| 1 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth or n exc 10 Sqm on plan and n exc 1.5 m in depth & getting out, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes or for layingunderground cable, pipe lines etc. in soft/ loose soil, complete all as specified & directed. |
| 2 | Returning, filling in soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed. |
| 3 | Removing excavated material (soil) n exc. 50m distance and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and directed. |
| 4 | M&L dry river clean Sand filling in trenches around underground cables for earth cushion, complete all as specified and directed. (Depth of sand shall be measured after punning). |
| 5 | Supplying and laying in renewal of un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm laid dry and flat adjoining each other over sand cushion in trenches as protection to UG cable, complete all as specified and directed. |
| 6 | M & L for hardcore broken stone or boulders crushed aggregate of size 25 to 40 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface at 4 Pole, 2 Pole strucutres and other E&M Installations complete all as specified and directed. |
| 7 | Demolition of old u/s existing transformer foundation and M & L for construction of plateform of size 2500 x 2500 x 1200mm with brick construction in cement mortar 1:4 PCC (M-10 nominal mix) in foundation, 100mm thick RCC M-25 grade slab, with & including 8mm MS TMT bars 120mm c/c on bothway, brick masonary steps on one side XPM Jali fixed on angle iron 40x 40x6 mm post upto height of 8 feet above ground level and openable gate with locking arrangment including making provision for entry and exit of HT/LT cables and steps made to access to the top of plateform including plastering to bricks masonary complete including painting with 2 coats of whitewash on plastered surface and painting steel surface with 2 coats of red oxide primer complete all as specified and as diredted. |
| 8 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts, in any hape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint & including dismantling of old unserviceable cross arms of MS channel or angle sections etc complete all as specified and directed. |
| 9 | M&L for pin type, porcelain, vitreous, white, borwn or green insulator, including one galvanised mild steel spindle, two galvanised mild steel spindle, two galnvanised iron wahers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade & including dismantling of old unserviceable insulator, complete all as specified and directed. |
| 10 | M&L for insulator disc type porcelain, vitreous, 145 mm high and 255 mm dia ball and socket type, white, brown or green for tension with tension clamps for conductor, working pressure 11000 volts & including dismantling of old unserviceable insulator, complete all as specified and directed. |
| 11 | M&L for Loop type insulator, vitreous porcelain, white, brown or green, Large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm & including dismantling of old unserviceable insulator, complete all as specified and directed. |
| 12 | S&F in renewal of earth continuity conductor or main earthing lead 32x6mm galvanised iron or steel strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required completeall as specified and directed. |
| 13 | S&F in renewal of earth continuity conductor or main earthing lead 32x6mm copper strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required completeall as specified and directed. |
| 14 | M&L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth lead of 4mm dia galvanised iron for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 2 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: -(a) Irrespective of whatever is shown in plate No 2 of SSR Part - 1 (2009), earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b)Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m. |
| 15 | M&L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing earth strip of 32x6 mm galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 32x6 mm galvanised iron for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 2 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: -(a) Irrespective of whatever is shown in plate No 2 of SSR Part - 1 (2009), earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b)Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m. |
