| 1 | Excavation in trenches / foundation in soft / loose soil not exc. 1.5 metre wide and n\"exc. 1.5 m deep for HT / LT underground cable / pole foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed. |
| 2 | Returningfilling of excavated soil after laying the cable with spreading leveling watering and wellramming in layers not exceeding 25cm thick in loose/soft soil complete all as specified and directed. |
| 3 | Removal of surplus soil/excavated material obtained from ground level to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above from the starting point complete all as specified and directed. |
| 4 | M&L for sand cushning to U/G cable in layers of 23cm thick (8 Cm before laying the cable and 15 cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and directed. Note: Only punned thickness 18 cm shall be measured and paid. |
| 5 | Supply and laying reinforced precast concrete cable cover class HVP type 1 with peak size 300mm x 180mm x 40mm in trenches for protection to under ground cable complete all as specified and directed. |
| 6 | M&L for Sub class ‘B’ bricks old size. laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required complete all as specified and directed. |
| 7 | M&L for drilling manually in soft/loose/ hard soil under road, pavement hard standing for protection of GI pipe up to 80mm dia complete all as specified and directed. Note Depth of bore shall not be more than 1 Mtr from ground level. |
| 8 | Supply & layingin replacement of GI tubing of 80 mm boredia, light grade conforming to IS 1239- Part-I and ISI marked in trenches, across the road, on wall or pole incl fixing arrangement as directed, culvert etc of required length for cable protection complete all as specified and directed. |
| 9 | Dismantling & taking down old, deteriorated, switch air break and S &F with new 33 kV Isolator Double Stack, Horizontal Type, 400 Amp, each pole consist of galvanised steel base, H.T. insulators as per IS, non ferrous knife and spring loaded contact, arcing horns of adequate section to break the magnetizing current, including horizontal G.I. pipe adequate length for phase separation, adequate length of G.I. pipe of 32 mm for operation from ground level and operating handle complete in both OFF and ON position, jumpers with suitable conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontally mounting, suppliedand fixed in repairs, complete all as specified and directed. |
| 10 | M&L for dot matrix rectangle LED Screen in size 5 feet X 3 feet with display technology dot matrix, laungage supportedenglish/hindi, Lighting type LED physical pixel-6mm,brightness-6500 nits, body material die cast, life span -100000 hours,refresh rate 2000hz for display of installation details with max 50 letters display on board complete all as specified and directed. Note-1. Electric Connection of display panel board shall be deemed to be included in quoted unit rate.2. Fixing of panel board with proper arrangement shall be deemed to be included in quoted unit rate. |
| 11 | S&F Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc.. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg eachincluding necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces, suppliedand fixed in repair complete all as specified and directed.(Note: - (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed by the Engineer-in-Charge.(ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only.Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account.)Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each to be measured under \"Structural Steel\") |
| 12 | M&L for advance maintenance free chemical earthingwith JMV CBE 403 enviornment friendly ring earthing system consisting each set of 03 (three) Nos of 10 (ten) feet length 40 mm dia earth eletrode made out by copper, maintenance free electrolytic grade copper earthing system of JMV make based on flat in pipe technology of 3 Mtrs length , 40 mm dia with crystalite conductive mixture COMPOUND filled withthe permanent sealings at the top & bottom with the leadterminal / strip in25x4 mm size copper with 2 holes of 10 mm dia at the top , to be lowered in 150 mm dia bore including filling of back fill ecofriendly earth enhancing compound tested by ROHS comply to IEC 62651-7 which should have passed leaching ,corrosion, supphur & resistivity