| 1 | Material and labour for servicing/cleaning of complete indoor and out door unit of Split Type Air conditioner / window type AC and Inverter type Split AC of capacity 2.0 TRby means of adding cleaning solution with water. The cleaning of the condensor and chiller tubes shall be done with use of nylon brushes till the scaling is removed and ensuring its serviceability by rectification / replacement of unserviceable parts and keeping AC in good working condition and specified and as directed by Engineer-in-Charge. |
| 2 | M & L for earthingcomplete with galvanized steel earth plate electrode60 x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt and connected to earth lead galvanised iron 4mm dia wire by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvd iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of2009.Note : RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmmin lieu of CI cover. |
| 3 | S&F in replacement MCCB 4 pole of capacity125 Amps AC 415 VoltsConfirms to IS/IEC 60947-2, Breaking capacity 16 KA, positive isolation, thermal magnetic release, adjustable overload 70-100%, adjustable short circuit 5-10 In Make : as per existing panel or its equivalent in Siemens/Legrand/ Schineder/ Hegar/ ABB all as specified and directed. |
| 4 | Supply and fixing 415V 10KA \"C\" curve miniature circuit breaker (MCB) TPN40 to 100 Amp of 4poles and current carrying capacity in the DB complete with connection testing and commissioning. |
| 5 | Supply only copper wire 1.5 Sqmm FRLS green/red colour single core complete all as specified and directed. Make- Anchor/Havells/Polycab |
| 6 | Supply and only copper wire 2.5 Sqmm FRLS green/red/black colour single core complete all as specified and directed.Anchor/Havells/Polycab |
| 7 | Supply & FixingPVC insulated sheathed service wiretwin core 10 Sqmm aluminium stranded conductor 1100 volts grade including taking down old unserviceable one. |
| 8 | M&L for Shifting of Split type AC/ Window type AC capacity upto 2 Ton , including submainall electrical items and drilling, making good on surfaceof PCC concreting, white cement plastering and all necessary items and transportingcomplete one location to other location in 23 Wing area and 256 SU Kaluchak area replacing unserviceable parts and handing over the machine/ equipmentin serviceable condition to the user including fixing to new location all as specified and directed by Engineer-in-Charge. |
| 9 | Supply of Labour only for attending and rectification ofcomplaints for maintenancefor Split AC/Window AC /hot & cold air conditioner/Dual inverter Air conditioners of any capacity and make installed in various locations of23 wing AF Jammu and 256 SU Kaluchak (excluding sundays and holidays) with high skilled refrigerator mechanic andhelper including detecting fault ofsplit/window air conditioner complain and servicing all unserviceable parts for split/window ac and replacement of u/s parts &repair of all necessary items and handed over to user for serviceable condition within 24 hours for minor faults and within 48 hours for major faultsall as specified and direted by Engineer In Charge.Note: (a) Contractor has to employ highly skilld Refrigerator Mechanic with helper and necessary T&P for attendingcomplaints of Ref and AC failing which recovery shall be made attwo times of quoted rate. (b) Rate quoted shall be inclusive of transport from AF Station to work shop & back shifting within permises.( c)Any partsshall be replaced and paid separately as \"supply only \" against relevant item (s) of this schedule. |
| 10 | Supply only blower motor complete suitable for window /split type AC upto 2.0 Ton as on site all as specified and directed by Engr-in-Charge. |
| 11 | Supply only outer unit condenser fan motor with fan suitable for window type AC up to 2 Ton as on site. |
| 12 | Supply only plastic airfilter suitable for Split AC Indoor unit AC upto 2 TR as on site. |
| 13 | Supply only wiring kit suitablefor split AC and window Type AC upto 2 Ton. |
| 14 | Supply only condenser fan motor complete with fan suitablefor out door unit ofsplit type Air conditioner upto 2 Ton as on site. |
| 15 | Supply only blower for indoor unitof Split AC upto 2 Ton AC as on site. |
| 16 | Supply and fix Power control Board ( PCB ) for window type /Split type ACup to 2 Ton . Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 17 | Supply and fix Power control Board ( PCB ) for split AC indoor unit dual inverter/Hot and coldAC up to 2 Ton . Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 18 | Supply and fix Power control Board ( PCB ) for split AC out door unit dual inverter/Hot and coldAC up to 2 Ton . Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 19 | Supply only Relay/Contractorsuitable for Split Type AC upto 2 Ton. |
| 20 | Supply only foaming insulator for AC suction/ cooling line,7/8\" ( Approx - length 5.9 ft). |
| 21 | Suppy and fixing suction and dischagre valvesuitablefor split Type Air conditioner out door unit as per sample. |
| 22 | Supply and fixing as in replacement ( hermetically ) uncut sealedcompressor unitrotatry type forSplit Type Air conditioner for the following capacity including gas charging: - |
| 23 | Capacity 2 TR. Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 24 | Capacity 1.5 TR. Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 25 | Material and labour for System fusing, welding, soldering,vaccumising and gas charging to Split Typeair Conditioners for the following capacity.Note-(i)Gas charging at one location will be counted and paid as one job inspite of charging it number of times at same location.(ii)Necessary T & P for gas charging of appliances for mechanic shall be arranged by the contractor at his end without any extra cost to the department. |
| 26 | Capacity 2 TR. |
| 27 | Capacity 1.5 TR. |