| 16 | M & L for supply, installation, testing and commissioning in renewal of pure copper pipe electrode earthing maintenance free earthing based on 2.25 mtr long copper pipe 55 mm dia(ID) with wall thickness of 3 mm, copper strip 25x4 mm ( strip in pipe type electrode) and pure copperpipe electrode shall be filled with MFC for improvement of conductivity of electrode, 60 KGS approx of BFC shall befilled around the copper pipe elecrode. Rate included for testing, commisioning including checking of earth continuity and earth result complete all as specified and directed. Vendors are bound to get earthing result less than or upto1 Ohm with or without grid of earthings (Maximum number of new earthings in grid are restricted to 3 nos) Copper strip required for interconnection of earth pits in grid must be laid 2 ft below the ground level and the same must be treated with chemical (BFC) if required to achieve resistance value. Any additional work and material required to achieve the required result is included in the cost. Any additional work and material required to achieve the required result is included in the cost. Rate is included for boring of earthing in any type of soil/rock upto 200 mm bore. Continuity of good earth resistance shall maintained upto 1 year and testing will be carried out monthly by MES authority. Copper strip must be connected with copper pipe electrode and at other joints through nut bolt in addition to brazing complete all as specified and directed. |
| 17 | S&F in renewal of 80 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed. |
| 18 | S&F in renewal of 100 mm bore steel water tubing, light grade, galvanised, with all fitting, laid in trenches/fixed to walls/poles etc as protection to cables, with and including necessary MS clamps, nuts botls, washers etc required for fixing, complete all as specified and directed. |
| 19 | Supply, installing, testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 15 nos including200 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, suitable for HT 11 KV, 50 Hz AC supply & including necessary electric connections and taking down old unserviceable GOD complete all as specified and directed. |
| 20 | Supply, installing, testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 15 nos including400 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, completesuitable for HT 11 KV, 50 Hz AC supply including necessary electric connections and taking down old unserviceable GOD complete all as specified and directed. |
| 21 | Supplying, laying, jointing, testing and commisioning XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) withaluminium conductor, 11000 volts Earthed grade (ISI marked), laid in trenches / ducts / encased in GI pipe / fixed to pole/wall with necessary angle iron support, clamp, nut , bolts etc and including taking down of old unserviceable existing UG cables complete all as specified and directed for following cross sectional areas of cables :- Notes for Srl item Nos. 21.00 to 21.10 :-(i) Excavation, earth work, sand cushioning, cable protection cover & GI pipes shall be measured and paid for separately under respective items of BOQ. (ii) Quoated rate shall be deemed to be inclusive of connecting up with control gear including cable glands and cable lugs.Cross Sectional area of cable 95 Sq mm 3 core |
| 22 | Cross Sectional area of cable 185 Sq mm 3 core |
| 23 | Supply, transporting, erection and fixing steel tubular swaged pole, 11.00 metres long, type 410 SP-55, complete with cast iron base plate, pole cap, finial taper plug, bolts, nuts, washers etc including necessary earth work and excavation, PCC in foundation 1:3:6 type C2, using 40 mm graded stone aggregate and PCC 1:2:4 type B1, using 20 mm graded stone aggregate as in coping to the pole, disposal of surplus soil to a distance not exceeding 50 m, painting the pole with two coats of aluminium paint over one coat of red oxide primer including 3 nos band/straps with red post office box colour (300mm wide each) synthetic enamelled paint at a distance 300mm from plinth block and marking pole nos with black synthetic enamelled paint including tarring one coat on steel surface embedded in concrete & including taking down existing old unserviceable poles and complete all as specified and directed. |
| 24 | M&L for painting the external exposed surfaces of 2 pole structures ofsteel tubular swaged poles of 11 metres long alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 strips of width min 10 cm around the pole complete all as directed. |
| 25 | M&L for painting the external exposed surfaces of 4 pole structures ofsteel tubular swaged poles of 11 metres long alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 strips of width min 10 cm around the pole complete all as directed. |
| 26 | M & L for cutting of bushes and cleaning the area around the sub station & surface dressing n exc 15 cm deep & including two pole/four pole structures premises at southern sector and trimming the trees,complete all as specified and directed. |
