| Sl. No. | Item Description |
| 1 | Dismantling/taking down carefully aluminium/ copper point wiring (light, fan,socket or power) complete, including fixtures and fittings such as switches, ceiling roses, pendants, regulators , sockets, light fittings etc., removing materials to stores for keeping in safe custody for taking credit and making good the disturbed surfaces of walls,ceilings etc. complete all as specified and directed by Engr-in-Charge. |
| 2 | Material and labour for concealed point wiring using approved colour coding as per IS, with multi stranded copper conductor 1.5 sqmm (Nominal area), single core, FRLSH (FIRE Retardant Low Smoke and low Halogen), PVC insulated and unsheathed stranded cable drawn through and including non metallic,medium grade PVC concealed conduit not less than 20 mm dia and its fittings including all tees, bell mouth pieces and fixing accessories such as couplers, saddlers, pipe hooks etc, PVC junction boxeswith GI metal flushboxes made out of 1.2mm thick of any module from 2 to 18module confirming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly coated with two coats of anti corrosive paintincluding modular cover plates with frame i.e. inner and outer plate extended upto 25 mm over metal flush boxes for housing the modular switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbedsurfaces as per existing for one light / fan / Bell point contorlled by one switch including 1.5 sqmm single core PVC insulated and unsheathed FRLSH (FIRE Retardant Low Smoke and low Halogen) copper cable, 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor upto common earth and connecting to common earth dollywith suitable size of lugs for one light point/ fan point/bell point controlled by one switch complete all as specified and as directed by Engineer-in-Charge.NOTES:- 1. Switch, socket and fan regulators to be measured and paid for separately.2. All chases will be cut by chase cutter only. |
| 3 | Description all as per item No 2.00 here in before but for socket out let point 5 Amps on same board complete all as specified and directed by Engr-in-Charge. |
| 4 | Description all as per item No 2.00 here in before but for socket out let point 5 Amps on independentboard complete all as specified and directed by Engr-in-Charge. |
| 5 | Description all as per srl item No 2.00 above but point wiring for one socket out let 15&5 Amps (independent) controlled by one switchwith using 2.5 Sq mm (nominal area) stranded copper conductor complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply and fixing modular switches, one way,6 amps one module, 230V, 50 Hz supply, complete all as specified and directed by Engr-in-Charge. |
| 7 | Supply and fixing modularswitches, oneway, 16/20 Amps, one module, 230 volt , AC supply, complete all as specified and directed by Engr-in-Charge. |
| 8 | Supply and fixingmodular socket outlet 6 amps, 2/3 pin combined 2 module, 230 volt, complete all as specified and directed by Engr-in-Charge. |
| 9 | Supply and fixing modular socket outlet 6/20 amps,3 pin, 2 module,complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply and fixing fan regulator step type one module / 2 module, 100 W 230 Volts, 50 Hz,complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply and fixing modular switches, bell push,6 amps one module, 230V, 50 Hz supply, complete all as specified and directed by Engr-in-Charge. |
| 12 | Supply and fixing modular blanking plate 1 module complete all as specified and directed by Engr-in-Charge. |
| 13 | Material and labour for Point wiring with 1.50 Sqmm single core PVC insulated , unsheathed cable FRLSH, 1100 volt grade with multi stranded copper conductor drawn through in existing conduit not less than 20 mm dia with FRLSH )accessories, concealed on wall/ceilingand including provision of 1.50 Sqmm single core PVC insulated , unsheathed cable FRLSH 1100 volt grade with multi stranded copper conductorgreen colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken box or pressed steel terminal boxes made out of 1.2 mm thick mild steel sheet metal conforming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly and coated with two coats of anti corrosive paint over a coat of red oxide primer bothinternally and externally including provision of new 3 mm thick plastic laminated sheet top cover extended up to 25 mm over sunken box for housing the switches , socket outlets, fan regulators etc. with brass screws and brass washersand making goodthe disturbed surfaces as per existing for one light/fan point/bell point controlled by one switch. NOTES:- 1. Switch, socket and fan regulators to be measured and paid for separately . 2. All chases will be cut by chase cutter only. |
| 14 | Description all as per item No 13.00 here in before but for socket out let point 5 Amps on same board,complete all as specified and directed by Engr-in-Charge. |
| 15 | Description all as per item No 13.00 here in before but for socket out let point 5 Amps on independentboard,complete all as specified and directed by Engr-in-Charge. |
