| 1 | Deployment of Wireman Grade-II and Khallasi for Annual Lights Maintenance of Park Lighting as per Inventory and Terms & Condition attached. |
| 2 | Supplying and Replacement of Street Light LED Fixture Powder Coated Pressure Die Cast Aluminum body with driver as per the requirement with Driver Efficiency>85%, Input voltage: 140-270 Volt AC, Frequency 50/60 Hz, Operating Temp range-5°C to 50°C, Internal Surge Protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency>85%, THD<10% as per IEC 61000-3-2 , PF≥0.95, IP- 66, IK-10, CRI>70, Under Voltage and Over Voltage Protection, EMI-EMC As per CISPR 15, Lenses for Beam Angle as per IESNA type I/II/III as per the width of the road and the project requirement, suitable to fit in up to 65 mm dia. pipe, life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching)<5, Maximum Power Consumption should not more than the specified rating and Fixture shall be of relevant BIS Standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC Insulated Copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System Lumen Efficacy≥120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED Fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal Management: Heat Sink of Aluminum Housing such that LED Junction Temperature shall not rise above 90°C) including rebate for dismantle Fixture.45 Watt |
| 3 | Supplying and Replacement of Flood Light, Powder Coated Pressure Die Cast Aluminum body with built in or separate driver as per the requirement with Driver Efficiency>85%, Input voltage: 140-270 Volt AC, Frequency 50/60 Hz, Operating Temp range-5°C to 50°C, Internal Surge Protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency>85%, THD<10% as per IEC 61000-3-2 , PF≥0.95, IP-66, IK-10, CRI>70, Under Voltage and Over Voltage Protection, EMI-EMC As per CISPR-15, Lenses for Beam Angle 30°-120° as per the application and the project requirement, suitable tilt able Fitting, life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching)<5, Maximum Power Consumption should not more than the specified rating and Fixture shall be of relevant BIS Standard complete in all respect i/c connections with 1.5 sq mm FRLS/HFFR, PVC Insulated Copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System Lumen Efficacy≥120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED Fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal Management: Heat Sink of Aluminum Housing such that LED Junction Temperature shall not rise above 90°C) including rebate for dismantle Fixture.100 Watt |
| 4 | Supplying and Drawing of following sizes FRLS PVC Insulated Copper Conductor, Single Core Cable in the Existing Surface/Recess Steel/PVC Conduit as required.3C x 1.5 sq.mm |
| 5 | 3C x 2.5 sq. mm |
| 6 | 3C x 4 sq. mm |
| 7 | Supplying of following sizes of XLPE (Cross Linked Poly Ethylene) Insulated PVC Sheathed Alumimium Conductor Armoured Power Cable of 1.1 KV grade including connection, testing etc. as required including rebate for dismantle material.2C x 16 sq. mm |
| 8 | 4C x 25 sq. mm |
| 9 | 4C x 50 sq. mm |
| 10 | Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size in the Existing RCC/HUME/METAL Pipe as required.Up to 35 sq. mm |
| 11 | Above 35 sq. mm and up to 95 sq. mm |
| 12 | Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size Direct-In-Ground including Excavation and Refilling the Trench etc. as required, but Excluding Sand Cushioning and Protective Covering.Up to 35 sq. mm |
| 13 | Above 35 sq. mm and up to 95 sq. mm |
| 14 | Providing and Fixing 6 SWG dia. GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub-main wiring/cable as required. |
| 15 | Supplying and Laying of following size DWC HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS: 14930, Part-II complete with fitting and cutting, jointing etc. direct-in-ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia. (OD-63 mm & ID-51 mm nominal) |
| 16 | Supplying and making straight through joint with Heat Shrinkable Kit including ferrules and other jointing materials for following size of PVC Insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV grade as required.2C x 16 sq. mm |