| 27 | S&F in renewal of HT cable route indicator made of RCC M15 (Nominal Mix) using 12.5mm nominal size crushed stone aggregate of size 150mm (Length)X100mm (Width)X900mm (Height) duly painted with cement base and written in white colour with lettering \"MES HT cable\" and arrow indicating direction using two coats of synthetic enamel paint in black colour and including necessary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20mm nominal graded crushed stone aggregate of size 400mmx400mmx300mm complete all as specified and as directed. NOTE : (i)The reinforcement in RCC shall not be less than as minimum reinforcement required as per IS.(ii) Cost of pcc shall be included in the rate quoted. |
| 28 | Supply and fixingin renewal of danger notice plate of 1.5 mm thick mild steel sheet vitreous enanelled white of size 20 x25 cm with figures letters and conventional skull bones in signal red colour and fixed with mild steeel clamps made of flat iron nuts bolts and washers etc for HT poles with voltage and danger indicated in hindi and english and local vernacular complete all as specified and directed. |
| 29 | M & L for horizental drilling under road/pavement hard standing with trenchless technology using machine 0.4 mpa working pressure for laying pipe line of size 80 mm bore complete all as specified and directed. Note:Drill hole (trenchless) shall be done without disturbing top surfaces of road by appropriate machine & no extra payment shall be given to contractor on this account. |
| 30 | M & L for horizental drilling under road/pavement hard standing with trenchless technology using machine 0.4 mpa working pressure for laying pipe line of size 100 mm bore complete all as specified and directed. Note:Drill hole (trenchless) shall be done without disturbing top surfaces of road by appropriate machine & no extra payment shall be given to contractor on this account. |
| 31 | M & Lin renewal of anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed. |
| 32 | M & L in renewal of HT jumperingfrom HT 4/2 polestructure to bus bar to GOD 3 Nos with HT cable 95 sqmm not less than 3 mtrcomplete including connector and lugs of suitable size with provision of Nuts & bolts washeretc complete all as specified and directed.Note : 3 lengths i.e. for R,Y & B shall be measured as one unit. |
| 33 | M & L for repairing/overhauling of Air break switch and DO fuse unit up to 400 Amps capacity 11 KV triple pole Mechanically operted mounted on insulators and steel frame installed vertically/horizontally by oiling and greasing of mechanical moving parts smoothing and polshing of electric contacts and applying conducting jelly to contact and replacement of broken/worn out compenents ( if required) including testing after repair complete all as directed.Note :- Cost ofreplacement of following worn out components /parts/insulators etc (if required) shall be included in the rate quoted. Bidders may quote accordingly :-(a) Female contact or fixed contact of capacity up to 400 Amps, 11 KV heavy duty of gigh conductive metal.(b) Male contact or moving contact of capacity up to 400 Amps, 11 KV heavy duty of high conductive metal.(c ) Tinned copper flexible jumper up to 400 Amp.(d) Fixed top and bottom contact assembly 11 KV 400 Amp for DO fuse unit.(e) Fiber glass tube with metallic fittings both ends suitable for DO fuse 11 KV. |
| 34 | M & L for disconnecting all HT/LT connection of transformer, lifting it from its foundation/ structureusing fork lift/crane carefully, refixing it to plateform making all HT/LT connetions and charging the transformer to restore electric supply complete all as specified and as directed.Note :- (i) Any damage during shifting or lifting of transfarmer will be responsibility of contractor and contractor will be liable to repair the same at his own cost. (ii) Lowering and lifting of transformer shall be treated as single job. |
| 35 | M & L for Servicing of HT 11 KV VCBs including raking out of Breaker, lubrication /greasing of the mechanical parts including healthy check, cleanign of CT, caliberation after servicing reconnection in all respect along with replacement of unserviceable relays, levers, LED indicators, control wiring, insulators etc (if required), allas per existing arrangement and restore the supply complete all as specified and as directed.Note :- Cost of unsv minor parts/materials replaced shall be deemed to be included in the rate quoted. No extra claim shall be accepted by dept on this account. Bidders may quote accordingly & Any major parts replaced shall be paid under respective item of schedule (BOQ). |
| 36 | M & L for hiring of cable fault locator machine for HT cables working voltage 11 KV to find out the fault inunderground trench at different location up to 500 RM after locate fault filling the straight through joint and charging the cable and jointing the cable on both side in RMU/VCB/HT bus bar chamber or over head line all as directed.Note :- (i) Complaint shall beintimated to contractor on phone between 8 am to 10 pm and will be attended by contractor within 12 hrs, failing which a penalty of Rs. 5000 per day shall be imposed on contractor.(ii) Cost of joints shall be measured andpaid in respective item of Schedule.(iii) Machine hiring count shall be measured and paid as per number of arrivals of machine not as per no. of faults located in a single arrival. |
| 37 | M & L for Servicing of 11 KV 3 phase 50Hz 3 wire 630 Amp breaking capacitySF6 Ring Main Unitby cleaning and lubricating mechanical parts and checking functioning of springs levers on/off position after proper shut down of electric supply along with replacement of unserviceable relays, levers, LED indicators, control wiring, insulator etc(if required) and restore the supply after complete servicing complete all as specified and as directed.Note :- Cost of unsv materials replaced shall be deemed to be included in the rate quoted. No extra claim shall be accepted by dept on this account. Bidders may quote accordingly. |
| 38 | M& L for Servicing of HT 33 KV VCBs including raking out of Breaker, lubrication/ greasing of the mechanical parts including healthy check, cleanign of CT, after servicing reconnection in all respectalong with replacement of unserviceable relays, levers, LED indicators, control wiring, insulators etc (if required), allas per existing arrangement and restore the supply complete all as specified and as directed.Note :- Cost of unsv materials replaced shall be deemed to be included in the rate quoted. No extra claim shall be accepted by the Deppt on this account. Bidders may quote accordingly. |
| 39 | Supply and filling as in renewal of silica gel inside the breather assembly and fixing properly with transformer complete all as specified and directed. |
| 40 | M & L for replacement of defective/ cracked HT porcelain bushing (set of three) of suitable size for 33/11 KV transformer upto 3.15 MVA including washers of good quality complete all as specified and directed. |
| 41 | M & L for replacement of defective/ wornout HT bush rod (set of three) made out of copper with brass nutsand washers of required length including connecting up with HT coil of transformer (33/11 KV) upto 3.15 MVA complete all as specified and directed. |
| 42 | Dehydration and filterationofexisting transformer oilusing transformer oil filteration plant to eliminate foreign particles and to improve di-electric strength upto 50 KV at 2mm electrode gap and to bring the acidity within the permissible limit complete all as specified and directed.Note :- Dehydration & filteration shall be done by using vehicle mounted setup cosisting of heating, filteration machine etcand oil shall be filtered/dehdrated in a closed circuit. |
| 43 | Supply & filling oil for power transformers for topping up/refilling the oil having dielectric strength 40-60 KV during filling after initial filteration complete all as specified and directed. |
| 44 | M/L for painting of power transformer up to 3.15 MVA capacity with good quality synthetic enameled paint using spray gun with compressed air on complete external portion of transformer including preparation of surface by scrubbing, cleaning ,stains greasy spots, dusts etc, The painting of transformer shall be carried out in situ ie. on four pole structure or in sub station at different places complete all as specified and directed. |
| 45 | M & L in renewal of numerical control over current earth fault IDMT relay CGI-14No crompton or equivalent, suitable for the existing VCBs complete all as specified and directed. |
| 46 | M & L in renewal of Master trip relay suitable for 24 Volt DC Supply crompton CGXH1 or equivalent, suitable for the existing VCBs complete all as specified and directed. |
| 47 | M & L in renewal of auxiliary relay suitable for 24 Volt DC Supply, Crompton CGXH1 or equivalent, suitable for the existing VCBs complete all as specified and directed. |
| 48 | M & L in renewal of battery backed Power pack unit 7-12 AH suitable for input 230 AC Supply and able to supply 24V DC supply complete all as specified and directd. |
| 49 | M&L for paint for MS structure of 33 kV main receiving station and preparing surface for painting by removing rust using sand paper & applying two coat of aluminium paint over a coat of suitable primer upto full surface area including MS clamps, cross arms, bracings etc all as directed at site complete all as specified and directed. |
| 50 | S & F in renewal for laying of XLPE insulated (heavy duty) armoured Copper conductor electric control cable 1100 volt of 2.5 Sqmm 04 core complete all as specified and directed. |
| 51 | M & L for servicing & greasing of 33 kV Isolators for smooth operation complete all as specified and directed. |
| 52 | M & L for performing all the routine/safety testsof power transformer incl Insulation test, Ratio test, Magnetic balance test, Test on all protection relays, test on operation and stability of earth fault relays, test on over current relays, trippling tests, buchholz relay trippng & alarmtest, alarm & tripping test of OTI, WTI, including calibration/setting of relays and submission of reports complete all as specified and directed. The the test shall be carried out by the OEM/auth rep of the OEM. Note :- Test report shall be submitted at the time of billing duly signed by company or its authrised dealer/Rep. |
| 53 | M & L for red colour sticker/strip 50mm wide fluorescent type for pasting on poles and fencing for night vision complete all as specified and directed. |
| 54 | S & F in renewal of TNC (trip, Neautral and close) switch lever for breaker and transformer control all as per existing arrangement complete all as specified and as directed. |
| 55 | M & L in renewal for lightening arresters expulsion type (set of three) complete with all fittings, transmission class, discharge capacity 65 kilo amp Suitable for 11000 volts complete all as specified and directed. |
| 56 | M & L in renewal for lightening arresters expulsion type (set of three) complete with all fittings, transmission class, discharge capacity 65 kilo amp Suitable for 33000 volts complete all as specified and directed. |
| 57 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable & including excavation in any type of soil/strata, taking out cable & making disturbed surface after relaying the cable making joints suitable for aluminium conductor of following size complete all as specified and directed:- Note:- Unserviceable joint shall be replaced within 24 Hrs after intimation of failure & documentary proof kept in record duly signed by the Enginner-in-Charge for the same.A penalty of Rs. 1500 per day shall be imposed on contractor, if not attended timely. |
| 58 | 50 Sqmm to 95 Sqmm |
| 59 | 120 Sqmm to 185 Sqmm |
| 60 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size & including excavation in any type of soil/strata, taking out cable & making disturbed surface after relaying the cable making joints suitable for aluminium conductor of following size complete all as specified and directed:- Note:- Unserviceable joint shall be replaced within 24 Hrs after intimation of failure & documentary proof kept in record duly signed by the Enginner-in-Charge for the same.A penalty of Rs. 1500 per day shall be imposed on contractor, if not attended timely. |
| 61 | 50 Sqmm to 95 Sqmm |
| 62 | 120 Sqmm to 185 Sqmm |
| 63 | 240 Sqmm to 400 Sqmm |
| 64 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm & including excavation in any type of soil/strata, taking out cable & making disturbed surface after relaying the cable making joints suitable for aluminium conductor of following size complete all as specified and directed:- Note:- Unserviceable joint shall be replaced within 24 Hrs after intimation of failure & documentary proof kept in record duly signed by the Enginner-in-Charge for the same.A penalty of Rs. 1500 per day shall be imposed on contractor, if not attended timely. |
| 65 | Supply and fixing in renewal of Hybrid solar street lights 50 watt capacity along with GI pIpeLight grade 50mm of height 9 metre fixing in PCCfoundation with (1:3:8) of that combines the use of solar energy and AC power. The lights use solar panels to charge a battery during the day, and then use the stored energy to power LED lights at night. They are also connected to the grid, which provides a backup power source in case the battery runs out of charge. The use of both solar and AC power allows these lights to have a longer operating time, especially during overcast days or in areas with less sunlight. The hybrid solar lights provide an efficient and reliable lighting solution that can save energy costs and also reduce the reliance on traditional power sources. Street lights with built in Mono Crystalline Panel, Lithium Ferro Phosphate (LiFePO 4) battery, MPPT charge controller , 50 watt capacity , 6000k, 150 lm/watt, complete all as specified and directed.Make: Bajaj , Wipro, Crompton, Philips.Note: (i) Cost of junction/ Polebox included in quoted rate.(ii) solar lights with GI pipe in cluding painting, fixing ,mounting deemed to be included in quoted rate. |
| 66 | S & F in renewal of installation of Name sign board of sizemade with acrylic sheet of width 10 mm along with LED luminated alphabets of size not less than 12 inch(L) x 10 inch(W) x 3 Inch (H) LED luminate from all 4 sides,LED sheets shall be water proof, color white/warm white operating on AC 220 Volts supply incl adoptors for the lighyts life time > 10000 Hrs, complete all as per OEM, complete all specified and directed.Note: (i) Cost of acrylic sheet for suitable size included in quoted rate.(ii) Details Name Boardshall be provided by Engr in charge/GE(iiI) Fixing of name board at site including necessary arrangements( nut,bolts,washers etc) shall be deemed in quoted rate. |