test as per IEC 62651-7 by NABL accredit LAB/JAM plus compound in 150 mm bore in immediate contract around the earth electrode and top of the bore shall be finished with 40 mm thick PCC in 1:2:4 type B 1 over 75 mm thick PCC in 1:4:8 type D-2 and backfilly/ JAM compound shall be covererd with FRP pit cover of suitable size for each earth electrode, joint to be made by JAM weld exothermically welded technology including copper strip size 32 x 6 mm for earthing ring system and copper strip 32x6 mm size for earthing electrode to test point with saddles & porcelain insulators suitable size on wall ,earth strip protected by light grade GI pipe 40 mm dia in case of plinth protection / floor/ hard standing crossing complete all as specified and directed. Make - JMV LPS Limited / JEF/ ALCOICE / Conducrete Note :- Earth work , PCC work,PCC cutting work by cutter, earth chamber in suitable size with testing on suitable valueetc rate shall deemed to be included in quoted rate |
| 13 | Supply in replacement toPVC insulated muiltistandard 3 core 1.5 Sqmmflexible copper conductor cable for making connection complete all as specified and directed. |
| 14 | Supply in replacement toPVC insulated muiltistandard 3 core 1.0 Sqmmflexible copper conductor cable for making connection complete all as specified and directed. |
| 15 | Supply in replacement toPVC insulated muiltistandard 3 core 2.5 Sqmmflexible copper conductor cable for making connection complete all as specified and directed. |
| 16 | Supplyin replacement toInsulation tap in length 18 Mtr with 2 Inches width suitable for 440 working voltage ISI marked complete all as specified and directed. |
| 17 | Supply & fixing PVC insulatedsheathed aluminium conductor armoured cable with inner sheathing for service connection size 10 Sqmm 2 core 1100 Volt complete all as specified and directed. |
| 18 | Supply & fixing PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 6 Sqmm 2 core 1100 Volt complete all as specified and directed. |
| 19 | Supply and laying to wall or poles or fixing or passing through pipe, in replacement of 1100 volts grade heavy duty cable with XLPE insulated aluminium multistranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall PVC sheathed16 sqmm nominal cross section 4 core in service connections complete all as specified and directed. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification) |
| 20 | Supply and laying in trenches or fixing to wall/pole or passing through pipe in replacement of XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 25 Sqmm 3.5 core complete all as specified and directed. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification) |
| 21 | All as per item No 20.00 above but cable of size 35 Sqmm 3.5 core complete all as specified and directed. |
| 22 | All as per item No 20.00 above but cable of size 50 Sqmm 3.5 core complete all as specified and directed. |
| 23 | All as per item No 20.00 above but cable of size 70 Sqmm 3.5 core complete all as specified and directed. |
| 24 | All as per item No 20.00 above but cable of size 95 Sqmm 3.5 core complete all as specified and directed. |
| 25 | All as per item No 20.00 above but cable of size 120 Sqmm 3.5 core complete all as specified and directed. |
| 26 | Supply, laying in trenches or passing through pipe/ducts, fixed to wall or poles XLPE insulated screened PVC sheathed galvanized steel strip or wire armoured electric power cable with alumn conductor of cross sectional area 95 Sqmm 3 core 11 KV rated suitable for earthed system including testing and commissioning complete all as specified and directed. Note : (Excavation and earth work, sand cushioning brick covers and GI pipe etc shall be measured and paid separately. |
| 27 | All as per item No 26.00 above but HT 11 KV cable of size 120 Sqmm complete all as specified and directed. |
| 28 | All as per item No 26.00 above but HT 11 KV cable of size 185 Sqmm complete all as specified and directed. |
| 29 | Supply and fix cable end jointing kit for 11 KV (Earthed)grade cable for indoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm complete all as specified and directed. |
| 30 | Supply and fix cable end jointing kit for 11 KV(Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 31 | Supply and fix cable straight through jointing kit for 11 KV(Earthed) grade cable termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm complete all as specified and directed. |