| 17 | 4C x 25 sq. mm |
| 18 | 4C x 50 sq. mm |
| 19 | Supply and Replacement of Pole Connector Box made out of Glass Reinforced Polyester Sheet Moulding Compound Conforming to IS:13410-1992 Grade-S1 of Outside Dimensions 280 mm (H) x 170 mm (W) x 115 mm (D) (all the corners of the box should be round & not pointed ones) suitable to mount on 40/50/65/80 mm dia. GI Pole with the following Provisions/Accessories Mounting in Box etc. complete as required including rebate for dismantle material.a) 2 Nos. Clamps made out of 19 mm x 3 mm MS Strip of suitable Length for Mounting Box on the Pole.b) Water Tight Front Cover with 2 Nos. Stainless Steel Hinges & 1 No. Screw for Tightening.c) 4-Way, 220 V, 30 A, Dough Moulded Connector with SMC with Stainless Steel Inserts- 1 No.d) 16 A, Moulded SMC Rewireable Kit-Kat- 1 No.e) Suitable size Hole at suitable Location on Rear Wall for Cable & Wire Entry in the Connector Box.f) Earthing Bolt M6 x 20 mm.g) Neutral Link- 1 No. |
| 20 | Supplying and Replacement of following Control Gear/accessories in the Existing Installation for Electric Panel Board/Feeder Pillar, Motor Starter complete in all respect including connections with appropriate size FRLS, PVC Insulated Copper conductor single core cable and earthing etc. as required including rebate for dismantle Fixture.6 A to 32 A ratings, DP MCB, “C” curve, 10 KA breaking capacity. |
| 21 | 6 A to 32 A ratings, TP MCB, “C” curve, 10 KA breaking capacity. |
| 22 | 6 A to 32 A ratings, TPN MCB, “C” curve, 10 KA breaking capacity. |
| 23 | 63 A, FP MCB, “C” curve, 10 KA breaking capacity |
| 24 | 100 A, 30 KA, 4-Pole MCCB |
| 25 | 200 A, 36 KA, 4-Pole MCCB |
| 26 | Electronic/Analogue Timer of model FM1/Quartz Daily 110 VAC-240 VAC Base/DIN Mounting in the existing Panel. |
| 27 | 3-Pole Power Contactor of AC3 Rating 32 Amp, MNX 32 type. |
| 28 | Digging Out of 1 No. Faulty PVC Insulated, PVC Sheathed/XLPE Power Cable Laid Underground including removal of the fault and relaying of the same cable after repair, refilling of the excavated trench and redressing of the site (e.g., restoration of surface levels, leveling), and to compliance with safety standards. |
| 29 | Supply, Installation, Testing and Commissioning of Ceiling Fan with Brush Less Direct Current (BLDC) Motor, Class of Insulation: B, 3 Nos. Metal (Aluminium Alloy) Blades, 30 cm Long Down Rod, 2 Nos. Canopies, Shackle Kit, Safety Rope, Copper Winding, Steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (Tolerance as per IS: 374-2019), THD less than 10%, Remote (preferably mobile app based) for Speed Control and all remaining accessories including Safety Pin, Nut Bolts, Washers, Temperature Rise=75 °C (Max.), Insulation Resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, Single Phase AC Supply Ceiling Fan compliant to IS: 374-2019 fan i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200 mm, Service Value>6.0 CM/Min/Watt, Air Delivery 210 CM/Min (Minimum) |
| 30 | Supplying and Replacement of 4 mtr. high pole made out of 65 mm dia. NB, B-class GI pipe ISI marked duly welded with MS base plate of size 300 mm x 300 mm x 12 mm thick with stiffener of size 130 mm x 60 mm x 5 mm thick; top edge to be blunted with a horizontal flat>5 mm (No sharp edge), Supplying and Fixing of suitable size of Bracket for mounting the light fitting on the pole, suitable earth stud on base plate, making suitable size hole in pole at a height of 2.5 meter from base plate for cable entry/exit, painting & numbering of pole, making suitable size hole in base plate for cable entry/exit into the pole and fixing the pole on the existing foundation with the existing nuts-bolts, washers etc. complete as required including rebate for dismantle Pole. |