| 28 | Supply and fixing as in replacement ( hermetically ) uncut sealedcompressor unit reciprocating type forwindow Type Air conditioner for the following capacity including gas charging: - |
| 29 | Capacity 2 TR. Make-Kirloskar, Tecumseh, As on site. |
| 30 | Capacity 1.5 TR. Make- Kirloskar, Tecumseh, As on site. |
| 31 | Material and labour for System fusing, welding, soldering,vaccumising and gas charging to Window Typeair Conditioners for the following capacity.Note-(i)Gas charging at one location will be counted and paid as one job inspite of charging it number of times at same location.(ii)Necessary T & P for gas charging of appliances for mechanic shall be arranged by the contractor at his end without any extra cost to the department. |
| 32 | Capacity 2 TR. |
| 33 | Capacity 1.5 TR. |
| 34 | Repair to Power control Board (PCB) of inverter type/hot and cold Split type AC/Window AC for the following capacity: - |
| 35 | Capacity 2 TR. Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 36 | Capacity 1.5 TR. Make- Voltas/ Bluestar/ LG/ Samsung/ As on site. |
| 37 | S & F By Flushing to walls MCB distribution board double door240volts 2 way making good to disturbed surfaces of floors walls including taking down the old DBs etc. Make- Legrand/Havells/L&T/Indoasian |
| 38 | S&F MCB SPN upto 32 Amps, 240 Volts completeincluding taking down old unserviceable .Make-Legrand/Havells/Indoasian |
| 39 | Supply forindustrial type metal socket enclosure with 240 volt MCB 20 Amps, withmetal plug top complete all as specified . Make ABB/Legrand/ L&T/Havells |
| 40 | Supply & FixingPVC insulated sheathed service wiretwin core 06 Sqmm aluminium stranded conductor 1100 volts grade incl taking down old unserviceable one. |
| 41 | S&F copper pipe 5/8\" and removing old u/s copper pipe complete all as specified and directed by Engineer-in-charge. |
| 42 | S&F copper pipe 1/4\" and removing old u/s copper pipe complete all as specified and directed by Engineer-in-charge. |
| 43 | Supply only thefollowingcapacitors to incorporate against repairable summer appliances Window / Split Type AC\"s : - |
| 44 | Running capacitor45 MFD. Make- Epcos. |
| 45 | Running capacitor 50 MFD. Make- Epcos. |
| 46 | Running capacitor 4 MFD. Make- Epcos , Havells. |
| 47 | Running capacitor 6 MFD. Make- Epcos , Havells. |
| 48 | Running capacitor 10 /15 MFD. Make- Epcos , Havells. |
| 49 | Starting capacitor 100 / 120 MFDcapacity Make- Tesla, Chezco slvika, Epcos. |
| 50 | M&L for sub main wiring with two run of6.00 sqmm single core multi stranded PVC insulated and unsheathed copper conductor(red for phase and black for neutral) of grade 1100 volt FRLS cable in and including electrical grade PVC conduitsof desired colour not less than 1.2 mm thick and of 25 mm dia& 6.00 sqmm copper conductor cable PVC unsheathed green coloured for earthing with complete accessories duly connected with earth dolly complete all as specified and as directed incl taking down old unserviceable one.(Note : Two runs of copper cable, one run of earth wire, one run of PVC conduit shall be measured as one unit.) Make of wire-- Finolex/Havells/Plaza. |
| 51 | M&L for sub main wiring with two run of 4.00 sqmm single core multi stranded PVC insulated and unsheathed copper conductor (red for phase and black for neutral) of grade 1100 volt FRLS cable in and includingincluding PVC cassing capping with fitting and accessories & 4.00 sqmm copper conductor cable PVC unsheathed green coloured for earthing with complete accessories duly connected with earth dolly complete all as specified and as directed incl taking down old unserviceable one.(Note : Two runs of copper cable, one run of earth wire, one run of PVC casing caping shall be measured as one unit.) Make of wire-- Finolex/Havells/Plaza. |
| 52 | Supply and fixing Switch socket combination two in onemultipurpose suitable for 3 pin 5 amp and 16 amp flush type universal, fixed in repairs, complete all as specified. |
| 53 | Supply and fixing Plug top 15 Amps capacity, fixed in repairs complete all as specified and as directed. |
| 54 | Supply and fixing Plug top 5 Amps capacity fixed in repairs complete all as specified and as directed. |
| 55 | Rewinding transformer of voltage stabalizer of capacity 03 KVA with existing guage copper winding of capacity range 90 to 280 Volts complete all as specified and as directed. |
| 56 | Rewinding transformer of voltage stabalizer of capacity 05 KVA with existing guage copper winding of capacity range 90 to 280 Volts complete all as specified and as directed. |
| 57 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 130 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA. |
| 58 | Material and labour for System fusing, welding, soldering,vaccumising and gas charging to refrigerator of following capacities: -Note :- Refrigerant gas for charging of equipment compressor shall be provided by the firm and cost thereof shall deemed to be included in the unit rate quoted against this Item. |
| 59 | Capacity 170 Ltrs. |
| 60 | Capacity 285 to 310 Ltrs. |
| 61 | Supply and fixing as in replacement hermetically sealedcompressor unitfor refrigerator: - |
| 62 | Capacity 170 Ltrs. Make- Godrej/GMCC/Blue star. |
| 63 | Capacity 280/310Ltrs. Make- Godrej/GMCC/Blue star. |
| 64 | Supply and fix wall mounted stand for mounting of outer unit of split ac made of heavy duty GI Steel of size upto 2.0 Ton with angle height 450 mm and bracket length 485 mm complete all as specified and directed. |
| 65 | Supply and fix 5 metre transparent drain pipe for split ac and window ac leak resistant all as specified and directed. |
| 66 | Supply & fixing in replacement of indoor type unit split Air conditioner electric driven single phase 220 volts of cap upto 2.0 TRCold type complete with all accessories as per existing make and model. |
| 67 | SCHEDULE \"A\" PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch \"A\" Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder. |