| 16 | Description all as per item No 13.00 above but with 2.5 Sqmm cable for 3pin 15 Amps switch socket outlet (Power Point),complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply and fixing switch piano 5 Amps, flush type, single pole, one way,230 volt , AC supply,, complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply and fixing switch piano 15 Amps flush type one way 230 Volts,50 Hz , AC supply, , complete all as specified and directed by Engr-in-Charge. |
| 19 | Supply and fixing bell push 5 Amps, flush type, single pole, one way, 230 volt , AC supply, , complete all as specified and directed by Engr-in-Charge. |
| 20 | Supply and fixing socket outlet 3 pin 6 amps, 230 volt. flush type, , complete all as speciied and directed. |
| 21 | Supply and fixing socket outlet 2 in 1, 6 pin 5 /16 Amp and multi pin flush type, complete all as specified. |
| 22 | Supply and fixing ceiling rose surface bakelite 65x50mm, 3 terminal,complete all as specified. |
| 23 | Supply and fixing fan regulator electronic step type ,230 Volts, AC supply, , suitable for ceiling fan any type/make/sweep, complete all as specified and directed by Engr-in-Charge. |
| 24 | Supply and fixing door bell electric ,ding dong /musical type, single phase 230 volts,complete all as specified. |
| 25 | Supply and fixing sheet metal enclosure SP with two pin and earth plug and socket inclduing metal clad topwith one single pole MCB 20 Amp complete all as specified and directed by Engr-in-Charge. |
| 26 | Supply and fixing in replacement of LED light fitting 1x20W , 220V, AC with Aluminium housing with batten type with driver , holder including 20W LED tube light, Cool White/Warm White, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/watt for connecting up with three core flexible copper conductor cable of suitablae size from celing rose to connector complete all as specifid and directed. |
| 27 | Supply and fixing in replacement channel for fixing of LED tube rod of CRCA body suitable for 18/20 watt LED tube, high efficient, AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. ( Tube rod shall be measured and paid for separately ).Note: - Channelmust be get approved from Engr in charge to check fesibilty i.e. one end contact or both end contact. |
| 28 | Supply and fixing in repair 18 W / 20WLED tube rod, environment friendly, high efficient, T8 with aluminium extrusion heat sink for optimum performance with high luminous efficiency and easy and taking down existing tube light and removal complete all as specified and directed by Engr-in-Charge. Note: - Tube rod must be get approved from Engr in charge to check fesibilty i.e. one end contact or both end contact for fixing in existing LED fittings . |
| 29 | Supply and fixing in replacement batten type withsurface mounted LED tube light fitting with high efficient diffuser mirror light, Aluminium housingin CRCA body suitable and including 10 watt LED energy efficient, AC 220-240 volts,duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/watt 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. |
| 30 | Supply and fixing in replacement bulk head light fitting, 10 watt, LED Energy efficient with provision of 2/3 core PVC copper conductor cable 0.5 Sqmm size from ceiling rose to light fitting completeincluding disconnecting and taking down old existing light fitting of any descriptioncomplete all as specified and directed by Engr-in-Charge. |
| 31 | Supply and fixing of LED lamp 9 watt B-22 base,,complete including taking down old existing lamp any type complete all as specified and directed by Engr-in-Charge. |
| 32 | Supply and fixing in repair ofbracket for security light made up of 25 mm dia suitable for security light, 0.9 metre long GI pipe,light grade, 120 degree bent to required length, fixed to wall with two clamps made of 20 x 3 mm mild steel flat minimum 15cm long, 4 nos 8mm dia bolts with nuts complete all as specified and directed by Engr-in-Charge. |
| 33 | Supply and fixing in replacement LED security light luminaire 30 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP66 protection, better optics for uniform distribution with multiplte LEDshaving optical grade polycarbonate lens with all accessories internally pre wired, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/watt and including connecting up with Two core 1.5 sq mmcopper conductor cable from connector to ceiling rose to connection of light including disconnecting and taking down oldunserviceable security light fitting of any description and in any positioncomplete all as specified and directed by Engr-in-Charge. |
| 34 | Supply and fixing in replacement LED security light luminaire 45 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP66 protection, better optics for uniform distribution with multiplte LEDs having optical grade polycarbonate lens with all accessories internally pre wired, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/watt and including connecting up with Two core 1.5 sq mmcopper conductor cable from connector to ceiling rose to connection of light including disconnecting and taking down oldunserviceable security light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. |