| 32 | Supply and fix cable straight through jointing kit for 11 KV grade cable termination heat shrink type joint complete with jointing material and all accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 33 | M&L for earthing complete with GIplate electrode of size 60cm X 60cm X 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including GI strip of size 32x6 mm up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of brass and protected by light grade 40mm dia upto 7.5 mtr long GI pipe connected to main controlboard and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover 50mm thick and PCC chamber pit with PCC 1:2:4 type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 including taking down old unserviceable and making test point and all connections complete all as specified and directed. |
| 34 | S&F in replacement of HT 11 KV bus bar outdoor type weather and vermin proof factory fabricated CPRI approved duly painted with two coat of enamelled paint, pedestal type made out of mild steel sheet 3.15mm thick, factory made,using angle iron 40mm x 40mm x 6mm and 500mm high, front opening double shutter weather proof , rust proof, dust proof with provision of rubber gasket and locking arrangement including HT bush, insulator & bus bar color code - 03 Nos and making connection with suitable size of thimbles, nuts, bolts and washers etc incl necessary earth work complete all as specified and directed. |
| 35 | Removing the cover of cable duct for removal of unwanted vegetation/bushes/small plants/ shrubs/soil from cable duct not exc 3\" wide and 3\" deep at 33 KV sub station and removing the excavated material to a distance exceeding 50 M and placing the cover after completion complete all as specified and directed. |
| 36 | Removal coarse aggregate of any size from MES installation and segregate/removal of vegetation/ bushes/ small plants/ shrubs etc and after that spreading in the same location incl levelling and removing the vegetation/ bushes/ small plants/ shrubs to a distance exceeding 50 M complete all as specified and directed. |
| 37 | M&L for coarse aggregate not less than 40 mm graded nominal size without any vegetation or chemical incl levelling spreading all around complete all as specified and directed. |
| 38 | M&L for cement concrete type B2 in ratio 1:2:4 (using 40 MM graded stone aggregate) as in foundation filling and mass concrete complete all as specified and directed. |
| 39 | M&L for cement concrete type C2 in ratio 1:2:4 (using 20 MM graded stone aggregate) as in foundation filling and mass concrete complete all as specified and directed. |
| 40 | Unbinding from insulators ACSR conductor any size of HT 33 KV sub station and S&F new ACSR conductor withsilicon rubberof thickness 3 mmsleevecolour code of Red ,yellow and blue andachieve proper sag and rewinding to the insulators using proper connectors/clamp and making all existing cable connections complete all as specified and directed. |
| 41 | M&L for RCC Nominal Mix 1:2:4 type B2 (using 12.5 mm coarse aggregate) forCover of cable ductof size 1.5 ft width 3 ft length and 50 mm thickness using 10 mm steel reinforcement bar with 125x 125 mm distance of reinfocement on double side and 40x40x5mm angle on top edge of cover complete all as specified and directed. Note- Rate of panting of cover shuold be included in quoted unit rate. |
| 42 | Supply & Fix 33 Kv Outdoor VCB, 1600A, 31.5 kA with CB Structure with motorized (230V AC), closing & tripping coil 24 V DC33 KV single feeder control & relay panel, Motor 230V AC(Aux. Supply 24DC),Loca;l/Remote Seelector switch,Panel illumination lamp LED,Toggle switch for heater and Socket,Space heater with rating 80W 230 VAC complete all as specified & directed.Note:- Technical specification1.Rated Voltage:- 33 KV 2.Maximum (continuous ) Rated Service voltage:- 36 KV 3. Nominal current rating 4. Under normal conditions :- 1600 A5. Under site conditions specified :- 1600 A ,6. Short time current rating 3seconds(rms) :- 31.5kA 7. Maximum temperature rise over ambient :- Within limits of IS-13118/1991 , 6. Breaking Capacity (Rupturing Capacity) 7. Symmetrical :- 25kA 8. Symmetrical at rated service voltage :- 1000 MVA 9. Making capacity :- 62.5KAp 10. Total break time 11. At 10% rated interrupting capacity :- 80ms max 12. At rated interrupting capacity :-100ms max 13. Arcing time :-20 msMake time:- 100 ms 14. Minimum reclosing time at full rated nterruption from instant of trip coil enerzisation :- 400 ms 15. Shunt Trip- 24 VDC, Closing coil-24 VDC |
