| 1 | New33/11 kVSubstations |
| 2 | 33/11 KV 2.5 MVA transformer withOLTC |
| 3 | 33 KV VCB ( 36KV,1250 A, 25KA) with G.I mounting structure |
| 4 | 33 KV Relay & Control Panel for 33 KV Feeder 110 V DC ( with numeric relay & static TVM and communication port for SCADA) |
| 5 | 33 KV Relay & Control Panel for 33 / 11 KV Transformer 110 V DC with out differential protection and with communication port for SCADA |
| 6 | 33 KV Single Phase Multi Core C.T. 400-200/5-5 A ( for Feeders) |
| 7 | 33 KV Single Phase Multi Core C.T. 100-50/5-5 A ( for Transformer) |
| 8 | Mounting structure for 33 kV CTs |
| 9 | 33KV Single Phase PT outdoor type oil filled, 33KV/√3 - 110V /√3 ,class-0.5/5P,30/30 VA |
| 10 | Mounting structure for PT |
| 11 | 33 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch as per IS (for incoming feeders) |
| 12 | 33 KV , 800 Amp Isolators triple pole single throw manually operated without earth Blade/switch as per IS (for Transformers fdrs, PT, 33 KV incomers & DTR) |
| 13 | Mounting structure for 33 kV Isolator |
| 14 | 30 kV 10 KA LA Class II ZnO Station Type |
| 15 | Insulated base for 30 kV LA |
| 16 | Surge counter for LA |
| 17 | Mounting structure for LA |
| 18 | 30 kV 10 KA LA Class II ZnO Distribution Class for (line type) station supply DTR with mounting structure |
| 19 | 11 KV Indoor 1250 A VCB Control and relay panel with 300-150/5/5 Amp CT, Static TVM and communication port for SCADA (for O/G feeders) |
| 20 | 11 KV Indoor 1250 A VCB Control and Relay panel with 300-150/5/5/5 Amp CT with static TVM and communication port for SCADA ( for Incomer) |
| 21 | 11 KV Indoor 1250 A VCB Control and relay panel with 300/5 Amp CT for incomer for bus coupler |
| 22 | 11KV lightning arrestor (9KV, 10KA), station type (for Transformers) |
| 23 | Mounting structure for 11 kV LA |
| 24 | 11 KV , 800 Amp Isolators triple pole single throw manually operated with earth Blade/switch as per IS (for transformers) |
| 25 | Mounting structure for 11 kV Isolator |
| 26 | 33/0.4 KV 100 KVA Station Service Transformer- EE-Level-2 latest amendment |
| 27 | 33 KV HG fuse unit for station service transformer |
| 28 | Mounting Structure for 33KV H.G Fuse |
| 29 | DTR LT Cubicle with bus bar and 2 Nos Outgoing MCCB\"s for Station Service Transformer (outdoor) |
| 30 | Battery Bank (150 AH, 110 V) |
| 31 | Battery Charger with DCDB |
| 32 | LT ACDB with 1 incomer + 6 O/G + 3 phase Static CT Operated Energy meter |
| 33 | Switchyard Area Lighting :- |
| 34 | Floodlighting (LED) 50W 6000K with waterproof fixture incl all accessories |
| 35 | G.I.-Hexagonal- 8 meter pole for Street Light along with mast arm rise with nut bolts complete |
| 36 | 2-core, 4sqmm. 1000 V grade PVC copper Cable |
| 37 | Termination lug for above |
| 38 | LT AC Panel for switchyard Lighting with light sensor / solenoid switch |
| 39 | GI Conduits 20 mm |
| 40 | Bus System and Support Structure :- |
| 41 | Switchyard Support Structure (G.I. lattice structure) with fdn bolts including Nut & bolts |
| 42 | TEE Clamp for wolf |
| 43 | ACSR Wolf Conductor |
| 44 | 33 kV Disc Insulator 70 KN |
| 45 | Hardware fittings with Tension Clamp for wolf |
| 46 | UPG Clamp for wolf |
| 47 | 33KV Post Insulator with accessories |
| 48 | Control Cable |
| 49 | 2.5 Sqmm 19 core Control Cable |
| 50 | 2.5 Sqmm 7 core Control Cable |
| 51 | 2.5 Sqmm 4 core Control Cable |
| 52 | 2.5 Sqmm 2 core Control Cable |
| 53 | Power Cable |
| 54 | 10 Sqmm 1 core PVC Copper Cable |
| 55 | LT XLPE Cable 1-core 120 Sq.mm. |
| 56 | 11 kV XLPE Cable 1-core 240 Sq.mm. |
| 57 | 11 KV XLPE cable 1 core, 185 sqmm |
| 58 | 11 kV XLPE Cable 1-core 240 Sq.mm. Termination Kit (Indoor) |
| 59 | 11 KV XLPE cable 1 core, 185 Sqmm Termination Kit (Indoor) |
| 60 | 11 kV XLPE Cable 1-core 240 Sq.mm. Termination Kit (Outdoor) |
| 61 | 11 KV XLPE cable 1 core, 185 Sqmm Termination Kit (Outdoor) |
| 62 | LT PVC Cable two core 25 sq mm (Aluminium) |
