| 1 | Supply , Install, testing & commissioning Non-clog sewage submersible pump set,eletric driven with supply voltage 415 volts, 3 phase, 50Hz ,18 to 20 M Head ,Discharge 1200 LPM 1450 RPM,H class insulation,CI FG 260 impeller,CI casing,CI motor parts connected with suction and delivery water line making electric connections complete includingmaterial and labourfor common Header of size 150 mm Dia MS pipe High grade ISI marked of length not less than 2.5 meter on pcc foundation, including necessary cutting,welding or making flanges for connection of Valves/pipe is included in this item and nothing extra will be paid on this account. |
| 2 | Supply and fix including lowering of polypropelene rope 16 mm dia virigin qualityISI marked,tested with test certificate, heavy duty grade all as per directed by Engr-in charge. |
| 3 | Supply and Laying PVC insulated, flat submersible cable sheathed,copper cable 1100 V ,3 core 10 sqmmcomplete all as specified and directed. |
| 4 | M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.8m below normal ground level connected to and including galvanised iron or steel earth strip 32X6 mmby means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing wire protected by galvanised iron or steel pipe 50mm bore medium grade and connected to continuous earth wire on pole/ test point.Watering pipe shall be 20mm bore GI medium grade. The earthing shall be inclusive ofexcavation and earth work in any type of soil,charcoal, salt,funnel , PCC pit and RCC cover complete all as specified & directed. Note 1- Following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labourfor connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust and common salt as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. |
| 5 | Supply,Fix and lowering of HDPE (high density polyethylene) pipe,PE-80 grade, ISI marked, as per IS 4984, PN-16, outer dia of nominal size 4\" and wall thickness at end being 15.2 mm to 16.9 mm suitable for bore wells , incl providing suitable size flanged and SS nipple for fixing with submersible pump sets and delivery mains complete all as specified and directed. |
| 6 | S&F of Non Return Valve class PN 1.6 of size 100 mm with cast iron body and both ends flanged,IS-5312 marked complete with neoprene rubber gasket,jointing material and incl nuts/bolts/washer of suitable size etc complete all as specified and directed. |
| 7 | S&F cast iron sluice valve with flanged ends class I PN-1.6 of size 100mm dia heavyduty ISI marked, drilled type, non raising type : IS- 14846 mark, including iron wheel complete with suitable rubber insertion 3.0mm thick at both ends with suitable MS bolts, nuts and washers etc complete all as specified and directed. |
| 8 | Supply, testing and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof, vermin proof, astehically designed, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar having size 40 mm x 6 mm cross sectional area, insulated color sleeves, epoxy insulators, rail channels cable alloy, danger notice board including provision of angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground and 60 cm above GL duly painted including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated of approved color connecting incoming MCCB/Changover connection withcopper strip & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete.The panel shall be comprising of the following:- |
| 9 | INCOMING(a) MCCB 4 POLE 415 V 100 A (16 KA) ,4 pole with adjustable thermal setting-01 No.OUTGOING(a) MCCB 4 POLE 415 V 63 A (16 KA) ,4 pole with adjustable thermal setting-02 No.(b) TPN MCB 40 A \"C\" type-01 No(d) Fully automatic star delta starter for non clog submersible pump of capacity 10 HP,3Phase 415 Volt with suitable size contactor and timer of-02 No(e) Single phase preventer - 01 No(f)Auto phase sequence corrector-01 No(g) Power factor correction capacitor,15KVAR(5 KVARx3),3Ph including APFC relay 3 step-01 No with suitable size of contactors.INDICATING DEVICES(i) Digital voltameter with selector switch 0-500 Volts - 01 No(ii)Digital Ammeter with selector switch 0-500 Volts - 01 No(iii)LED inicating lamp with holder for main supply indicating RYB (set of three) - 01 Set(iv)Indication lamp for starter power ON/OFF - 02 Nos |
| 10 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 Core |