| 35 | Material and labour for sub main wiring with two single core FRLSH PVCinsulatedunsheathed copper conductor cable 6.0 sqmm drawnin and including rigid non metallic PVC medium grade 25mm dia New concealed conduit with accessories onwall or ceiling withone additional PVC insulated , strandedcopper conductor FRLSHof 6.0 sqmm,green colourfor earthcontinuity conductor including taking down old unserviceable sub main wiringand making good the disturbed surface complete all as specified and directed by Engr-in-Charge. NOTE: - 3 run of 6.0 sqmmcable with concealed conduct shall be measured as 1 unit. |
| 36 | All as per Item No 35.00 here in before but for Material and labour for sub main wiring of 4.00 sqmm. NOTE:- 3 run of 4.0 sqmmcable with concealed conduct shall be measured as 1 unit. |
| 37 | Material and labour for earthing with Galvanised Steel earth plate electrode 60cmx 60cm x 6.0 mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer ofcharcoal dust and common salt filling in alternate layers and electrode connections by usingGalvanised Iron wire 4mmas earthing lead(upto terminal point) by means ofbolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 15 mm diaGI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6)type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type ofsoil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 ofSSR 1991(Part-I) Taking out old unserviceable earthing complete all as specified and directed by Engr-in-Charge. NOTE : - The rates for earth work, GI protection pipe, funnel, wire wesh, CI cover, etc shall be deemed to beincluding in quoted rates. |
| 38 | Supply and fixing in repair sheet metal enclosures vertical distribution board VTPN,(MCCB DB) 4 ways, double door , 415 volts with 200 Amps rated bus bar IP 54 protection, with shrouded neutral bar and insulated bus bar and earth link, with and includingMCCB 4 pole thermal release type ,125AMPS ,25 KAas incomer and MCBsas out going complete with making suitable size of MS cabinet 1.2 mm thick dully grouted on the wall (flush) with opening arrangement including making connections with suitable size of lugs/thimbles/glands and making good the disturbed surface matching with existing surface including taking down existing unserviceable MCCB/DBs including MCBs complete all as specified and directed by Engr-in-Charge. Note: (i). Painting shall be done with Powder Coated Finish. (ii). PU (Polyurethene ) gasket shall be used in DB. |
| 39 | All as per Item No 38.00 here in before but VTPN DB alongwithMCCB 4 pole,100AMPS 16 KAas incomer and MCBsas out going complete all as specified and directed by Engr-in-Charge. |
| 40 | Supply and fixing in repairSPN distibution board 8 way, double door, IP 43, as per IS 8623including not less than 100 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles /gland/gaskets and making good the disturbed surface matching with existing surface including taking down existing unserviceable DBs including MCBs complete all as specified and directed by Engr-in-Charge.Note: (i). Painting shall be done with Powder Coated Finish. (ii). PU (Polyurethene ) gasket shall be used in DB. |
| 41 | Supply and fixing in repairSPN distibution board 4 way, double door, IP 43, as per IS 8623including not less than 100 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles /gland/gaskets and making good the disturbed surface matching with existing surface including taking down existing unserviceable DBs including MCBs complete all as specified and directed by Engr-in-Charge.Note: (i). Painting shall be done with Powder Coated Finish. (ii). PU (Polyurethene ) gasket shall be used in DB. |
| 42 | Supply and fixing in repair MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, \"B\" curve 6 to 32 Amps, ISIcomplete all as specified and directed by Engr-in-Charge. |
| 43 | Supply and fixing in repair MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, \"B\" curve 40 to 63 Amps,complete all as specified and directed by Engr-in-Charge. |
| 44 | Supply and fixing in repair MCB single pole and neutral 240 volts, 40 to 63 Amps,10KA, 50 Hz,\"B\" Series,complete all as specified and directed by Engr-in-Charge. |
| 45 | Supply and fixing in repairMCCB four pole 415 volts, 125 Amps,25KA, 50 Hz, thermal release adjustable type, ICS=ICU=100% complete all as specified and as directed by Engineer-in-Charge. |
| 46 | Supply and fixing in repairMCCB four pole 415 volts, 100 Amps,16KA, 50 Hz thermal releaseadjustable type, ICS=ICU=100% complete all as specified and as directed by Engineer-in-Charge. |
| 47 | Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections, one twin core cable circulat of size 10 Sqmm,including all incoming and outgoing connection with proper size of thimble complete all as directed and specified. |
| 48 | All as per Item No 47.00 hrere in before but one twin core cable circulat of size 06Sqmm complete all as directed and specified. |
| 49 | Material and labour for taking down existing lighting fiting any type/size/Make/capacity i.e T/L, Surface/ Recess Panel, flame proof, wall light, bulk head, mirror light etc and re-fixing the same after minor repair/cleaning including replacement connection wire with suitable size coper wire twin core 0.75 sqmm for connection from ceiling rose to light fitting complete all as specified and directed by Engr-in-Charge. |
| 50 | Material and labour for attending day to day complaints of E/M nature by means of checking unserviceable Electrical fitting and fixture and emergent fault rectification in elctrical circuit inclno light , earth leakage, short cicuit, neutral breakmains /sub mains/internal circuits of existing system of main building / block ,making continious electric supply including carrying out minor repairs etc as required to make system in order / functional by replacing, copper cable , copper thimbles, glands, earthing wire complete all as specified and as directed as required at site by Engineer-in-Charge. NOTE : - (a) Items reqd for replacement such as switchs, sockets for power/light/ fan/ bell/geyser points including complete will be measured and paid under respective items of BoQ. (b) Contractor rep/supervisor will report to MES Service Centrealongwith qualified/Experianced electrician and helper to collect dockets between 0900 hrs to 1000 hrs on all working daysfor rectification of complaints and resubmit the dockets after completion of each job on the same day.If contractor is failed to submit the docket within 48 hoursafter issuing of dockets , the contractor willliable to pay the penalty i.e. 50.00per docket per day till the re-submission of docket.if contractor failed to attend complaint or in absent situation for Electrician @ 500/- per day and for helper @300/- will be recovered from contractor.(c) Contractor will attend emergent nature of work i.e. no light, short circuit after working hours/holiday as when ordered. The rate of the is deemed to be included in above quoted rates. |
| 51 | Supply only switch piano 5 Amps, flush type, single pole, one way,230 volt, AC supply, , complete all as specified and as directed by Engineer-in-Charge. |
| 52 | Supply onlyswitch, single pole two way 6 Amps, 230 volts AC circuit, complete all as specified and as directed by Engineer-in-Charge. |
| 53 | Supply only switch piano 15 Amps flush type one way 230 Volts,50 Hz , AC supply,complete all as specified and as directed by Engineer-in-Charge. |
| 54 | Supply only bell push piano 5 Amps, flush type, single pole, one way, 230 volt , AC supply,complete all as specified and as directed by Engineer-in-Charge. |
| 55 | Supply only socket outlet piano 3 pin 6 amps, 230 volt. flush type, , complete all as specified and as directed by Engineer-in-Charge. |
| 56 | Supply only socket outlet piano 2 in 1, 6 pin 5 /16 Amp and multi pin flush type,complete all as specified and as directed by Engineer-in-Charge. |
| 57 | Supply only ceiling rose surface bakelite 65x50mm, 3 terminal, complete all as specified and as directed by Engineer-in-Charge. |
| 58 | Supply only fan regulator electronic step type ,230 Volts, AC supply, , suitable for ceiling fan any type/make/sweep, complete all as specified and as directed by Engineer-in-Charge. |
| 59 | Supply onlydoor bell electric ,ding dong /musical| type, single phase 230 volts, complete all as specified and as directed by Engineer-in-Charge. |
| 60 | Supply only lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings,complete all as specified and as directed by Engineer-in-Charge. |
| 61 | Supply only switch modular 6 amps, one way single module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type, complete all as specified and as directed by Engineer-in-Charge. |
| 62 | Supply only switch modular 16 amps, one way single module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type, complete all as specified and as directed by Engineer-in-Charge. |
| 63 | Supply only socket modular 6 amps, 5 pin combined universal socket 2 module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type, complete all as specified and as directed by Engineer-in-Charge. |
| 64 | Supply only socket modular 6/16 amps, 2 in 1, combined universal socket 2 module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type, complete all as specified and as directed by Engineer-in-Charge. |
| 65 | Supply only fan regulator step type one module / 2 module, 120W, 230 Volts, 50 Hz, AC complete with and including necessary frame and cover i.e. inner and outer plate as per existing make and type, complete all as specified and as directed by Engineer-in-Charge. |
| 66 | Supply only 6Amp bell pushmodularwith and including necessary frame and cover i.e. inner and outer plate as per existing make and type, complete all as specified and as directed by Engineer-in-Charge. |
| 67 | Supply only Fan condenser 2.5 mfd complete all as specified and as directed by Engineer-in-Charge. |
| 68 | Supply only Cable PVC copper conductor flexible twin core 0.75 mm, complete all as specified and directed by Engr-in-Charge. |
| 69 | Supply onlyMCB single pole, 240 volts, 50Hz , breaking capacity 10KA, \"B\" curve 6 to 32 Amps,complete all as specified and as directed by Engineer-in-Charge. |
| 70 | Supply only MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, \"B\" curve 40 to 63 Amps,complete all as specified and as directed by Engineer-in-Charge. |