| 63 | Bi-metallic lug (assorted) |
| 64 | Evacuation of 11kV power: (Considering 3 feeder) |
| 65 | Galvanized S.T. poles,Sp-60, 12 m |
| 66 | 11 kV GO-AB Switch , channel base, 400A (for 11 KV O/G Fdrs ) |
| 67 | Channel cross arm, 75x40x4.8x2800mm |
| 68 | 11 kV Polymer Disc Insulator 70 KN |
| 69 | Hardware fittings with tension clamp for Raccoon |
| 70 | 11 kV pin insulators with GI pin. |
| 71 | G.I Jam clamp 12 M top |
| 72 | G.I Pole clamp 12 M top |
| 73 | G.I Pole clamp 12M middle |
| 74 | G.I Pole clamp 12 bottom |
| 75 | HT stay Set |
| 76 | GI Through bolt 5/8x10\" inch |
| 77 | G.I. bolt 5/8x4\" inch |
| 78 | G.I Pipe for 11 KV Cables riser on poles (75 mm Dia) |
| 79 | 11 KV lightning Arrestor (9 kV, 10 kA) line type with GI Structure (for O/G feeders) |
| 80 | Mandatory spare parts and Other Items : |
| 81 | 3 kg Co2 Fire Extinguisher + Sand Bucket |
| 82 | Furniture and equipment for Substation Control Rooms (Annexure FR) |
| 83 | Mandatory spare parts & tools for substations (Annexure MS - List 1) |
| 84 | Switchyard Earthing and Other Items : |
| 85 | Earthmat Materials as per (Annexure ES) |
| 86 | Safety Insulation mat for indoor 11 kv Switchgear Panels 1m width |
| 87 | Other items for completion of the works. |
| 88 | New 33 KV Line (12.40Ckm) |
| 89 | Galvanised pole 12 Mtr( SP-60)-410 |
| 90 | G.I. Channel 100x50x6x3050 mm |
| 91 | HT Stay set compete |
| 92 | 33 KV Bracing set (D/Tier) |
| 93 | G.I Pole clamp 12 m(Top) |
| 94 | G.I Pole clamp 12 m (Middle) |
| 95 | G.I Pole clamp 12 m (Bottom) |
| 96 | G.I Jam clamp 12m(Top) |
| 97 | G.I Jam clamp 12m( Middle) |
| 98 | G.I Stay clamp 12 m(Bottom) |
| 99 | GI Through bolts 5/8\" x 12\" |
| 100 | M.S. Nut & Bolt 5/8 x 4\" |
| 101 | 33 KVPolymer Pin insulator |
| 102 | ACSR Wolf Conductor |
| 103 | Polymer Disc Insulator 70 KN |
| 104 | Hardware fittings for Wolf |
| 105 | MVCC-AL59 ACS-148.00 Sqmm |
| 106 | Jointing Kit for MVCC along with all accessories complete for 1 km |
| 107 | HT Guy Insulator 88 KN |
| 108 | GI Stay wire 7/10 SWG |
| 109 | 1 -Metre G.I. Earthing Pipe 40mm, |
| 110 | 33 KV lighting spikes |
| 111 | Cement for grouting of pole & stay set |
| 112 | Danger Plate |
| 113 | Anti -climbing device |
| 114 | Cradle Guard cross Arm for DP 33 KV (65X65X6X4320 mm) along with clamp |
| 115 | G.I wire, 8 SWG for guarding and grounding |
| 116 | G.I wire,6 SWG for guarding and grounding |
| 117 | Sundries ( drilling of holes, welding of channel etc) |
| 118 | New 11 KV Line (5.80 Ckm) |
| 119 | Galvanized pole STP 9.5mtr (SP-39)-410 |
| 120 | G.IChannel cross arm 75×40×4.8×2280 mm |
| 121 | G.IChannel cross arm 75×40×4.8×1200 mm |
| 122 | G.IChannel top bracket 75×75 * 40 *4.8 * 310 mm |
| 123 | 11 KV Z- Type bracing set (50x50x6 mm) |
| 124 | 11 KV Polymer insulators 45 KN |
| 125 | 11 KV Pin insulators Polymer |
| 126 | 11 KV Lighting Spike |
| 127 | HT Stay set |
| 128 | HT Guy insulators 88 KN. |
| 129 | G.I.Stay wire7/10 SWG |
| 130 | G.I. wire8 SWG |
| 131 | G.I Pole clamp 9.5 mtr(T) |
| 132 | G.I Pole clamp 9.5 mtr (M) |
| 133 | G.I Pole clamp 9.5 mtrpole (B) |
| 134 | G.I Stay clamp 9.5 mtr |
| 135 | G.I Jam clamp 9.5 mtr (T) |
| 136 | G.I Nuts & Bolts (a) 5/8”,4\" |
| 137 | G.I through bolts 5/8\"x 12\" |
| 138 | GI earthing pipe |
| 139 | ACSR WeaselConductor |
| 140 | MVCC-AL59 ACS-52.88 Sqmm |
| 141 | Hard ware fittings for Weasel2 bolted |
| 142 | Jointing Kit for MVCC along with all accessories complete for 1 km |
| 143 | 11 KV GOAB switch channel base type 400 Amps. |
| 144 | Barbed wire 12 swg. |
| 145 | Danger plate |
| 146 | Anti -climbing device |
| 147 | Cradle Guard cross Arm for DP 33 KV (65X65X6X3800 mm) along with clamp |
| 148 | G.I wire, 8 SWG for guarding and grounding |
| 149 | G.I wire,6 SWG for guarding and grounding |
| 150 | Cement for grouting of poles |
| 151 | Cement for grouting of stay |
| 152 | Sundries ( drilling of holes, welding of channel etc) |