| 1 | 25/31.5 MVA, 66/11kV T/Fs |
| 2 | 12.5/16 MVA 66/11 kV T/F (This 1 no. Transformer will be shifted from existing 66kV Substation Shahbad to new 66kV Substation Shahbad) |
| 3 | 66 kV SF-6 Breaker along with 20% extra SF-6 Gas |
| 4 | 66 kV Isolator with E/Switch |
| 5 | 66 kV Isolator without E/Switch |
| 6 | 66 kV Surge Arrestor |
| 7 | 66 kV CTs for Line & Bus Coupler (600-300-150/1-1-1A) |
| 8 | 66 kV T/F CT (300-200-150/0.577-1-1A) |
| 9 | 66 kV PT for line |
| 10 | 66 kV NCT (300-200-150/1A) |
| 11 | 11 kV NCT (1800-900/5A) for 25/31.5 MVA, 66/11 kV T/F |
| 12 | 11 kV NCT (1200-900/5A) for 12.5/16 MVA, 66/11 kV T/F |
| 13 | 11 kV Surge Arrestor |
| 14 | 11 kV 15 Panel Board (2000A) (including one no. bus sectionalizer panel) |
| 15 | 11 kV 13 Panel Board (1250A) (including one no. bus sectionalizer panel) |
| 16 | 66kV C&R Panels with SAS:a) Bus Coupler Protection and Circuit Breaker Panel (Without Auto Reclose) with SAS |
| 17 | b) Line Protection and Circuit Breaker Panel (Without Auto Reclose) with SAS |
| 18 | b) Line Protection and Circuit Breaker Panel (Without Auto Reclose) with line current differential- cum- backup DPR with SAS |
| 19 | c) Transformer Protection and Circuit Breaker Panel (Without Auto Reclose) with SAS |
| 20 | a) 9000 KVAR 12.65 kV Automatically Switched Capacitor Bank along with allied equipment as per technical specification |
| 21 | b) 4800 KVAR 12.65 kV Automatically Switched Capacitor Bank along with allied equipments as per technical specification. |
| 22 | 220V 100AH Battery Bank San Tubular |
| 23 | 220 V 20/30 A Battery charger (SMPS) |
| 24 | 220V D.C.D.B. |
| 25 | 415 V LT AC Distribution Board 300 A |
| 26 | 11/0.4 kV Station T/F 200 KVA |
| 27 | 1.1 kV Copper Control Cable unarmoured for 66 kV bays of size 7Cx4mm2, 4Cx4mm2, 2Cx4mm2, 2Cx6mm2, 3Cx2.5mm2, 16Cx2.5mm2, 10Cx2.5mm2 & 7Cx2.5mm2 including junction box etc. refer Section-5 of copper & control cable & Section-7 for switchyard erection |
| 28 | Stainless steel MK (200 TB) |
| 29 | a) 11 kV Power Cable XLPE 1C x1000mm2 for T/F to 11kV incomer (4 runs per phase for each 25/31.5 MVA 66/11kV transformer allocating them 2 runs per phase for each 11kV I/C & 2 runs per phase for each 12.5/16 MVA 66/11 kV transformer allocating them 1 runs per phase for each 11kV I/C) |
| 30 | b) Termination kit at both ends for 11kV XLPE power Cable (1C x 1000mm2) Termination Kits for (Indoor/Outdoor) both ends along with accessories constitute a set for each cable. |
| 31 | a) 11 kV Power Cable XLPE 3C x 400sq mm for Capacitor Bank |
| 32 | b) Termination kit at both ends for 11 kV XLPE Power Cable ( 3C x 400 mm2) Termination kits for (indoor/outdoor) both ends alongwith assessories constitute a set of each cable. |
| 33 | a) 11 kV Power Cable XLPE 3C x 50 sq mm for station T/F |
| 34 | b) Termination kit at both ends for 11 kV XLPE Power Cable ( 3C x 50 mm2) Termination kits for (indoor/outdoor) both ends alongwith assessories constitute a set of each cable. |
| 35 | 650/1100 Volts 3.5 core 240 mm2 aluminium power cable from Aux. T/F to ACDB. |
| 36 | 650/1100 Volt 3.5 core 70 mm2 aluminium cable for oil filtration set. |
| 37 | 650/1100 Volt 4core 16mm2 unarmoured with copper power cable for MLDB and other cable required as per contract for 66 kV bays. |
| 38 | Earthing Mat Material. The earth mat will be designed/ quoted for soil resistivity of 50Ωm. In case soil resistivity is more than 50Ωm then the earth mat will be designed for actual soil resistivity. The payment of extra material to be used for earth mat shall be made on pro rata basis. The approximate area of earth mat to be laid is given in the corresponding columns of the substations. However, item will remain a Lot item. (calculations may be made considering fault/shock duration of 1 sec.) Area: 5600 m2 |
| 39 | Fire Fighting equipments as per section-6 :i) 22.5 Kg Capacity FE CO2 type, Trolley Mounted |
| 40 | ii) 25 Kg Capacity FE DCP type, Trolley Mounted |
| 41 | iii) DCP 10 Kg Capacity, Wall mounted |
| 42 | iv) FE CO2 6.5 Kg Capacity, Wall mounted |
| 43 | v) DCP 5 Kg Capacity, Wall mounted |
| 44 | vi) Foam Type 9 Litre Capacity, Wall mounted |
| 45 | vii) Water CO2 9 Litre, Wall mounted |
| 46 | viii) Fire Buckets (12 Nos. with stand in one set) |
| 47 | Complete lightning of control room building, switch yard area, road and street as per section-7 of the specification:a) Supply and installation of 2 fittings of 240W LED lamps with all accessories for Complete lighting of outdoor Switch yard area as per clause 16.0 of section 7 of the specifications. |
| 48 | b) Supply and installation of 35W LED tube on tubular steel poles along with the boundary wall at a distance of 30 meter as per as per clause 16.0 of section 7 of the specification |
| 49 | c) Complete lighting of road and street by providing 90W LED lamps on tubular steel poles at a distance of 15meter along the roads and streets as per clause 16.0 of section 7 of the specification. |
| 50 | d) Supply and installation of post top lantern 40W LED Lamps with all complete accessories at the entrance gate of sub-station. |
| 51 | e) Supply and installation of 40W LED Lamps with all complete accessories on corners of control room building. |
| 52 | Complete Substation automation system of 66/11kV substations including hardware (along with transducers) and software along with associated equipment for the bays (bay as defined in the technical specification, sec-sub-station automation system) as per technical specification. Present FutureSr.No. Description No. of 66 kV Bays1. T/F 3 *2. Line 43. B/C 1 -Note: signals from protection relays in 11kV incomer would also be wired to substation automation system (SAS). *Future scope in SAS shall also be kept as per the space available in GELO for future bays (i.e. for 66kV) |
| 53 | Time synchronization equipment |
| 54 | High wall type split AC unit of 2 Ton capacity for SCADA room & C&R Panel room (as per technical specification). |
| 55 | Computer system (SFF) with: Intel core i5 processor with 11th generation or higher as specified in section-04 |
| 56 | Multi-Function Monochromatic Laser Jet Machine (A4-25 PPM or more) with print copy and scan function, Duplexing feature, composite cartridge, ADF, A4 or larger flatbed size, Networking and wi-fi both, at least 1 input tray, 3 years on site OEM warranty. |
| 57 | BOM FOR SAMAST COMPLIANT IEM (ON SEPARATE CUBICLE) FOR 11KV I/C: 1. (a) 3P4W Interface Energy Meters (ABT type) 0.2s Class 1A with TTB & BCS (02 no. for each 11KV Incomer) |
| 58 | 1 (b) Testing of IEM System from NABL accredited lab |
| 59 | 2. Wired Indoor Meters Panel suitable for 8 meters |
| 60 | 3. 16 P Industrial Grade un-managed Network switch |
| 61 | 4. 4 Port line interfacing unit with patch chord |
| 62 | 5. (a) Data concentrator unit (DCU)/communication Gateway (IG) with dual SIM Modem along with enclosure and accessories |
| 63 | 5. (b) 3C x 2.5 Sq. mm Un-armoured cable for DCU and Switches |
| 64 | 6. Cat-6 cable-unshielded |
| 65 | 7. PVC conduit Pipe - 3/4\" with accessories for Cat-6 cable (In line with cat-6 cable) |
| 66 | 8. Armored Fibre Optic Cable (2 pair) |
| 67 | 9. HDPE conduit - 40/33 with accessories (In line with armored cable for CT/PT) |
| 68 | 10. 4Cx4 Sqmm armoured cable for PT |
| 69 | 11. 4Cx4 Sqmm armoured cable for CT |
| 70 | 48V 120AH Battery Bank San Tubular |
| 71 | 48V SMPS Battery Charger (for 48V 120AH Battery Bank San Tubular Battery) |
| 72 | 220kV S/Stn. Shahbad a) Supply of Numerical Line Current Differential Relay-cum backup Distance protection relay in place of existing distance protection relay on existing C&R Panel (non SAS complaint) installed at 220kV S/Stn Shahbad (for 66kV Ckt-II from 220kV Shahbad to 66kV Shahbad) |
| 73 | b) The erection/retrofitting, testing and commissioning of Numerical Line Current Differential-cum-backup Distance Protection Relay on existing C&R Panel (non SAS Complaint) installed at 220kV S/Stn Shahbad (for 66kV Ckt-II from 220kV Shahbad to 66kV Shahbad) |
| 74 | 66 kV bolted type suspension string assembly with 5 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and suspension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators |
| 75 | 66 kV Bolted type tension string assembly with 6 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connection and tension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators |
| 76 | 66 kV bolted type suspension string assembly with 5 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and suspension clamp set suitable for twin zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators |
| 77 | 66 kV Bolted type tension string assembly with 6 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connection and tension clamp set suitable for twin zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators |
| 78 | Bolted type 11kV tension string assembly with 3 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and tension clamp sets suitable for twin tarantulla conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators |
| 79 | Boltless C-Type Wedge connectors matching with conductor size. |
| 80 | Copper lugs glands, PVC ferrules for control cabling. |
| 81 | Fiber cleats, Aluminium clamps, bolts, nuts, washers etc., for fixing control cables in trenches. |
| 82 | Galvanized iron perforated tray with side coupler plate bolts, nuts, washers and clamps etc. of size 75x25x2 mm, 150x25x2mm, 100x25x2mm etc. & G.I. Conduits of 50mm/100mm dia from equipment to main trench as per Section-7, Switchyard erection. |
| 83 | ACSR Zebra Conductor (approx.) |
| 84 | AAC Tarantulla Conductor |
| 85 | 7/3.15 GS Earth wire |
| 86 | Spacers for Twin Tarantulla and Twin Zebra Conductor |
| 87 | U-bolt 20mm dia. |
| 88 | Mandatory spares for hardware/ mechanical/ Electrical auxiliaries to be supplied. 10 % of the finally approved quantities for item mentioned from Sr. No. 74 to 78. |
| 89 | 2.5 ″ dia HDD/PVC pipe for 4c x 4 mm2 c/cable from CT, VT to maintaining system as per sec-5. |
| 90 | Item for associated structure workA)‘Lattice type steel structure for 66 kV AIS Shahbad (Kurukshetra), Supply of material, preparation of fabrication drawing, galvanizing and delivery of lattice type steel structure for tower and beams for 66/11KV switchyard fabricated from steel conforming to IS: 2062 including nuts-bolts gusset plates foundation bolts and other accessories as per drawings supplied by the owner:(66kV Cable support structure of galvanized iron along with foundation to be designed by bidder as per site requirement/size of cable). Main S/Stn. tower and beam:a)Tower type CT-4 |
| 91 | b) Tower type CT-5 |
| 92 | c) Tower type CT-6 |
| 93 | d) Tower type CT-8 |
| 94 | e) Beam type CB-6 |
| 95 | f) Beam type CB-7 |
| 96 | g) Tower type DT-2 |
| 97 | h) Tower type DT-3 |
| 98 | i) Beam type DB-2X |
| 99 | B) Equipment Structure:a) 66 kV CT Drg. No. HTD/ST-88R |
| 100 | b) 66 kV NCT Drg. No. HTD/ST-145 (if required ) |
| 101 | c) 66 kV PT Drg. No. HHW/ST-66 |
| 102 | d) 66 kV Surge Arrestor Drg. No. HTD/ST-89 |
| 103 | e) 66 kV Isolator Drg. No. HTD/ST-87R |
| 104 | f) 66 kV L&E Switch Drg. HTD/ST-87R |
| 105 | g) 11 kV NCT Drg. HTD/ST-149 (if combined structure used) or 11 kV NCT Drg. HTD/ST-88R (if required). |
| 106 | EARTH WORK IN FILLING :1.1 Earth filling with good earth (as per satisfaction of Executive Engineer/Civil Works Division), laying in layers (as per specification), dressing, including carriage, irrespective of lead, loading, unloading, watering and compaction in layers with roller including compensation of earth complete in all respect. |
| 107 | 2. FOUNDATIONS:Supply of labour, T&P, material and construction of RCC footings & pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications & approved drawings including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work.A. GANTRY TOWERSi) CT-4 |
| 108 | ii) CT-5 |
| 109 | iii) CT-6 |
| 110 | iv) CT-8 |
| 111 | v) DT-2 |
| 112 | vi) DT-3 |
| 113 | B. EQUIPMENT 66kV sidei) 66KV LA |
| 114 | ii) 66KV PT |
| 115 | iii) 66kV CT |
| 116 | iv) 66kV L&E & Isolator |
| 117 | v) 66KV NCT |
| 118 | 11kV sidei) 11kV NCT |
| 119 | 3. BREAKER FOUNDATIONDesign, engineering, supply of labour, material, equipment & const. of foundations for breaker including all associated works PCC, RCC, structural steel, steel reinforcement & any other item not specifically mentioned herein but reqd. for completion of work as per tech. spec.i) 66 kV Breaker Foundation |
| 120 | 4. ROADSSupply of labour, material and construction of cement concrete roads and walkways/shoulders from NH/SH/etc. to Switch yard/Switch house building as per GELO/CLO as per sectional detail drawing no. HCD/SK-181 R1 and technical specification.i. 6.0m wide road (Near main gate of substation) |
| 121 | ii. 3.66m wide road |
| 122 | 5. CAPACITOR BANK FOUNDATIONSDesign, Engg. & supply of labour, material & construction of foundations for capacitor bank with capacitor unit (with allied equipments) & series Reactor etc. including chain link fencing 1.8M height around cap. bank complete in all respect including any other items not specifically mentioned herein but required for completion of job as per technical specification.i) 9000KVAR 12.65 kV Capacitor Bank |
| 123 | ii) 4800KVAR 12.65kV capacitor bank |
| 124 | 6. ROAD CULVERTDesign, Engineering and const. of Pipe culvert(s) at suitable locations under the approach road (from main PWD/ HUDA/Municipal/Village road to the sub-station entry point) including, cost of labour, material complete in all respects as per I.R.C. Standards.The successful bidder shall develop the designs & drawings as per the soil investigation report attached in specification and shall get these checked/vetted from any professsional institute as per contract before final approval. |
| 125 | 7. TRANSFORMER FOUNDATION7.1 Design Engineering & construction of transformer foundation including all associated works, RCC, PCC, reinforcement steel, misc. structural steel and other items not mentioned herein but required for completion of work as per technical specifications & approved drgs. In case extra foundation(s) has/have to be constructed (as per approved T/F drawing) to complete the job, nothing extra would be paid on this count.The successful bidder shall develop the designs & drawings as per the soil investigation report attached in specification and shall get these checked/vetted from any professsional institute as per contract before final approval.i) 25/31.5MVA,66/11kV T/F foundation complete in all respect. |
| 126 | ii) 12.5/16MVA,66/11kV T/F foundation complete in all respect. |
| 127 | Design, Engg., supply of labour, material and construction of foundation for station transformer including all associated works, RCC, PCC, Reinforcement steel, misc. structural steel and other items not mentioned herein but required for the completion of work as per technical specifications.The successful bidder shall develop the designs & drawings as per the soil investigation report attached in specification and shall get these checked/vetted from any professsional institute as per contract before final approval.11/0.4kV 200KVA Station T/F |
| 128 | 8.OUTDOOR CABLE TRENCHESSupply of labour, material such as cement, reinforcement steel, GI angles, flats, PCC & brick pillars below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers including associated works like Cable trench Culverts, crossings for roads and sumpit-cum-pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per approved trench layout plan, HVPNL drgs. & tech. specs. complete in all respect.i) D-type trench |
| 129 | ii) E-type trench |
| 130 | iii) F-type Trench |
| 131 | iv) G-type trench |
| 132 | v) GI Pipe |
| 133 | vi) Trench Culvert (The successful bidder shall develop the designs & drawings as per the soil investigation report attached in specification and shall get these checked/vetted from any professsional institute as per contract before final approval.) |
| 134 | vii) Sump Pit Cum Pump House |
| 135 | 9. SITE SURFACING9.1 Providing, supplying & laying 100mm thick in two layers of 50mm each of 20mm nominal size uncrushed/crushed/ broken stone pebbles gravel fill including dressing, rolling & compacting complete in all respects as per specs. & instructions of engineer incharge. |
| 136 | 9.2 Providing, supplying & laying 100mm thick PCC (1:4:8) using 20mm nominal coarse aggregates and supplying & spreading 100mm thick layer of 40mm nominal size uncrushed/ crushed/broken stone pebbles over the PCC including construction of toe wall (exposed wall plastered with cement mortar 1:5) to hold 40mm single size uncrushed/ crushed /broken stone pebbles wherever required in the bays covered under the present scope as detailed in the GELO & instructions of engineer incharge. The slope shall be kept as 1:500 for draining out the water. |
| 137 | 10. BOUNDARY WALL10.1 Supply of labour, T&P, material & construction of front, side, U/C boundary & U/C fencing below DPC level as per GELO/CLO, tech. spec. & HVPNL drg HCD/TS-1176 R-3 including excavation, PCC, brickwork, back filling, plaster, painting etc. complete in all respects. |
| 138 | 10.2 Supply of labour, material and construction of front, side, U/C boundary walls & u/c fencing above DPC including main gate foundations as per GELO/CLO, technical specifications. & HVPNL drg. complete in all respect.i) 6 ft. high U/C B/wall with barbed wire on angles at top. ( HCD/TS-1176 R-3 & JOB NO. 1358 Drg-02) |
| 139 | ii) 4½ ft. high front wall including providing grill at top of wall & construction of gate pillars. ( HCD/TS-1176 R-3 & JOB NO. 1358 Drg-01) |
| 140 | iii) 4½ ft. high side wall with barbed wire on angles at top of wall. ( HCD/TS-1176 R-3 & JOB NO. 1358 Drg-02) |
| 141 | iv) U/C fencing including GI angle iron posts and gate(s) complete as per electrical layout & tech. spec. & as per drawing attached. (HCD/TS-1024 R1) |
| 142 | 11. CONTROL ROOM BUILDINGThe design of control room building including architectural & structural drawings is in the scope of successful bidder. However, the floor plan layout shall be kept same as per GELO. Design engineering, supply of labour, material, T&P and construction of control room building complete in all respect as per tech. specs. including exterior weather proof paint, interior emulsion, all internal services like water supply including supply & providing of 5000ltr. capacity double layer Sintex/Diplast PVC tank, Sewerage system, electrification including wiring, modular switches, minimum 28W 4ft. long LED tubes & Sensor lights(motion-activated or light-sensitive) with fittings minimum 1960 lumens, ceiling/exhaust fans, 12 no. CCTV Camera (their Locations to be decided by concerned XEN), Finishing, Plinth protection, flooring, roofing with tile terracing, Indoor trenches, Soakage pit near the switch house building, connection of sewerage system to Soakage pit/Sewerage system of local authorities (as applicable), connection to main water supply system of local authority, bore (Tubewell) (as applicable) etc. & any other item not mentioned herein but required for completion of works. Further, all associated drawings related to control room building shall be evolved by the successfull bidder such as illumination,plumbing,soakage pit, Water Supply & Sewage plan etc or any other drawing required to complete the work.The successful bidder shall develop the designs & drawings as per the soil investigation report attached in specification and shall get these checked/vetted from any professsional institute as per contract before final approval. |
| 143 | 12. PARKINGDesign engineering, providing and laying 100mm thick factory made cement concrete interlocking paver block of M-35 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over (BIS 15658:2006) and including 60mm thick compacted bed of coarse sand, 100mm thick PCC 1:5:10, 100mm thick sand, filling the joints with line sand etc. all complete as per the in front, rear or side (as per site requirement of the switch house building) or as per the direction of Engineer-in-charge. |
| 144 | 13. DRAINAGE–CUM-RAIN HARVESTING SYSTEM13.1 Supply of labour, material for construction of recharge structures with bore well(s) as per HVPN drawings & specs. complete in all respect. The location of recharge structures shall preferably be located on corner(s) of the substation and shall be got decided from the concerned Engineer in-Charge on the basis of surroundings of the substation(s). In case ground water table is less than 8m from FGL, rain harvesting well shall not be constructed (the drainage system with sump pit is to be constructed as per item mentioned below). |
| 145 | 13.2 The successful bidder shall evolve design & drawing for drains, manholes with RCC covers and settlement tank including preparation of drainage layout drawing for disposal of rain water from building’s roof top & switch yard (s/stn.) area into respective bore well(s) in such a way that there shall be no ponding of water on the roof and switch yard (s/stn.). The layout so developed shall be got approved from the employer. The location of sump-pit-cum-pump chamber shall preferably be located on corner(s) of the s/stn. and shall be got decided from the concerned Engineer in-Charge on the basis of surroundings of the substation(s). The successful bidder will also supply labour and material for construction of sump-pit-cum-pump chamber as per HVPNL drgs. & provide one no. non clog pump(s) of 5HP of reputed make capacity with main switch, starter, volt meter, Amp. Mtr. etc. (for each sump pit) for disposal of excess water to outfall point. Any other item(s) not mentioned herein but is/are required for completion of works shall be done by the successful bidder without any extra cost to the employer.The successful bidder shall develop the designs & drawings and shall get these checked/vetted from any professsional institute as per contract before final approval.i) Drain Section-1 |
| 146 | ii) Drain Section-2 |
| 147 | iii) Drain Section-3 |
| 148 | iv) Road Crossing |
| 149 | v) Trench Crossing |
| 150 | vi) Sump Pit Cum Pump House |
| 151 | vii) RCC Hume Pipe |
| 152 | 14. CONSTRUCTION OF ANTI FIRE WALLDesign engineering & construction of RCC anti fire wall of suitable height between T/F and all associated works including supply of labour, material, cement, reinforcement steel, steel form work etc. as per technical specification.The successful bidder shall develop the designs & drawings as per the soil investigation report attached in specification and shall get these checked/vetted from any professsional institute as per contract before final approval. |
| 153 | 15. Dismantling of existing structures, boundary wall etc.Dismantling including substructure & superstructure of existing residential quarters, boundary wall,XEN residence,AE residence, OP division office, garrage, parking shed, rest house or other structure alocated within the land earmarked for the new substation construction. The material whatsoever shall be the property of the successful bidder. The dismantled material shall not be allowed for reuse at any of the sub-stations. |
| 154 | 16. RCC M-20 inclusive of labour, material, shuttering, steel reinforcement etc. complete in all respects to compensate excess quantity required to be executed due to difference in existing ground level and the formation level to be fixed after contouring or difference on account of revised drawing issued at the time of construction and the tender drawing. Please Enable Macros to View BoQ information |