| 71 | Supply only MCB single pole and neutral 240 volts,32 Amps,10KA, 50 Hz,\"B\" Series, complete all as specified and as directed by Engineer-in-Charge. |
| 72 | Supply only MCB single pole and neutral 240 volts, 40 to 63 Amps,10KA, 50 Hz, \"B\" Series, complete all as specified and as directed by Engineer-in-Charge. |
| 73 | Supply only 3 pin Top plug, 16 Amp , 240 volts AC ,complete all as specified and directed by Engr-in-Charge. |
| 74 | Supply only metal clad top plug, AC Plug, 20 Amp, 230 Volt AC complete all as specified and directed by Engr-in-Charge. |
| 75 | Disconnecting and taking down old existing wall light fitting of any description and in any position and Supply and fixing aesthetically designed wall bracket light of metal base with glass and B22 holder including 7 watt LED lamp Warm White & clear diffuser including connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed by Engr-in-Charge. |
| 76 | Supply and fixing in repair post top lantern LED 30/35 W , cast aluminium spigot, with high effieient LED light, with poly carbonate diffuser, complete with high efficient LED 30/35 W and accessoriesinternally pre wired, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/watt and including connecting up with three core 1.5 sqmm flexible copper conductor cable including disconnecting and taking down existing light fitting and removal complete all as specified and directed by Engr-in-Charge. |
| 77 | Supply and fixing of LED based Bollard light 10 watt with aluminium pipe housing with glare free PMMA Diffuser, IP 65,, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/wattincluding necessary excavation & PCC work etc complete including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. |
| 78 | Disconnecting and taking down old existing recess/surface mounting ceiling light fitting of any description and in any position and Supply and fixing surface/ recess mounting LED slim square/round down lighter 10/15 W LED with high efficient LEDs glare free opal diffuser madeup of PDC AL with IP 20 Protection ,PF not less than 0.9, including connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed by Engr-in-Charge. |
| 79 | Supply and fixingLED Highbay light fitting 120 watt , pressure die casthousing,IP 65/66 protection, better optics for uniform distribution with multiplte LEDssuitable for ceiling suspended mounting with system efficiency upto 120 lm/W withall accessories internally pre wired and including connecting up with Two core 1.5 sq mmcopper conductor cable from connector to ceiling rose to connection of light including disconnecting and taking down oldunserviceable security light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. |
| 80 | Supply and fixing in repair driver for bollard light, recess/ ceiling light of 10 to 20 watt of suitable size and easy installation as per existing make all as specified and as directed. |
| 81 | Supply and fixing in repair driver for post top lantern and security light ofof 30 to 45 watt of suitable size and easy installation as per existing make all as specified and as directed. |
| 82 | Supply and laying of LT undergroung cable, XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty), 1100 volts grade, with stranded aluminium conductor of size 6 Sqmm 2 Core, with suitable size of PVC Concealed/ surface conduit alondwith necessay fixing accessories (for Gate lights, Garden Lights and Garrage) complete all as specified and directed by Engr-in-Charge. |
| 83 | Supply and fixing for GI protection pipe of 40mmdia light grade for cable protection including all fittings laid in trenches or fixed on pole, complete all as specified and as directed by Engineer-in-Charge. |
| 84 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes, laying of cableetc not exceeding 10 Square metre on plan and getting out in soft/loosesoil complete all as specified and as directed by Engineer-in-Charge. |
| 85 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in soil of any description, complete all as specified and as directed by Engineer-in-Charge. |
| 86 | Removing excavated soil to a distance not exceeding 50 metre and deposited where directed at a level not exceeding 1.5m above the starting point, complete all as specified and as directed by Engineer-in-Charge. |
| 87 | Material and labour for unwashed dry sandcushioning for cable protection ,filling in trenches/ducts, complete all as specified and as directed by Engineer-in-Charge. |
| 88 | Material and labour for old size bricks sub class \"B\" for cable protection laid along length of cable complete all as specified and as directed by Engineer-in-Charge. |
