neutral with single pole MCB 32 Amps 240 volts fixed in repairs complete. |
| 139 | Supply and fixing ofEarthing to building with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth strip 25x4mm by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead strip protected by GI pipe 40 mm dia light grade and connected to earth test point includingexcavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion all as specified and directed. |
| 140 | (Note : The Scope of Work contained in \"Sch of Credit\" amounting to Rs. 81,292.00. The Quoted sum shall be arrived at after deducting the amount of “Sch of Credit” from the total amount of the ‘BoQ’ |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail