| 1 | Operation & Maintenance of firefighting system. Mechanical ventilation system, DG set Electrical installation and compound lighting at Community Plaza, kendra & Shopping Plaza as per inventory attached. |
| 2 | Rewinding of ceiling fan i/c varnishing, oiling, greasing, bearing replacement, 2.5-4 mfd capacitor replacements, testing, commissioning i/c removing & re-fixing in the same position etc. complete as reqd. |
| 3 | Supplying and replacement of 5A to 32A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required i/c rebate for dismantle material.a) Single pole |
| 4 | b) Double pole |
| 5 | Supplying & replacement following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.i/c Rebate for dismantle materiala) 100 A,30KA,FPMCCB |
| 6 | b) 63 A |
| 7 | LED Batten light(System lumen efficacy>135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 withdriver (Replaceable) as per the requirementwith Driver efficiency >85% ,Operating voltage AC140 270 Volt,frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20,CRI>80,Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), ofminimum 50000BurningHours with70%ofinitial Lumenmaintained tilllife ends,CCT3000°K/ 4000°K / 5700°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BISstandard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respecti/c external connectionswith1.5sq.mm FRLS/HFFR,PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required forLED fixtures as per BISshall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powdercoateddiecast/Extruded aluminiumBody (Thickness > 1.20 mm) 18-22 watt |
| 8 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135lm/Watt). Supplying, Installation,Testing&CommissioningofFloodLight, powdercoatedpressuredie cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as erIEC61000-4-5,Driverefficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95,IP-66,IK-10,CRI>70,undervoltageandovervoltageprotection, EMI-EMCasper CISPR-15,lenses for beam angle 30 deg-120deg as per the application and theproject requirement, suitable tilt able fitting, life time(LED, Driver & electrical circuitry) of minimum 50000Burning Hours with 70% of initial Lumen maintained tilllife ends as per LM80extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K/6500°K(AsperANSIBin), SDCM(Standard Deviation Colour Matching) <5, Maximumpowerconsumptionshouldnotmore than the specified rating and Fixture shall be of relevant BIS standard completeinallrespecti/c external connectionswith1.5sq.mmFRLS/HFFR, PVCinsulatedcopper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy ≥120 and <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).150 watt |
| 9 | Supplying of size 2 x 10 sq. mm XLPE aluminium conductor un-armoured power cable of 1.1 KV grade complete as required. |
| 10 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including |
| 11 | Supplying an Exhaust fan 450 mm, 1400 rpmmetal body as directed by engineer-in charge |
| 12 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making well the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 13 | Painting of MS Pipe fitting of following sizesfor firefighting system with 2 coats of enameled paint with single coat of Red oxide primer before applying the enamel paint i/c cleaning, rubbing etc. as reqd. for smooth surface complete as reqd.a) 150 mm to 200 mm Dia. |
| 14 | b) 65 mm to 100 mm Dia. |
| 15 | c) 25 mm to 40 mm Dia. |
| 16 | Painting of Hydrant box & Fire shaft door of different sizesfor firefighting system with 2 coats of enameled paint i/c single coat of Red oxide primer before applying the enamel paint i/c cleaning, rubbing etc. as reqd. for smooth surface complete etc. as reqd. |
| 17 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia. instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :a) Single headed Stainless steel |
| 18 | Servicing82.5 KVA capacity DG Set of \"Jakson\" make i/c supply and replacement of following items/ parts.i. Mobil Oil-15 ltr.ii. Diesel Filter-1 No.iii. Oil Filter-1 No.iv. Super by Pass Filter -1 No.v. Air Filter -1 No.vi. Coolant-10 ltr.vii. Water temp. Gauge-1 No.viii. O Ring-3 Nos. |