| 11 | M&L for excavating in trenches n. exc 1.5m wide for laying of cables foundation not exceeding 10 Sqm area on plan and not exceeding 1.5 meters in depth and getting out in soft/loose soil. |
| 12 | M&L for removing excavated material n.exc 50m and deposting where directed at a level n.exc 1.5 m above the starting point. |
| 13 | M&L for returning filling in including spreading, levelling, watering and well ramming in layers not exc 25cm. |
| 14 | Supply,spreading and filling of clean river sand spreading leveling in layers not exceeding 25 cm thick as cushioning to LT UG cable complete all as directed by Engineer-in-Charge.(NOTE : Punned thickness of dry sand will be measured and paid) |
| 15 | Supply and laying un-reinforced precast concrete cable, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete |
| 16 | Surfaces excavation n.exc (not exceeding) 30cm deep and averaging 15cm deep and getting out of hard / dense soil. |
| 17 | Excavation inpost holes (or similar holes) inhard dense soil, each n exc 0.50 cum , getting out returning,filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25 cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface. |
| 18 | Earth work in excavation by mechanical means (Hydraulic excavator) means over areas in any kind of soil (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5m, as directed by Engineer-incharge. |
| 19 | All as per item No 18 above but exceeding 1.5 mtr depth but not exceeding 3.00 mtr depth complete all as specified and as directed by Engineer-in-Charage. |
| 20 | All as per item No 18 above but exceeding 3.0 mtr depth but not exceeding 4.50 mtr depth complete all as specified and as directed by Engineer-in-Charage. |
| 21 | M&L for cement concrete (1:3:6) type C2 (using 40mm graded stone aggregate) as foundation, filling and mass concrete all as specified & directed. |
| 22 | Using and waste of Form work to sides of concrete foundation, footings, base of columns, rafts and raft beams, sides and soffits (if any) of foundation and plinth beams etc for rough finished curved surfaces complete all as specified and directed. |
| 23 | M & L for RCC M-30 (Design Mix) in foundation including rafts, footing, foundation beams, plinth beams, bases for column etc basement slab and mass concrete complete all as specified and directed |
| 24 | Use and waste of Form work to sides of wall/retaining wall or to batter for rough finished curved surfaces complete all as specified and directed. |
| 25 | M&L for RCC M-30 (Design Mix) as in wall/retaining wall complete all as specified and directed. |
| 26 | Form work to soffits of roof slabs, floor slabs, landings etc & similar work n. exc 200mm thickwith fair finished curved surfaces of concrete horizontal or sloping. |
| 27 | Formwork to edges of concrete flats, treads, breaks in floors, window cills, concrete railings, openings in concrete walls, floor and roofs n exc 20 cm wide and sides of RCC/ PCC bands in walls, horizontal or sloping and similar work exc 10cm but n exc 20cm wide |
| 28 | M&L, RCC M-30 ( Design mix) using 20mm graded aggr in roof slab, landings etc |
| 29 | Form work to sides of pillars, post, struts, columns etc with rough finished surfaces of concrete of square, rectangular or polygonal with fair finished surface. |
| 30 | M&L RCC M-30 (Design mix ) in columns, pillars, piers, posts and struts. |
| 31 | S&F Mild Steel CRS bars 10mm dia and over, cut to length, bent to shape required, including cranking , bending, hooking etc and binding with MS wire 0.9mm dia(annealed). |
| 32 | S&F mild steel CRS bar 6mm to 8mm dia ,cut to length, bent to shape reqd including cranking, bending , hooking ends and binding with mild steel wire (annealed) not less than 0.9mm dia |
| 33 | S&F mild steel CRS bar 5mm to over upto 10mm dia in stirrups ,cut to length, bent to shape reqd including cranking, bending , hooking ends and binding with mild steel wire (annealed) not less than 0.9mm dia. |
| 34 | S&F 150mm wide PVC water bar in RCC wall. |
| 35 | S&F of PVC ultra drain,SelFit pipes, single socketed, ISI marked, IS-13592 type \"B\" in any length, jointed with solvent cement fixed in walls and floors of 110mm dia size. |
| 36 | Cleaning of septic tank and soak pit of any capacity & any size by taking out sludge and sludge loading to the cart/ lorry & depositing out side MD land including bailing out foul water by manually or by any mechanical means in tanker and dispose the waste water out side MD land and all as specified and directed by Engr-in-Charge.Note:-(i)Rate quoted includes bailing out water from septic tank upto 2/3 depth of tanks and removing sludge.(ii) The measurements for sludge upto depth of 1/3 of septic tank shall only be recorded for payment purpose. |
| 37 | Removing excavated material exc 500m and n.exc 1.5Km depositing where directed at a level n exc 1.5m above the starting point. |
| 38 | Cutting into existing manhole/Septic tank for connecting new drains of 150mm/200mm internal dia, making good to pipe and rendering, cutting out existing benching for and forming branch channel ( ½ roundor3/4Section) in cement concrete 1:2:4 type B-1 smooth finished and reforming benching as required. |
| 39 | M&L for cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in bed to drain pipes of size 200 mm bore, including packing under & haunching against the sides of pipes after they are laid and tested. |
| 40 | S&F Reinforced concrete pipes 200 mm dia, class NP2including collars laid in trenches and jointed with CM 1:1 complete all as specified and directed. |
| 41 | M&L for precast reinforced cement concrete 1:2:4 type B1 using 20 mm graded stone aggregate in landings, cover slabs (for manholes etc.) chullah hoods, chajjas, shelves and similar articles with plain faces, set in CM 1:4, including necessary form work moulds etc all as specified. (Reinforcement shall be measured and paid for separately). |
| 42 | M&L for Precast PCC block masonry in 1:3:6 with solid blocks, exc 10 cm in width and setting in cm 1:6 complete all as specified & directed |
| 43 | M&L for rendering 5mm thick cement plaster on concrete surface of walls in cement mortar (1:3) finished even and smooth without using extra cementcomplete all as specified and directed.. |
| 44 | M&L for rendering 15 mm thick in CM 1:4 on block masonry surfaces finished even and smooth without using extra cement. |
| 45 | M&L for two coat of exterior emulsion paint in camofaluge pattern over one coat of primer on external surfaces |
| 46 | M&L for PCC 1:3:6 Type C2(40 mm graded stone aggregate) in post, foundation, filling and mass concrete complete all as specified and as directed by Engr-in-Charge. |
| 47 | M&L for Steel work in tubular trusses including special shaped washer etc. complete usingERW or induction butt welded tubes conforming to I. S.1161-1979 grade St.-240 |
| 48 | S&F rolled mild steelfor Roof trusses (framed), trussed,purlins, crane gantries, rails andfastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc |
| 49 | S & F for Plates (plain ) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted,bolted or welded attachment, Fe 410-W (Gde-E-250) quality-A,flat iron, etc with ornamental and intricate design complete all as spd and directed. |
| 50 | S & F for Mild steel screw bolts ( Machine made) with hexagonal or square heads at one end and screws the other or screwed both ends. each screwed and to be fitted with washers and one hexagonal or square nut length at bolt exceeding 5 cm but not exceeding 10 cm long for 16 to 20mm dia of neck complete. |
| 51 | M&L preparing New Steel or Iron Surfaces of any description, over 10 Cm width or girth and applying twoCoats of Synthetic Enamel Paint (First quality) over a coat of red oxideprimer complete all as specified and as directed. |
| 52 | S & F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering, fixed with self tapping screws as specified etc complete all as specified. |
| 53 | S&F for chain pulley block with triple gear arrangement lifting hook, load chain & hand chain & locking device etc.Capacity: 1 Ton, Span: as per site condition, Lift: as per site condition. |
| 54 | Cutting holes into or through brick wall built in cement mortar and making good in cement mortar 1:3 or cement concrete 1:2:4 type B1 not exceeding 150 Sq CM as required complete all as specified and as directed. |
| 55 | M& L for D.I.K-9 grade 100 mm dia pipes within side and outside epoxy paint including Ductile Iron Flange socket spigot bends,tees,reducers or any other specials required, all taxes, insurance, transportation, freight charges, octroi,inspection charges, loading, unloading, conveyance to departmental stores,stacking etc.complete.. |
| 56 | M& L for Morrumin beddinglaid in layers n exc. 15 cm thick, spread, levelled and rammed including wateringincl. ramming, watering, levelling, consolidating etc. Complete as per standard and instruction of engineer incharge. |
| 57 | Connection charges for connecting the DI sewage pipeline from UG sump to existing manhole of Gujarat Municipal Corporation outside boundary wall near P-91. |
| 58 | Rolling and consolidating formation surfaces in cutting using power roller exc 8 tonne but n exc 12 tonne |
| 59 | M & L hardcore of gauge n exc 63mm, deposited spread and levelled in layers n exc 15cm thick, watered and rammed to a true surface broken stone or boulders |
| 60 | M & L PCC 1:3:6 type C2 using 40mm graded aggregates as in sub-base 100 mm thick. |
| 61 | M & L PCC 1:2:4 type B1 using 20mm graded aggregates as in flooring100 mm thick. |
| 62 | M&L for forming Contraction (Dummy) joints 30mm deep x 10mm wide,filled with sealing compound Grade B. |
| 63 | Supply, installation, testing and comissioning of cooling split type inverter air conditioner 2 tonne cold type (indoor/outdoor unitcomplete) with star rating 5 (BEE/ ISEER rating not less than 4.85) copper condenser cordless remote control unit and within built air ioniser and plazma filter for better indoor air quality with stand for outdoor unit,230 Volt , 50Hz ,1Phasecomplete all as per direction of Engg-in-charge or equivalent model Diakin/Mitsubishi/O-Gernal/Hitachi/Samsung.Note :- Copper pipe, insulation material, PVC clamps,outdoor unit stand and water pipe for condensate not more than 10 meter as per requirement will be arranged by the contractor and the cost of the same shall be deemed to be included in the unit quoted rates. |
| 64 | S&F Voltage stablizer for automatic operation single phase naturally air cooled indoor type and designed for input variatiion between 140 volts to 270 volts with output voltage stabilized at 230 volts with accuracy of+/- 2.5% of capacity 5 KVA. |
| 65 | S&F Sub main wiring with two single core cable PVCinsulated unsheathed of copper multi stranded conductor FRLS cable of size4 sqmm, 1100 votls grade drawing through and includingcaping casing medium duty including acessories such as Tee, bend, Elbow etc, ISI marked with and including PVC insulated 4 sqmm unsheathed multistranded FRLS copper conductor cable for earth continuity and connected to common earth dolly including cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed by Engineer-in-charge. Note:- (i)Two lengths of 4 Sqmm cable, one length of 4 Sqmm cable and one length of PVC caping casing conduit will be measured as one length. |
| 66 | M&L for point wiring for one light point controlled by one, one way switch with 1.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor FRLS cable 1100 Volt grade including 1.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor FRLS cable 1100 Volt grade as continuous earth wire in green colour to common earth and connected to earth dolly laid/drawn into and includingPVC rigid non metallic caping casing suitable size as per IS medium grade (ISI marked) with all fittings such as tees, bends etcincluding sunk type modular pressed steel box covered with modular cover plate and frame for housing switch, socket , fan regulators etccomplete, all as specified & directed. (Note :- Switches, sockets etc shall be measured and paid for separately under appropriate items of BoQ\" ). |
| 67 | AllaspersrlitemNo.66(here-in-before) but for 15 Amp socket out let by using 2.50 Sqmm PVC insulated unsheathed copper conductor cable FRLS multi stranded on independent boardincluding provn of2.50 Sqmm unsheathed, multistrandedcopper conductor cable FRLS continues as earth wire connected to earth dolly etc complete all as specified and directed by Engineer-in-Charge. |
| 68 | Supply and fixing modular type switch 1 way 6Amp, 230Volts 1 modlecomplete all as specified and directed |
| 69 | Supply and fixing modular type switch 1 way 16Amp, 230Volts 2 modlecomplete all as specified and directed |
| 70 | Supply and fixing modular type socket 6Amp - 5 pin combined 2 modle 230 volts AC complete all as specified and directed |
| 71 | Supply and fixingmodular type socket 6Amp/16 Amp - 6 pin combined 2 modle 230 volts AC complete all as specified and directed |
| 72 | M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth wire 4 mm dia by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 15 mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers,PCCchamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing all as specified & as directed. Note :- PCC chamber shall be constructed at least 1.5m away from the earthelectrode and pipe for watering shall be provided in slanting manners. |
| 73 | S&F modular metal flush box alongwith modular white cover plate with frame for mounting, switches, sockets, fan regulator etc of 3 module deep sunk in wall including making good distrubed surfaces complete all as specified and directed Note: The cost of cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed by Engineer-in-charge including taking down old unserviceable blocks is included in this item and nothing will be paid extra on this account. |
| 74 | S&F modular metal flush box alongwith modular white cover plate with frame for mounting, switches, sockets, fan regulator etc of 4 module deep sunk in wall including making good distrubed surfaces complete all as specified and directed Note: The cost of cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed by Engineer-in-charge including taking down old unserviceable blocks is included in this item and nothing will be paid extra on this account. |
| 75 | S&F sheet metal enclosure distribution boardVTP&N,4 way, double door, powder coated, protection class IP-43, suitable for mounting MCCB up to capacity 125 Amps, DBs confirming to IS-13032, IS-8632, BS-5484 with min 200 Amp rating copper bus bar and isolated neutral bar, complete all as specified & directed. |
| 76 | S&F MCCB TPN, 63 Amps415 Volts , type \"C\" curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. |
| 77 | S & F MCB SP, 6 to 32 Amps240 Volts , \"C\" curve, 10 KA, IS-8828 marked for fixing in DB complete all as specified & directed |
| 78 | Supply lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armouredelectric power cable heavy duty with stranded aluminium conductor 1100 volts grade of size 50 Sqmm 3.5 core |
| 79 | 7.Supply, fixing and testing LED Building security light fitting of 60 Watt complete with robust body, corrosion resistant, superior finish, made in a single piece by high pressure die cast aluminium alloy including fixing on wall with 1.2 Mtr long GI pipe 25mm/suitable dia medium grade bracket at 120 degree angle with help of suitable GI clamps, nuts, bolts and washers etc complete all as directed.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 and Total Harmonic Distoration THD(I) less than 15% ,cool white colour and lamp starting time shouldnot be more than 10 second. Fitting should be provided with 10 KV surge protection. Driver should have high voltage withstanding capacity upto 300 volt AC. Driver should also have normal phase protection, no load , open circuit and short circuit protection. LED light fitting should be suitable for ambient temperature from -10 degree Centrigrade to 50 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be toughened glass to ensure IP 66 degree protection.Cover should not degrade due to heating and ageing. The efficacy of LED luminaries system shall be more than 110 lumens per watt |
| 80 | Supply and connecting three core cord flexible wire alongwith PVC medium grade 20 mm dia round pipe, copper conductor multistranded, PVC insulated and overall PVC sheathed of size 1.5Sqmm 1100 Volt , draw through LT steel tubular polesfor connection to street light from junction boxas directed by Engr- in- Charge. |
| 81 | M&L for road cutting including excavation returning filling in spreading leveling, well ramming in layers, soling with broken boulders/ stones obtained from demolition of existing road. 7.5cm thick coarse aggregate obtained from demolition of existing WBM o road, watering and ramming, 40mm thick PCC 1:3:6 type C-1 using 20mm graded stone aggregate for road match repair work. Section/ cross section areaof cuttingshall be as specified and as directed by Engineer -in Charge |
| 82 | Supply & laying light grade GI Pipe of size 80 mm bore, ISI marked in trench for cable protection complete all as specified and directed. |
| 83 | Supplying and laying DWC HDPE pipe of pressure rating 6 kgf/cm2 of Size 40 mm bore dia for cable protection as per IS 14930 laid in trenches/ fixed to wall/ pole/roof/laid in floor/hardstanding including suitable size of clamps all as specified and directed by Engg-in-Charge. |
| 84 | S&Fsheet metal enclosure Single pole and neutral with a two pin and earth plug and socket complete with and including one 20 Amp SPN MCB\"C\" curve complete all as specified. |