| 31 | Providing and laying in position, 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) reinforced cement concrete foundation of size450 mm x 450 mm x 1200 mm deep (900 mm below ground level and 300 mm above ground level) including excavation of earth, refilling, providing, cutting, bending and placing in position, reinforcement of cold twisted bars of 12mm dia.- 1200 mm long (approx.)- 8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia.- 1400 mm long (approx.)- 6 Nos. (with suitable spacing) including centering & shuttering as required with providing, fixing and positioning of one set of foundation bolts comprising of 4 Nos., 16 mm dia. 750 mm long J-Type MS bolts (Threaded portion shall be galvanized) along with 3 Nos. GI nuts and 2 Nos. GI washers etc. per bolt and 1 No. anchor plate (3 mm thick) of suitable size and providing 63 mm (OD) DWC pipe ISI marked for cable entry & exit etc. complete as required. |
| 32 | Painting of Existing GI Poles up to 4 to 5 meters in Height, applying Two Coats of Luxol Hi-Gloss Enamel-Colours including Red Oxide Primer, with Numbering of the Poles. This includes Painting the Base Plate and Mounting arrangements etc. complete as required. |
| 33 | Supplying and Replacement of floor mounted LT Feeder Pillar cubical type double door of size 1000 (H) mm x 900 mm (W) x 300 mm (D) with general arrangement made out of 2 mm thick MS CRCA Sheet having hinged gasket covers and screwed knobs with double locking arrangement & Locking Hooks and separate Rain Protection Cover with extension of 100 mm in Width & Depth, supported with MS Angle Iron legs and bottom frame of size 40 mm x 40 mm x 6 mm x 1 mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs (around 25% of length) should be covered with brick walls, duly 1:4 cement plaster, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles, ferrules wherever required, Painting with Primer, Numbering, Identification Plate of Component embossed and/or printed in Metal including Supply & Fixing of following accessories etc. complete as required (as per drawing approved by Engineer-in-Charge) including rebate for dismantle Feeder Pillar.a) 100 A, 30 kA Ics=100% Icu and Operational Voltage 690 V, 4 Pole MCCB- 1 No. (Incomer).b) Ammeter (0-100 A) 96 sq. mm in size and 100/5 CT’s Ratio- 1 Set.c) Voltmeter (0-500 V) 96 sq. mm in size with Selector Switch- 1 Set.d) Indication Lamp (RYB) with Control HRC Fuse with Fuse Fitting- 1 Set.f) 6 A to 32 A ratings, DP MCB, “C” curve, 10 KA breaking capacity- 1 No.g) 6 A to 32 A ratings, TPN MCB, “C” curve, 10 KA breaking capacity- 1 Nos.h) 63 A, FP MCB, “C” curve, 10 KA breaking capacity- 3 No.i) 200 A, 4-Strip Al. Bus-Bar of minimum 400 mm long and of size 30 mm x 5 mm with sleeve and nut-bolts- 1 Set.j) 200 mm x 150 mm MV Danger Notice Plate of 2 mm thickness- 1 No.k) Earthing Stud- 2 Nos.l) Lifting hook on the top of feeder pillar- 1 Set. m) Lamp Holder inside Feeder Pillar- 1 No.n) 4 Way Neutral Link- 2 Nos. |
| 34 | Hire Charges of Cable Fault Locating Machine with Skilled Operator for Underground LV Cable Fault Identification, including all testing equipment, safety precautions etc. as required. |
| 35 | Providing and Fixing MV Danger Notice Plate of 200 mm x 150 mm, made of Mild Steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single Red colour on front side as required. |
| 36 | Attending to complaints for Park Lighting Maintenance on Poles exceeding 10 meters in Height, utilizing Tower Wagon or Hydra, as received via Online Grievance Portals, VIP References, or other Communication Channels. This includes all required works (such as inspection, repair, and resolution) and covers to-and-fro Transportation Charges for the Hydra. |
| 37 | Repair, Maintenance and Fault Rectification of Park Lighting System during Odd Hours/Night Shifts, including Network Fault Diagnosis and to Remove Fault with safe handling. The agency has also to arrange staff at very short notice for this item without fail. |
| 38 | Earthing with GI Earth Pipe 4.5 meter long, 40 mm dia. including accessories, and Providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 39 | Providing and Fixing 25 mm x 5 mm GI Strip on surface or in recess for connection etc. as required. |