| 89 | Material and labour for taking down existing light fitting of any type alongwith GI pipe/ pole of any dia / any size and Supply and fixing of MS pipe (Hot dipped Galvanized) decorative pole in two sections i.e Top pipe not less than 75 mm outside dia x 1500 mm long and Bottom pipe not less than 110mm outside dia x 500 mm long, thickness of pipe not less than 3 mm with base plate 250 x 250 x 12mm thick having 14mm dia hole for fixing of foundation \"J\" bolts of size 12mm dia x 450 mm \"J\" including 115 x 200 mm long utility window in pole, fixing of suitable size nuts/bolts and washers including Tripple layer metallic PU paint (Etching, Epoxy & PU) having Embalishment aluminium castiing suitable for and alongwith 30/35 Watt Warm white LED post top lantern IP 65 environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs clear cover offers bright illumination including all fixing accessoreis including necessary excavation, removal and PCC 1:3:6 work as directed etc complete all as specified and directed by Engr-in-Charge.Note :(i) Quoted rates shall be inclusive of excavation, taking down existing pole, all fixing acessories & PCC 1:3:6 for fixing of pole & post top lantern.(ii) Drawing of pole must get approved before installation..(iii) MS pipe of pole (Top & Bottom) should beas per latest standard. |
| 90 | Supply, laying and testing cable XLPE Insulated ,armoured, heavy duty electric cable 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core, including taking down exising service wire of any size all as specified and directed. |
| 91 | Supply and fixing ,Air ventilator made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200 copper winding of sweep 250 mm including taking down existing fan all as specified and directed. |
| 92 | Supply and fixing recess/ surface mounted LED flat panel 2\" x 2\" with high efficient LEDs and glare free full decorative light fitting, energy efficient provided withincluding LED36 watt, Cool White / Warm White, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/watt withprovision of 2/3 core PVC copper conductor cable 1.5 Sqmm size to light fitting and completeincluding disconnecting and taking down existing light fitting and removal complete all as specified and directed by Engr-in-Charge. |
| 93 | Supply and fixing LED flood light highly efficient integral type, made of pressure die cast aluminium housing with 10 KV SPD lens & toughened glass IP 66, energy efficient provided withincluding LED50 watt LED, duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/wattwithprovision of 2/3 core PVC copper conductor cable 1.5 Sqmm size to light fitting and completeincluding disconnecting and taking down existing light fitting and removal complete all as specified and directed by Engr-in-Charge. |
| 94 | Supply and fixing LED flood light highly efficient integral type, made of pressure die cast aluminium housing with 10 KV SPD lens & toughened glass IP 66, energy efficient provided withincluding LED100 watt duly marked with relevent IS, PF not less than 0.9,lumen efiicacy not less than 100 lumen/wattwithprovision of 2/3 core PVC copper conductor cable 1.5 Sqmm size to light fitting and completeincluding disconnecting and taking down existing light fitting and removal complete all as specified and directed by Engr-in-Charge. |
| 95 | Supply and fixing of LED based Bollard light not less than 15 Watt with aluminium pipe housing with glare free PMMA Diffuser, IP 65 of height not less than 1000mmand dia not less than 65mm, ,PF not less than 0.9,lumen efficacy not less than 100 lumen/watt including necessary excavation & PCC work etc complete including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. |
| 96 | Supply and fixing LED Picture Light of 5-7 Watt,Warm White , 220-240 V AC Supply,Aluminium housing Bronze/Silver finish, flexible neck for adjustable beam, size not less than 300 mm, connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connectorof the light including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and directed by Engr-in-Charge. |
| 97 | Supply and fixing MCB DB4 way TPN double door powder coated complete alongwith 200 Amp rated Bus bar, 415 Volts rated bus bar IP 43 protection, suitable forMCB 4 Pole 63 Ampas incommer. Note: Thimble/lugs of rating of MCB TPN should be used with wire for fixing in the MCB. complete all as specified and directed by Engr-in-Charge. Note: (i). Painting shall be done with Powder Coated Finish. (ii). PU (Polyurethene ) gasket shall be used in DB. |
| 98 | Supply and fixing MCB TPN63 Amps,440 volt,10 KA \"B\" curve, complete all as specified and directed by Engr-in-Charge. |
| 99 | Material and labour for taking down ceiling fan of any size/ sweep after disconnecting the wire from existing ceiling rose dismantaling of blades and deposit to store for repair all as specified and directed. |
| 100 | Supply and fixing in repair fan condencer 2.5/ 4MFD, 240 volts suitable capacity for ceiling/ exhaust Fanall as specified and directed. |
| 101 | Supply and fixing in repair ball bearing of suitable size and capacity, for ceiling/ Exhaust fan all as specified and directed. |
| 102 | Supply and fixing in repair shaft of suitable size and capacity for ceiling/ Exhaust fan all as specified and directed. |
| 103 | Supply and fixing in repair hanging assembly set comprising with rubber reel, MS clamps, nuts, bolts with one lock hole and lock pins,canopy suitable for any type of fans & down rods complete all as specified and directed by Engr-in-Charge. |
