| 1 | Dismantling/Taking down ACSR conductors of any type & size from existing LT pole & taking a side duly disconnecting all electrical connection complete all as specified & directed by Engr-in-Charge. |
| 2 | Dismantling/Taking down Cross arms of MS Channel or angle section etc complete all as specified & directed by Engr-in-Charge. |
| 3 | Dismantling Insulatotrsof any type & size from existing LT polecomplete all as specified & directed by Engr-in-Charge. |
| 4 | Taking out unserviceable LT service connection cable of size up to 35 sqmm 3.5 core complete all as specified and directed. |
| 5 | Taking out old unserviceable LT cable of size 50 sqmm up to 150 sqmm 3.5 core complete all as specified and directed. |
| 6 | Excavating in trenches, in any type of soilnot exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc or not exceeding 10 Sqm on plan and not exceeding 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed. |
| 7 | All as per item No 6.0, above but for each additional 1.5 m or part thereof in depth beyond the first 1.5 mtr. |
| 8 | M&L for Cement concrete1:2:4 type B 2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed. |
| 9 | M&L for Cement concrete1:4:8 type D 2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed. |
| 10 | M&L for Cement concrete1:3:6 type C 1 (using 20 mm graded stone aggregate) as in roof kerbs or pole couping of size 300x300 mm or chamfered on edges complete all as specified and directed. |
| 11 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. |
| 12 | Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 13 | M&L Sand cushioning with fine dry unwashed sand in trenches for cushioning of cables complete all as specified and directed. |
| 14 | M&L Old size sub class \"B\" bricks, laid in trenches as cable covers complete all as specified and directed. |
| 15 | Supply and fixing in repairsSteel tubes, galvanised, light grade, ISI marked 40mm bore for protection of cable under floor, road and on wall complete all as specified and directed. |
| 16 | Supply and fixing in replacement for LED flood light 170 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP-66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 17 | Supply and fixing in replacement for LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 18 | Supply and fixing in replacemntmoulding compound Street light junction box of size 250 mm x 200 mm x 105mm complete with shock and rust proof, termite resistant, tamper proof , front openable type and including suitable provisionfor single phase, two wire cable (size upto 25 Sqmm 2 Core) incomming & outgoing loop -in loop connection and including one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole/wall complete all as specified and directed. |
| 19 | Supply and Fix, Three core pvc insulated coppercable with multistranded copper condutor ofsize 1.0 sqmm x three core, and drawing in to PVC Conduits & GI pipe bracket and connect tostreet light fittings complete all as specified and directed by Engr-in- Charge. |
| 20 | M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape suitable for fixing street light / security light fitting on Steel tubular pole/ RCC pole / building wallincluding two Nos clamps made out 30mm X 5mm flat with suitable nuts and bolts (clamp type - as per siterequirement ) including two coats of aluminium paint over a coating of red oxide primer and Taking down of existing unserviceable rusted street light brackets with clamps, nuts and bolts etc, complete all as specified and directed. |
| 21 | Supply and Laying in replacement XLPE insulated and PVCarmoured heavy duty electric cables with aluminum conductor, 1100 volt grade of size 10 sqmm,4.0 core, in trenches/through pipes/ducts or on poles/walls jointing to O/H conductor, LT panels, main switch with suitable size aluminum lugs and testing complete all as specified & directed for the following sizes:- Note :(a) Excavation shall be measured and paid seperately under respective items of Sch \"A\" . (b) Allrequired lugs of suitable sizes according to laying of cable & Connection deemed to be including in quoted rate. |
| 22 | All as perabove Item No. 21.00,above,but Size 16 Sqmm 4.0 core. |
| 23 | All as perabove Item No. 21.00,above, but Size 35 Sqmm 3.5 core. |
| 24 | All as per above Item No. 21.00, above,but Size50 Sqmm 3.5 core. |
| 25 | All as per above Item No. 21.00, above, but Size 95 Sqmm 3.5 core. |
| 26 | All as per above Item No. 21.00, above, but Size 150 Sqmm 3.5 core. |
| 27 | Supply and fix in repairs MCCB 125 Amps, 16 KA, FP, 415 volts with neutral link including al cable lugscomplete all as specified and directed. |
| 28 | Supply, installation testing and commissioning replacement of street light control boxas a pole mountable enclosureconforms to IP-64 suitable for 440/230V, AC, 50 Hz,consisting of a light sensitive control system, power contactor for load switching, MCB and terminal suitable for 1 phase, 5 KW load blocks complete all as specified and directed. |
| 29 | Supply, installation testing and commissioning replacement of street light control boxas a pole mountable enclosureconforms to IP-64 suitable for 440/230V, AC, 50 Hz,consisting of a light sensitive control system, power contactor for load switching, MCB and terminal suitable for 3 phase, 5 KW load blocks complete all as specified and directed. |
| 30 | Supply and fix in repairs PVC tubes, medium grade, ISI marked 20mm bore for laying of sub-main wire/cable on Street Light Poles and on wall, incl necessary accessories & fixing arrangments like PVC band, clamps , nut -bolts etc.complete all as specified and directed. |
| 31 | Supply and Errecting LT Panel outdoor type mounted and fixed with PCC foundation , made out of MS sheet factory assembled and factory fabricated out of 3.15 mm thick sheet steel with suitable size MS angle duly spray painted with two coat of gray synthetic enamel paint over one coat of red oxide zinc chrome primer after preparation of surface , with required civil work & wiring with copper cable of suitable size, connecting including indication lamp LED type for each phase , Aluminium bus bar - 300 Amps rating - 03 Nos. for phases and 300 Amp rating - 01 No. for neutral and adjustable type MCCB 200 Amp, 36 kA, FP, 415 volts with neutral link incl inbuilt industrial type locking arrangments , front openable incl necessary arrangments for fixing with suitable, clamps,nuts, bolts wahers etc, & incl Danger notice board , feeder marked,testing and commissioning , size 600 x600x 300 mm, complete all as specified and directed by Engr-in-Charge. |
| 32 | M&Lfor dismantaling of oldPCC poles /MS pole struts any type and size and Transporting setting aside for re-use within 50 metres or taking out against schedule of credit complete all as specified and directed. |
| 33 | Supply and fix Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 ,9.0 metres long, erected to truely vertical position, painting externaly embedded portion in PCC with black bitumenous paint and externally exposed to view portion with aluminium paint in two coats, making five alternate strips 30cm wide with black and yellow paint in two coats, marking MES number with black paint complete all as specified and directed. (Note : Excavation and PCC will be measured and paid separately under respective items). |
| 34 | Supply and fix Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 ,11.0 metres long,erected to truely vertical position, painting externaly embedded portion in PCC with black bitumenous paint and externally exposed to view portion with aluminium paint in two coats, making five alternate strips 30cm wide with black and yellow paint in two coats, marking MES number with black paint completeall as specified and as directed. (Note : Excavation and PCC will be measured and paid separately under respective items). |
| 35 | M & L forPainting to street light pole of steel tubular swaged typewith two coat of aluminiumpaint after cleaning to rusted portion of poleand finishing the surfaces including one coat primer top to bottom, painting on cross arms/FI clamps/street liht brackets of any type including makingalternative blak and yellow strip with synthethic enemelled paintup to 1.5 Mtr height from ground level & writing of polenumbers with black paint onpoles complete all as specified and directed. |
| 36 | M&L for painting of LT PCC poles 09 Mtr. with acrylic paint after apply two coat of cement base primer and making the surface smooth including painting of cross arms, clamps, etc with two coat of aluminium paint and providing alternative strip of 30 cm width (3 black and 2 yellow) from bottom of pole to 1.5 m height, writing of pole numbers in yellow circle 15 cm withblack paint on poles complete all as specified and directed. |
| 37 | Supply, installation, testing and commissioning out door typeLT panel board ,made out of 3.15mm thick CRCA sheet , factory made, CPRI Approved, cubical type, with slantingtop at leaset 10 Cm projection all around, fedder pillar type,fabricatedwith 50x50x6mm angle iron frame workwith independent door for each feeder,busbar chamber cable tray on both side fully compartmentlized design, double door type & commen openable hinged door from rear side, floor mounting type, busbars made of aluminiumduly insulated with heat retardent fire proof (HRFR) heat shrinkable sleeves of relevant colours.Bus bar shell be properly supported/mounted on epoxy insulators.All live parts and joints shall be insulated with (HRFR) shrouds, conforming to IS, including provn for connecting suitableearth strips,painting with one coat of anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032),Confirming to IP 54 protection and confirming relavent IS, comprising the adequate arrangement to supply & fix the following accessories,including connecting cable glands and cable lugs,fixing of earth lead to earth terminal of panel including necessary excavation & PCC foundation complete all as specified & Directed by Engr-in-Charge.( Note:- Cost of all accessories are deemed to be included in the rate quoted). |
| 38 | Incoming (a) Aluminium bus bar - 400 Amps rating - 03 Nos. for phases and 400 Amp rating - 01 No. for neutral(b) MCCB 4 pole 400 Amps, 415 volt, 36 KA - 01 No ( incoming) ( Make - Legrand/ L&T/ ABB/ Schenider) (c)3 phase Voltmeter (0-500V) digital type with selector switch-01 No (d)3 phase Ammeter (0-500 Amps) digital type with CT\"s of suitable ratio and selector switch - 01 No.(e) ON/OFFLED type indication lamp with toggle switch - Set of 03Out going:-(a)MCCB 3 pole 160 Amp, 415 volt, 25 KA - 01 Nos (Make - Legrand ,HPL,Havells or equivalent)(b) MCCB 4 pole 160 Amp, 415 volt, 36 KA - 02 Nos ( Make - Legrand/ L&T/ ABB/ Schenider)(c)MCCB 4 pole 100 Amp, 415 volt, 16 KA - 02 Nos (d) MCCB 4 pole 63 Amp, 16 KA, 415 volt, - 02 Nos(e) MCB TPN 40 Amp, 415 volt, \"C\" curve - 2 Nos |
| 39 | All as per item No- 37.00, above but consisting the following items :-Incoming :-(a) Aluminium bus bar - 300 Amps rating - 03 Nos. for phases and 300 Amp rating - 01 No. for neutral(b) MCCB 4 pole 200 Amps, 415 volt, 36 KA - 01 No.( incoming) ( Make - Legrand/ L&T/ ABB/ Schenider) (c)3 phase Voltmeter (0-500V) digital type with selector switch-01 No (d)3 phase Ammeter (0-500 Amps) digital type with CT\"s of suitable ratio and selector switch - 01 No. (e) ON/OFFLED type indication lamp with toggle switch - Set of 03Out going:-(a)MCCB 4 pole 100 Amp, 415 volt, 16 KA - 02 Nos ( Make - Legrand/ L&T/ ABB/ Schenider) (b)MCCB 4 pole 63 Amp, 415 volt, 16 KA - 02 Nos ( Make - Legrand/ L&T/ ABB/ Schenider) (c) MCB TPN 40 Amp, 415 volt, \"C\" Curve - 2 Nos (Make - Legrand/ L&T/ ABB/ Schenider) |
| 40 | All as per item No- 37.00, above but consisting the following items :- Incoming (a) Aluminium bus bar - 250 Amps rating - 03 Nos. for phases and 250 Amp rating - 01 No. for neutral(b) MCCB 4- pole 160 Amps, 415 volt, 25 KA - 01 No ( incoming) ( Make - Legrand/ L&T/ ABB/ Schenider)(c)3 phase Voltmeter (0-500V) digital type with selector switch-01 No(d)3 phase Ammeter (0-500 Amps) digital type with CT\"s of suitable ratio and selector switch - 01 No. (e) ON/OFFLED type indication lamp with toggle switch - Set of 03Outgoing:-(a)MCCB 4 pole 100 Amp, 415 volt, 16 KA - 02 Nos( Make - Legrand/ L&T/ ABB/ Schenider)(b) MCCB 4 pole 63 Amp, 415 volt, 16 KA - 01 Nos ( Make - Legrand/ L&T/ ABB/ Schenider) (c) MCB TPN 40 Amp, 415 volt, -01 Nos( Make - Legrand/ L&T/ ABB/ Schenider) |
| 41 | M&L for Cutting the Existing bituminouse road for passing of UG Cable in road crossing and making good of disturbed surfaces of road to match the existing complete all as specified and directed by Engr-in-Charge. |
| 42 | Supply and fixing in repairsSteel tubes, galvanised, light grade, ISI marked 80mm bore for protection of cable under floor, road and on wall complete all as specified and directed. |
| 43 | M&L for Earthing complete with GI earth plate electrode of size 60cm X 60cm X 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using GI strip 32x6mmby means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 50mm dia GI pipe connected to main switch board or main control board and GI pipe, light grade, 20mm bore, for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type C2 (including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 metre) complete all as specified and directed and shown on plate No 5 of SSR Part-I 1991. (i) The unit rate shall include for protection pipe, GI water pipe, wire mesh, funnel, excavation, RCC pit cover, test point, 25mm x 4mm GI strip from top of earth plate upto 5 metre above ground level and if GI protection pipe is less than 5 metre, no price adjustment shall be made.(ii) RCC pit cover shall be precast of RCC 1:2:4, type B-1, 80mm thick reinforced with XPM weighing not less than 4 Kg/sqm in lieu of cast iron cover |