| 1 | Repair / maintenance of lifts including carrying out daily check and periodical services of automatic electrical lifts 08 PS (544kg) at Sanik Aaramghar(G+4) floors havingpower operated doors and micro processed collective control system with VVV drive with repair and replacement of unserviceable parts such as bearings, bushes, all types of shoes, headers, hangers, door cards, door locks, control cards, connector/links, hall push buttons covers, rewinding of motor, welding of crecked/broken parts, repair/replacements of door safety edge working at any principal and any type sensor or mechanical safety lock, magnetic lock or control, COP buttons, car position indicator door sill, car door sill, shaft wiring cables, cabinfan,cabin light, etc complete to ensure safaty and smooth operation of lift and all as directed by Engineer in Charge. total Lifts -02 Nos. Note : -Annual inspection/ Half yearly of lift Inspector to be done Payment included in the quoted rate. LOC: Lift No. 1 & 2. |
| 2 | Dismantling and taking out all existing old defective sensor and supply and fixINFRA RED safety edge with power unit fitted on car door to safe guard passenger entering and leavingthe lift suitable for Passsenger lift and 800/900 mm x 2000 mmdoor opening all asspecified and directed. LOC: Lift No. 2. |
| 3 | Replacement of old main steel wire rope with new steel wire rope, 16 mm dia ungalvanised, 8/19 construction including connection with counterweight, pulley and car cabin etc. with conforming to IS 14665 latest, Make -Usha Martin complete all as specified and directed. |
| 4 | Disconnecting & Taking out defective unserviceable main drive (any type) from existing control panel and supply and fixing new main drive VVVF drive upto 7.5 KW/10 HP in Sanik Aaram Ghara common Lift 08 PS Auto door complete with all electric connection of following capacities complete all as specified and directed. Make :- Yasakava/ FUJILOC: Lift No. 1. |
| 5 | Replacement of existing unservicable shaft wiring in hoist way with new shaft wiring in hoist way upto lower limit switch with PVC insulatedwith multi standard copper conductor 0.75sgmm & 01 sgmm for earthing, 1100volts grade drawing through in and including galvanised sheet metal trunking (24Swg) up to ground floor in hoist way for control of all floor hall push button assy, limit switches, terminal switches, fireman switches etc completeall duly earthed at all points,suitable for Lift complete all as specified and directed. LOC: Lift No. 1 & 2. |
| 6 | Dismantling and taking out old architrave from landing door complete all as specified and directed. |
| 7 | Material & labour for 16-18mm thick mirror polished black granite slab, machine cut mirror polished cladding with chamfered/rounded edges approved decorative design including necessery PCC work granite slab & jointing in cement slurry and pointed in white cement mixed with pigement to match with shade of granite for lifts architrave at all floors for vajrabahu Goods lift complete all as specified and directed. |
| 8 | Dismantling and taking out unserviceable landing door supply and fixing new landing door comprise of 02 No power operated 800 mm centre opening by horizontal sliding stainless steel panel 18 SWG 1.2 mm thick with hair line finish, flush type panel complete with hangers, headers gate lock aluminiumsill etc for 08 Passanger Lift (554 Kg) complete all as specified and directed. LOC: Lift No. 2. |
| 9 | Dismantling and taking out unserviceable travelling cable from hoist way and supply & fixing new travelling cable PVC insulated 16core flat/round type with multistranded copper conductor 1100 Volts grade of size 0.75Sqmm confirming to IS and including thimbless suspended type freely move with car cabin up and down movements between ground and upper floors including necessary proper connectiion with Mid way junction and other connection required in circuit complete for passenger & Goods Lift of Naval Dockyard complete all as specified and directed. LOC: Lift No. 1 & 2. |
| 10 | Taking out unserviceable cabin fan from car cabin and supply and fix new cabin fan non -oscillating type axial flow, single speed 300mm sweep, 240 volts ISI mark with aluminium powder coated grill complete all asspecified and directed by Engineer in Charge Make - EMCO/VBM/CINI for lifts in various locations complete all as specified and directed. |
| 11 | Dismantling and taking out unserviceable &provision of new ARD control system, by supplying, Testing & commisioning of new UPS based, ARD system consists of contactors, IGBT card, battery charger, control card, power transformer etc. assembled in M.S. sheet powder coated with hinged doors & foot mounted cabinet suitable for existing 10.0 KW capacity Induction AC motor & compatibleincluding wiring with connected items in existing 544 Kg (8 Passangerlift 415V,50 HZ, 3 phase with Exide Make maintenance free batteries 12 V 18 AH for ARD. LOC: Lift No. 1. |
| 12 | Supply and Fixing in replacement of Contactor 10-20 Amps of lifts as per existing complete all as specified and directed. |
| 13 | Material & Labour for Rewinding of induction motor of capacity 5.0KW/6.8 HP with super enamelled copper winding wire of existing guage/dia including necessory insulating material, varnishing etc including taking out from site to workshop and return back after repair & re-installing complete all as specified and directed. LOC: Lift No. 1. |
| 14 | Supply & Fixing in repairdoor safety lock set for auto door suitable for lifts complete all as specified and directed. |
| 15 | Supply & Fixingin replacement of gate bearing suitable for lifts complete all as specified and directed. |
| 16 | Supply & Fixing in replacement ofgate shoe complete as recommended as per manufacturer cateloge/Model complete all as specified and directed. |
| 17 | Supply & Fixing in replacement ofbreak shoe suitable for lifts complete all as specified and directed. |
| 18 | Supply & Fixingin replacement ofcounter shoe suitable for lifts complete all as specified and directed. |
| 19 | Supply & Fixing in replacement ofspeed governor rope of size 8.0 mm dia suitable for lifts as per existing complete all as specified and directed. |
| 20 | Supply & Fixing in replacement ofdoor shoe complete as per existing manufacturer manual/catelogue. |
| 21 | Supply & Fixing in replacement ofRecess mounted ultra bright compact 5 watt LED down lighter with high efficacy LEDs, ideally suited for low ceiling area to give glare free light complete all as specified and directed. |
| 22 | Material and Labour in replacement of old unserviceable floor matting of car cabin by Marbonite/Granite 10mm thick as approved by the Garrison Engineer all as directed at site |
| 23 | Material and Labour for preparing, scraping the old painted surfaces and applying two coat of approved colour synthetic enamelled paint in machine room on all accessories includingmarking /stencil writing of MES number, Location, Capacity, Sl No etc with white synthetic enamelled paint complete all as specified and directed. |
| 24 | Supply and Fixing in replacement of Stop Switch/ Pause siwtch as per existing make for lifts complete all as specified and directed. |
| 25 | Supply and Fixing in replacement of Emergency alarmas per existing make for lifts complete all as specified and directed. |
| 26 | Supply and Filling of Gear oil 90W in gearbox of lifts complete all as specified and directed. |
| 27 | Supply & Fixing in replacement ofLimit switch set as per existing make complete all as specified and directed. |
| 28 | Supply and Fixing in replacement of SMPS power supply as per existing make for lifts complete all as specified and directed. |
| 29 | Supply and Fixing in replacement of REED Switchas per existing make for lifts complete all as specified and directed. |
| 30 | Supply and Fixing in replacement Serial card suitable for lift as per existing complete all as specified and directed. |
| 31 | Supply and Fixing in replacement ofrelay card for main card as per existing make for lifts complete all as specified and directed. |
| 32 | Supply and Fixing in replacement of main card as per existing make for lifts complete all as specified and directed. |
| 33 | Supply and fixing in replacement MCCB TP 160 Amps, 415 Volts,10 KA, 3 pole , Ics=100% Icu, including complete all as specified and directed. |
| 34 | Supply and fixing in replacement MCB TPN 63 Amps, 415 Volts,10 KA, 4 pole including complete all as specified and directed. |
| 35 | Dismantling andtaking down old u/searthing complete with galvanisedearth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m belowground level with top edge of the earthplate not less than 1.5m belownormal groundlevel, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GIprotection pipe (light grade), funnel, wire mesh,cast iron cover andframe etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed.Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way.(ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC.(iii) On testing after completion if the desired earth resistanceis more than 2Ώthe earthing will be redone at no extra cost. |
| 36 | Supply and laying, connecting and testing XPLE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 35 sqmm 3.5 core including Aluminium thimbles laid in trenches/on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall indcluding dismantling and taking down of old unsv cable complete all as specified and direcred. Note :- (i) Earth work, sand, bricks removing, returning filling will be paid seperately. (iii)All equipments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost. |
| 37 | Note:-Amount of credit ofRs.28000.00 for retrieved materials is mentioned in Schedule of Credit Page No. 17 & 18 of tender documents in pdf form which will be deducted offline while acceptance of tender. |