| 104 | Material and labour for painting of ceiling fanusing synthetic enamel paint in two coat over one coat of primer of any make/sweep/model etcafter cleaning/washing and fill up cavities using filler complete all as specified and directed by Engr-in-Charge. |
| 105 | Material and labour for hanging only ceiling fan any type/sweep after repair and connecting up including provision of cable from ceiling rose to connector to fan including refixing of blades all as specified and directed. |
| 106 | Material and labour for rewinding of ceiling fan of any size with super enameled copper wire of existing gauge incuding varnishing and drying complete reassembling & testing complete of size 1200/ 1400 mm sweep complete all as specified and directed by Engr-in-Charge.NOTE : -(i) Fans to be repaired/ rewinded will be handed over to contractor at MES store yard after cutting the burnt winding in presence of Engr-in-charge and cost of cutting of winding shall be included in the quoted rate.(ii) The cost of shifting the fan from MES store yard to contractors workshop andback shall be included in the item.(iii) Fans will be issued to the contractor in lots of 10 Nos and more for which, contractor shall ensure that minimum lot of 10 number each be returned to the department on every fifth day from the issue of fans after carried out rewinding and other repair,in failing so, the amount @ Rs. 20/- per fan per day shall be deductedfrom the contractor due till the returning of fan duly tested. |
| 107 | Supply and fixing of GI fan rod 600 mm long , 15 mm dia medium duty with superior quality and nut and bolts with locking arrangement complete with all as specified and directed by Engr-in-Charge. |
| 108 | Supply and fixing of GI fan rod 1.0 meter long , 15 mm dia medium duty with superior quality and nut and bolts with locking arrangement complete with all as specified and directed by Engr-in-Charge. |
| 109 | Material and labour for taking down Exhaust fan / wall mounted fan of any size/ sweep after disconnecting the wire from existing ceiling rose dismantaling of blades and deposit to store for repair all as specified and directed. |
| 110 | Material and labour for rewinding of Exhaust fan/Wall Mounted Fan of any size with super enameled copper wire of existing gauge incuding varnishing and drying complete reassembling & testing complete of size 230 to 450 mm sweep complete all as specified and directed by Engr-in-Charge.NOTE: -(i) Fans to be repaired/ rewinded will be handed over to contractor at MES store yard after cutting the burnt winding in presence of Engr-in-charge and cost of cutting of winding shall be included in the quoted rate.(ii) The cost of shifting the fan from MES store yard to contractors workshop andback shall be included in the item.(iii) Fans will be issued to the contractor in lots of 10 Nos and more for which, contractor shall ensure that minimum lot of 10 number each be returned to the department on every fifth day from the issue of fans after carried out rewinding and other repair,in failing so, the amount @ Rs. 20/- per fan per day shall be deductedfrom the contractor due till the returning of fan duly tested. |
| 111 | Supply and fixing in repair metal fan blade including fixing mountings and accessories of exhaust fan of 230 to 450 mm sweep complete all as specified and directed by Engr-in-Charge. |
| 112 | Material and labour for re-fixing only exhaust fan any type/sweep after repair and connecting up including provision of cable from ceiling rose to connector to fan including refixing of blades, louvers etc all as specified and directed. |
| 113 | Taking down old unserviceable geyser of cap 25 ltrs including all necessary electrical/water connection and keeping in safe custody for reuse inciuding all necessary minor repairs /servicing etcand checking serviceability of parts, necessary cleaning & reassembling the geyser, making necessaryadjustment and refixing the repaired geyser in position, connecting to existing electric & water connectionsand testing at site complete all as specified and directed by Engr-in-Charge. Note : The cost of minor repair including following works deemed to be included in quoted rates. (a) Inspection of geyser after opening bottom cover plate.(b) Examine any water leakage from geyser/storage tank.(c) Carry out operation of all stop cocks, pressure reducing valves,etc. to ensure free movement of the working parts.(d) Replace washers and glands to ensure smooth functioning. (e) Inspect vent pipes and remove blockage obstruction if any. (f) Check and correct earth continuity of electrical items.(g) Check and correct temperature setting of thermostats. (h) Items reqd for replacement will measured under respective item of BOQ. |
| 114 | Description all as per Item No 113.00 here in before but for gayser of cap 35/ 50 ltrs capacity complete all as specified and directed by Engr-in-Charge. |
| 115 | Supply only heating element of capacity 2 KW of geysers of any makecomplete all as specified and directed by Engr-in-Charge. |
| 116 | Supply only apparatus plate assembly with rubber gasket including nuts, bolts, washers for geysers of 50/35/25 ltrs capacity, complete all as specified and directed by Engr-in-Charge. |