| 43 | M&L for complete removal of existing treatment mechanically with electric paint remover dry wall sander machine and preparation ofof walls and applying two coat of exterior weather proof anti algae paint over a coat of primer. The paint will be applied through aireless spray techonology with max working pressure of 3300 PSI by Trucare Graco machine / Airless paint sprayer (Vands Engineering solutions) / Airless sprayer machine Surya 9 (Jaguar) / Control Pro 190 Air paint sprayer (Wagner) and capable of operational single spray gun with a maximum materials hose length 150m working, complete all as specified and directed. |
| 44 | M&L for lightening arrestor non linear resistor type confirming to Fe 410 W (gde -E-250) quality \"A\" complete line discharge class 3 nominal discharge current 10 KA station class & high discharge with stand 100 KA assembly suitable for 33 KV working pressureand mounted on hot dip galvanised steel structure including all clamp nuts bolt and washers etc connecting to earth 32 x 6 MM GI strip including taking out the same complete all as specified and directed. Note:- MS channel and angle shall be measured and paid seperately. |
| 45 | S&F LED board of size 15\"X3\"X4\"\" (L x W x H)made out of 24 guage GI sheet and front with acrylic sheet total enclosed with computerised letter writings of size not less than 100 mm as decided by Engr-in-charge and inside with 4*20w LED tube lightcomplete with time control switch , MCB and battery back up with timer and synchronised motor board should be fix on 40mm dia medium grade GI pipe of 5\" height board from Bldg roof ( 3\" from the bottom of the board ,3\" depth of the board and 1\" embedded in PCC above Bldg roof),fixed in PCC 1:2:4 type B-1 using 20mm graded agg of size 450*450*600mm with complete wiring of 2 sqmm 3 core copper sheathed cable 10 meter long including service connection from the Bldg main DB by means of 25mm dia light grade pipe to the board. The cable inside theboard shall run in PVC reinforced flexible conduit including PCC work for fixing of board on Bldg roof. The details to be written with computerised writing including taking down of old unsv board complete all as specified and directed. |
| 46 | Supply and fixing glow sign board (box type) of size 1500 mm x 1200 mm x 200 mm cladding PGI sheet 18 gauge fixed on aluminium angle of size 25 mm x 25 mm x 3.00 mm on top/bottom both side and transfrant acrylic sheet 3.00 mm in front on which lay out of station HT electrical equipment and cables to be marked with different colours as directed complete with 4*20w LED tube light with wiring of 1.00 sqmm 3 core copper sheathed cable 10 meter long including service connection from the Bldg main DB by means of 25mm dia light grade pipe to the board complete all as specified and directed. |
| 47 | Material and labour for perodical servicing ,repairing & testing of33 KV outdoor SF6 circuit breaker including relay and control panelof capacity 1600 Amps andrating 36 KV complete all as specified and directed as details mentioned as under:-(a) Details of periodical servicing of breaker :-(i) Checking of Closing/Tripping coil assembly(ii) Adjustment of mechanism if required.(iii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter andinsulating materials shall be wiped with a clean cloth.(iv) Checking the contact for wear. Replace if the contact piece has worn out.(v) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.(vi) Check for rust and wear.(vii) Checking of spring charge mechanism(viii) Visual check for rust and deformation.(ix) Check for loosened bolts and nuts, broken spring washers and snap pins etc.(x) Check for loosened connections, rust, damaged lead wires.(xi) Checking of control circuit & tighten the connections if any.(xii) Check close & trip coil.(xiii) Replacement of Dashpot/shock absorbers .(xiv) Replacement ofcarbon brush of spring charging motor(xv)Cleaning ofporcelain bushing(xvi)Checking of limit switch |
| 48 | (b) The following test shall be carried out:-(i) Primary Injection Test of outdoor CT / PT(ii) Closing & Opening Timing Test for all three poles.(iii) IR Test with megger in open and closed condition.(iv) Contact resistance test for all three poles(v) Testing VCB bottle(vi) Closing coil resistance(vii) Tripping coil resistance.(viii) High voltage test.(ix)Testing of Over current and earth fault numeriacal relay of control panelwith Secondary Injection Kit, checking,programming & coordination of relay as directed by Engr-in-Charge.(x) Testing of auxilary relays such as DC Supply supervision relay, Master trip relay ,Buchholzrelay , WTI relay, OTI relay & etc.Note- . The rates for Nuts, bolts, washers, lugs, thimble, wires and minoritems required for efficient and smooth functioning of the equipment shall deemed to be included in in the quoted item.Rates for testing equipments and accessories required at site for condcuting above tests shall deemed to be included in quoted rates by contractor. |
| 49 | Supply and fixing SF6 circuit breaker motor 200 watt, 220-250 V, AC-DC, 50 Hz as per existing make and model complete all as specified and directed. |
| 50 | M&L XLPE insulated, Heavy duty, Galvanised steel strip or wire Armoured, stranded copper conductor Electric LT cable, 1100 Volts grade, cross sectional area 1.5 Sqmm 8 core complete with all connection and taking out old unsv cable complete all as specified and directed. |
| 51 | Supply, laid in trench/ fixed with surface of wall / roof etc, jointing, thembling and glanding in suitable size, testing in replacement toHT XLPE cable insulated, screened, PVC bedded galvanised steel strip or wire armored electric power cable (heavy duty) with alumunium conductor 33 KV, grade cross section area 300 Sqmm of 3 core complete all as specified and directed.Note : Excavation earth work cable cover, sand cushioning etc shall be measured and paid separately under respective items) |
| 52 | M&L paintingto steel prepared surfaces of any width or girth not otherwise described by using synthetic enamel paint in two coats (one as finishing coat) over one coat of red oxide zinc chromeprimer on surface of steel structure /girder/ angle frame/ wire mesh fencingetc in any description at E/M installation using paint spray gun on specified working pressure including sign making / marking withusing different colour in given size of letter etc complete all as specified and directed. Note- Paint colour & shade including writing marking of letters etc shall be deemed included in quoted unit rate and the same shall be approved by Engr-in-charge Make:Asian/ Berger/ Dulex or equivalent. |
| 53 | M&L Painting to existedPTs/ CTs /GOD/run of ACSR etc of 3 three phase distribution bay/ network of 33 KV yard from end terminating point to transformer HT leg/ studs using luminious paint for phase indication in colour coading (Red, blue and yellow) phase wise in two coats over one coat of red primerincluding cleaning /prepration/ removing etc to old paint on external surfaces of existed located protection equipements as above and marking as per given by Deptt complete all as specified and as directed. Note :Quoted rate shall be including the cost of painting to external surface of PTs/ CTs/ control panel in existed colour complete. |
| 54 | Supply & fixing self adhesive PVC insulation tape suitable for 11 KV, 25.1 MM x 9.1 Mtrs x 0.305 MM for HT Scotch-70 complete all as specified and directed. |
| 55 | Supply & fixingscotch Rubber mastic tape 2228, 2\" (50 MM minimum) width and 10 feet in length suitable for 11 KV complete all as specified and directed. |
| 56 | Supply and fixing in replacement to cabin assemblyof silica gel suitable for step down transformer 11/ 0.440 capacity upto 630 KVA including excess water storage bottol, clamp including silicazel filled etc in existing make model sepcification in all complete all as specified and directed. Note : Quoted rates shall be including the cost of silicalgel intially filling. |
| 57 | Detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as one Job either machine placed from one side or both side of the cable. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be measured and paid seperately. 4. Material for repair and replacement measured and paid saperately. 5. One job shall be measured if the fault has successfully identified by the fault locator machine or removing moisture in the cable if required. |