| 117 | Supply only thermostatsuitable for the Geysers 25 ltrs capacity, 20 Amps, 240 Volts AC, adjustable type, 210 mm long or nearest size as per sample complete all as specified and directed by Engr-in-Charge. |
| 118 | Supply only thermostatsuitable for the Geysers 50 ltrs capacity,20 Amps, 240 Volts AC, fixed type,300 mm long or nearest size, Set at 90+/-6 degreeC as per sample complete all as specified and directed by Engr-in-Charge. |
| 119 | Supply only temperature resistent SS braided pipe suitable to sustaine pressure up to 8 barnot less than 60 Cm long suitable forout going / Hot water connections of Geyser with washer etc. complete as an directed. |
| 120 | Supply only Non-return valve 15mm / 20mm dia of brassas per requirement complete all as specified and directed by Engr-in-Charge. |
| 121 | Supply onlyIndicators of Geysers of any capacity/type (Red & Green) as per requirement complete all as specified and directed by Engr-in-Charge. |
| 122 | Supply only Geyser storage inner tank made out ofstainless steel sheet suitable for 25 ltrs capacitycomplete all as specified and directed by Engr-in-Charge. |
| 123 | Supply only geyser storage inner tank made outof stainless steel sheet suitable for 50 ltrs capacity complete all as specified and directed by Engr-in-Charge. |
| 124 | Supply only safety valve plug made out brass metal with fusible lead, inner thread type suitable for geyser of any type/capacity complete all as specified and directed by Engr-in-Charge. |
| 125 | Supply and fixing in repair copper cable PVC insulated and PVC sheathed flexible size 2.5Sqmm 3 core, complete all as specified and directed by Engr-in-Charge.(Cable shallbe in suitable length as per site requirement). |
| 126 | Supply and fixing in repair PCB unit of suitable size for BLDC Ceiling fan of 1200mm sweep as per make of ceiling fan, single phase, 240 V complete all as specified and directed by Engr-in-Charge. |
| 127 | Supply and fixing surface mounted LED flat panel 1\" x 4\" with high efficient LEDs and glare free full decorative light fitting, 36 watt, energy efficient provided withincluding LED36 watt withprovision of 2/3 core PVC copper conductor cable 1.5 Sqmm size to light fitting and completeincluding disconnecting and taking down existing light fitting and removal complete all as specified and directed. |
| 128 | Supply and fixing LED Decorative,wall mounting light, brushed nickel finish fixture with Opal Glass diffuserwith 2 x 9 W LED Lamp/lamp B22 base. including connecting up with driver three core flexible copper conductor cases of suitable size complete. |
| 129 | Supply and fixing recess/ surface mounted LED flat panel 2\" x 4\" with high efficient LEDs and glare free full decorative light fitting, 72 watt, energy efficient provided withincluding LED72 watt withprovision of 2/3 core PVC copper conductor cable 1.5 Sqmm size to light fitting and completeincluding disconnecting and taking down existing light fitting and removal complete all as specified and directed by Engr-in-Charge. |
| 130 | Supply and fixing in replacement of heavy duty PVC body wall mouting fan 400 mm sweep with corrosion resistant PVC body minimum noise, operation and maintance free designtotally enclosed highly efficient heavy duty motorwith pressure die cast aluminumrotor mounted on two ball bearings aerody namically contoured blades rigid frame ,1400 RPM PVC blades and testingcomplete all as specified and as directed by Engineer in Charge. |
| 131 | Material and labour as in repair for test point terminal block made of gun metal or phosphorus bronze, size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex. Head screws moundted on PVC insulator complete all as specified and directed by Engr-in-Charge. |
| 132 | Supply and fixing as in repairaluminium strip 25 X 3 mm with saddle and fixing screw etc for roof conductor and down conductors above ground, complete all as specified and directed by Engr-in-Charge. |
| 133 | Supply and fixing as in repair of Air termination, single pointed,aluminium rod 12mm dia and 300mm long complete all as specified and directed by Engr-in-Charge. |
| 134 | Material and labour for earthing with Galvanised Steel earth plate electrode 60cmx 60cm x 6.0 mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer ofcharcoal dust and common salt filling in alternate layers and electrode connections by using32x6mm GI stripby means ofbolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 15 mm diaGI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6)type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type ofsoil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 ofSSR 1991(Part-I) Taking out old unserviceable earthing complete all as specified and directed. NOTE : - The rates for earth work, GI protection pipe, funnel, wire wesh, CI cover, etc shall be deemed to beincluding in quoted rates. |
| 135 | NOTE:- Amount of credit ofRs. 1,06,012.00 for retrieved materials is mentioned in Schedule of Credit Page No 19& 20 of tender documents in pdf form which will be deducted offline while acceptance of tender. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail