| Sl. No. | Item Description |
| 1 | LIST OF WORKS (Schedule A Part I to Part XV) |
| 2 | Total amount of Sch \"A\" Part-I (Building Works) brought forwarded from sl page No 26. |
| 3 | Total amount of Sch \"A\" Part-II ( Foundation for DG set) brought forwarded from sl page No 28. |
| 4 | Total amount of Sch \"A\" Part-III (Fire main system) brought forwarded from sl page No 30. |
| 5 | Total amount of Sch \"A\" Part-IV (Demolition & Dismantaling) brought forwarded from sl page No 31. |
| 6 | Subtotal |
| 7 | Sch \"A\" Part- V (MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only. |
| 8 | FIRE SUPPRESSION SYSTEN |
| 9 | Supply,Installation,testing&CommissioningofMicroprocessorbasedAnalogue addressable fire alarm control panel. panel shall have below specifications:1) Combination of 120 Detectors & Devices per SLC loop.2) expandable up to min. 1loops.3) Minimum 40 x 4 Characters LCD display.4) Networkable - Modules shall be considered ( OFC/copper )5) Auto Dialer upto 5 numbers. ( vendor shall consider the auto dailer )6) Auto Programming Day and Night Mode7) Enable and Disable function8)FM Approved.9) Advanced user friendly programming software including ‘Fuzzy Logic’.Operateson120to220VAC,60/50Hz.OperatingTemperature0°C-49°C/95% relative humidity RH (non-condensing) .Built-in Alarm, Trouble, Security, and Supervisory relays, with 24Hrs Normal Condition 1Hrs Alarm Condition battery backup & mounting accessories as per site conditions. Quote rate shall be included required network/communication modules.Scope of work includes cutting the false ceiling, drilling the holes, laying the cables as per site conditions etc. |
| 10 | 1Loop |
| 11 | SupplyInstallation,Testing&Commissioningof Analogue Addressable type Optical Smoke & Heat Detectors(Multisensor) with required mounting base and back box |
| 12 | Supply,Installation,Testing&Commissioningof AddressablepulltypeManual call point/resettablewhich is used for manually trigger a fire alarm suitable for interconnecting to the loop technology directly. |
| 13 | Supply,Installation,Testing&Commissioningof Soundercumstrobesmultitonesounder. |
| 14 | Supply, Installation , Testing & CommissioningofAddressable Control Modules with requiredbatterybackupandPowerSupplyUnits.Withrequiredbackbox. |
| 15 | Supply,Installation,Testing&Commissioning ofAddressableRelayModulesfor third party integration. ( for Smoke extraction & ventilation fans ) With required back box. |
| 16 | Supply, Installation , Testing & Commissioningof Addressable Monitor Modules.(for third party integration) . With required back box. |
| 17 | Supply, Installation , Testing & CommissioningofFaultIsolatorModule with required back box. |
| 18 | Supply and fixing of 2 core x1.5 Sq.mmFRLS Copper conductor Armoured shielded typefire rated lowsmoke multi-stranded,copper conductorcable.(includes terminationand testingof loop into device) ( for loops & Hooters ) |
| 19 | Supply and fixing of3 core x1.5 Sq.mmFRLS Copper conductor Armoured shielded type Power cable multi-stranded, copper conductor cable.(includes termination and testing of loopinto device) ( for control modules/FZM ) |
| 20 | Supply, Installation, Testing and commissioning of Tube based fire suppression cleanagent systemconsistof 4Kgcylinderfilled withHFC227eacleana gent gas, cylinder shall be local approved, HFC227ea must be UL Lited and all fixing accessories, Selection of system design and implementation shall be as per IS 15493/BIS 6382/NFPA 2001 |
| 21 | Supplyandfixingofhightemperaturedetectiontubemadeofpolymerwithfixing accessories.The quoted rate shall include cost of modification (any type) to the existing panels required for proper functioning of fire suppression system. |
| 22 | Supply,Installation,TestingandcommissioningofonlineUPSindustrial grade, suitable for Sea Port application with all requirements/accessories to meet theCEFFES guidelines upto 5KVA single phase. The quoted rate shall include cost of suitable size copper wiring upto 5 meters at input side and upto 5 meters at output side. |
| 23 | Note: (i) Pre-commissioing test of Fire alarm system and Fire suppression system shall be carried out as per standard practice or as per OEM recommendation in presence of Testing Officer and the cost deemed to be included in the quoted rate. (ii) Completion drawings, test certificates/reports, cylinder certificates, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 24 | LIGHTNING PROTEACTION |
| 25 | Supply and installation of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination system . Cross sectional area of conductor should be 50 mm².Test Parameter:a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.034 µΩm,c.Tensile strength - 178 MPa or N/mm²d. Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2. |
| 26 | Supply and installationofNylon Conductor Holder for Parapet wall for holding 8 mm diaAluminium alloy roundConductor. |
| 27 | Supply and installation of Stainless steel SS 304 Grade Metal roof holder as per sheet profile for 8-10 mm dia Aluminium alloySolid Round Conductor for horizontal Air terminal above metal sheet to meet the requirements for IS/IEC 62305.Test Parameter:a) Mechanical Loadb) Environmental Test Tested as per IEC 62561-4c) The quoted rate shall include Adhesive glue for fixing metal roof conductor holder over the metal sufrace. |
| 28 | Supply and installation of Stainless steel 304 Grade Cross Connector for 8 mm dia Aluminium alloy round conductor & 10 mm Copper bonded conductor at cross/Tee junction.Test Parametera) Mechanical Loadb) Electrical Testc) ENvironmental Test Tested for IEC 62561-1 |
| 29 | Supply and installation of Expansion Joint with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations. Expansion Joint should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor. |
| 30 | Supply and installation of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Test Parametres:a) Mechanical Loadb) Electrical Resistivityc) Environmental Test Tested as per IEC 62561-1 |
| 31 | Supply and installation of air termination rod of3mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends (Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories .Test Parameter for 3 mtr vertical air terminal a)ELectrical Resistivityb) Tensile Strengthc) Condition of Salt Mist Tested as per IEC 62561-2.Test Parametrer for Wall clampa) Mechanical load as per IEC 62561-1 |
| 32 | Supply and installation of air termination rod of4 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stone and fixing accessories .Test Parameter for 4 mtr vertical air terminal a)ELectrical Resistivityb) Tensile Strengthc) Condition of Salt Mist Tested as per IEC 62561-2. |
| 33 | Supply and installation of Stainless steel SS 304 GradeFolding Clamp as per sheet profile for 8 mm dia Aluminium alloySolid Round Conductor for horizontal Air terminal above metal sheet to meet the requirements for IS/IEC 62305.Test Parameter:a) Mechanical Loadb) Environmental Test Tested as per IEC 62561-4 |
| 34 | DOWN CONDUCTOR SYSTEM |
| 35 | Supply and installation of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination system . Cross sectional area of conductor should be 50 mm².Test Parameter:a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.034 µΩm,c.Tensile strength - 178 MPa or N/mm²d. Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2. |
| 36 | Supply and installationofNylon Conductor Holder for Parapet wall for holding 8 mm dia Aluminium alloy roundConductor. |
| 37 | Supply and installation of Stainless steel SS 304 Grade Metal roof holder as per sheet profile for 8-10 mm dia Aluminium alloySolid Round Conductor for horizontal Air terminal above metal sheet to meet the requirements for IS/IEC 62305.Test Parameter:a) Mechanical Loadb) Environmental Test Tested as per IEC 62561-4 |
| 38 | Supply and installation of Lightning counter - LCD screen shows the number of lightning strikes, hour and date of lightning eventsButtons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6. |
| 39 | Supply and installation of Stainless Steel 304 grade Test Joint with enclosure to interconnect between 8 mm Al. round conductor to 10 mm copper bonded round conductor.Test Parameter:Salt Spray Test for test joint plate -No sign of Corrosion Tested as per IEC 62561-1 |
| 40 | EARTHING SYSTEM |
| 41 | Supply and installationof 10 mm copper bonded Solid Steel Round Conductor with minimum coating thickness 100µm as integrated down conductor. Material should be tested Tensile strength, Electrical Resistance, salt mist, Bend & Adhesion to meet the requirements of IS/ IEC 62305 and IEC 62561-1&2. |
| 42 | Supply and installation ofStainless steel SS 304 Grade Conductor Holder for fixingthe 8 -10 mm dia round conductor on thewall .Test Parameter:a) Mechanical Loadb) Environmental Test Tested as per IEC 62561-4 |
| 43 | Supply and installation of UL Listed Maintenance Free Copper bonded Earth rod of 3048mm length having the dia of 14.2 mm with copper coating thickness of 254 microns. The rod has been tested for Dimension, Marking, Tensile Strength, Salt mist, coating thickness, Electrical resistivity test before and after corrosion test as per IEC 62561-2 & UL 467. Supply of CAPE make earth enchancing mineral compound tested for leaching and TCLP with NABL accredited Lab as per IEC 62561-7 -25 kgSupply of Earth rod clamp made for terminating cable / flat conductor.Supply of Earth Chamber Inspection Pit made up of Plastic withstand load of 60kN |
| 44 | Notes for Lightning Protection : (i) The quoted rate shall include any type of civil work required for proper installation of LP, making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (iii) Completion drawings, test certificates/reports, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 45 | DM WATER PLANT MECHNICAL |
| 46 | Supply and installation of a horizontal centrifugal raw water transfer pump made of cast iron (CI), with a duty condition of 10 m³/h at 3.5 m head, from Grundfos or an equivalent manufacturer, including one working unit and one standby unit. |
| 47 | Supply and install, testing and commissioning of a horizontal centrifugal product water trasfer pump made of SS 316 with a duty condition of 10m³/h at 45m head from Grundfos or an equivalent manufacturer. |
| 48 | Supply and installation of a Feed Water Tank (Raw Water Storage Tank) with a shell dimension of Ø5000 mm x 10500 mm height x 16 mm thickness (1 unit), including ISMC 175 x 150 structural support and three nozzles (N1, N2, N3) with a size of 150 NB each. |
| 49 | Supply and installation of a Feed Water Tank (Product Water Storage Tank) with a shell dimension of Ø5000 mm x 10500 mm height x 16 mm thickness (1 unit), including ISMC 175 x 150 structural support and three nozzles (N1, N2, N3) with a size of 150 NB each. |
| 50 | Supply and installation of a multigrade sand filter with an operating flow rate of 8.5 m³/h, made of mild steel (MS) with epoxy coating, dimensions of 800 mm (D) x 1875 mm (H), a shell thickness of 3 mm, a dished end thickness of 4 mm, with inbuild strainer made of GI and a maximum working pressure of 3.5bar, with a minimum working pressure of 2 bar . |
| 51 | Supply and installation of media from Indion or an equivalent manufacturer for the multigrade sand filter. |
| 52 | Supply and installation of an activated carbon filter with an operating flow rate of 8.5 m³/h, constructed from mild steel (MS) with epoxy coating, featuring dimensions of 800 mm (D) x 1875 mm (H), a shell thickness of 4 mm, a dished end thickness of 4 mm, with inbuild strainer made of GI a maximum working pressure of 3.5 bar, and a minimum working pressure of 2 bar. |
| 53 | Supply and installation of media with an IV (Iodine Value) of more than 900, sourced from GAC or an equivalent manufacturer, for the activated carbon filter. |
| 54 | Supply and installation of a strong acid cation (SAC) filter with an operating flow rate of 8 m³/h, constructed from mild steel rubber lined (MSRL), featuring dimensions of 1000 mm (D) x 1800 mm (H), a shell thickness of 4 mm, a dished end thickness of 8 mm, with inbuild strainer made of GI a maximum working pressure of 3.5 bar, a minimum working pressure of 2 bar, and utilizing Indion 225H resin. |
| 55 | Supply and installation of resin with a volume suitable for an operating flow rate of 8 m³/h. |
| 56 | Supply and install testing and commissioning of a strong base anion (SBA) filter with an Operating flowrate: 8 cum/h, MoC: MSRL, featuring dimensions of 800 mm (D) x 2500 mm (H), a shell thickness of 8 mm, a dished end thickness of 8 mm, a maximum working pressure of 3.5 bar, with inbuild strainer made of GI a minimum working pressure of 2 bar, and Type of Resin: NIP along with vessels and strainers. |
| 57 | Supply and installation of resin with a volume suitable for an operating flow rate of 8 m³/h. |
| 58 | Supply and install, testing and commissioning of a mixed bed (MB) resin with an Operating flowrate: 8 cum/h, MoC: MSRL, featuring dimensions of 800 mm (D) x 2800 mm (H), a shell thickness of 8 mm, a dished end thickness of 8 mm, a maximum working pressure of 3.5 bar, a minimum working pressure of 2 bar, and Type of Resin:225H and FFIP. |
| 59 | Supply and installation of mixed bed (MB) resin, with a volume appropriate for an 8 m³/h operating flowrate system |
| 60 | Supply and installation of a Degassing Tower(DGT) with an Operating flowrate: 8 cum/h, MoC: MSRL, featuring dimensions of 600 mm (D) x 2000 mm (H), a shell thickness of 8 mm, a dished end thickness of 8 mm. |
| 61 | Supply and installation of Acid Measuring Tank with dimensions 600 diax 900 H mm, made of MSRL material for SAC, and 500 dia x 845 H mm MSRL tank for MB, designed for HCL storage and handling. |
| 62 | Supply and installation of a Caustic Dilution Tank with dimensions of 600 dia x 900 mm made of MSRL for SBA, and a 525 x 825 mm MSRL tank for MB, designed for handling NaOH. |
| 63 | Supply and installation of a degassed water tank with 1000 mm x 2500 mm (D x H), MoC: MSRL. |
| 64 | Supply and installation of a degassed water pump with a duty condition of 10 m³/h at 3.5 m head, rated at 5 HP, from Grundfoss or an equivalent manufacturer. |
| 65 | Supply and installation of a degasser blower made of cast iron (CI), with a duty condition of 6.0 m³/h at 50 mm Wg, powered by a 0.25 HP motor, from Grundfoss or an equivalent manufacturer. |
| 66 | Supply and installation of low-pressure gauges with a range of 0 to 7 bar, sourced from Baumer or an equivalent manufacturer. |
| 67 | Supply and installation of a rotameter with a capacity of 14,000 LPH, from Aster or an equivalent manufacturer. |
| 68 | Supply and installation of motorized valves, 2\" in size, with manual override, sourced from Festo or an equivalent manufacturer. |
| 69 | Supply and installation of pH and conductivity sensors with local display and transmitters, with 2 sensors on the feed line and 2 on the product water line, from Hanna or an equivalent manufacturer. |
| 70 | Supply and installation of low-pressure sensors with local display and transmitters, sourced from Baumer or an equivalent manufacturer. |
| 71 | Supply and installation of flow sensors equipped with local display and transmitters for monitoring flow rates. |
| 72 | Supply and installation of a turbine-based mechanical water meter for quantifying feed and product flow rates. |
| 73 | Supply and fix of cope points (150mm dia)including valve etc all as per existing including necessary end fittings, securing arrangements, and related accessories for jetty installation. |
| 74 | Supply and installing portable industrial fume extractors for a DM water plant with a capacity of 150 TPD, housed in a building measuring 13m x 5m(approximately). The fume extractors shall have a required airflow capacity. The system shall be constructed of corrosion-resistant materials suitable for chemical environments and equipped with easy-to-move caster wheels, a flexible suction arm with a 360-degree swivel, and an integrated noise control mechanism (<75 dB). The extractors should comply with relevant IS/IEC standards and ensure optimal indoor air quality, safety, and regulatory compliance. |
| 75 | Pipes and Fittings |
| 76 | supply and installation of a 75 mm HDPE pipe, extending over a length of 50 meters. This pipe will be tapped from the existing source to ensure a seamless connection and integration with the current system, meeting the required specifications and operational needs. |
| 77 | supply, laying, Installation of a 50mm in diameter UPVC pipe, it includes procuring the pipe in compliance with approved standards and ensuring careful jointing to achieve optimal functionality and long-term durability. Used for interconnection of process tanks etc. |
| 78 | supply, laying, Installation of a 75 mm in diameter UPVC pipe , includes procuring the pipe in compliance with approved standards and ensuring careful jointing to achieve optimal functionality and long-term durability.Used for connecting Dm unitwith feeder tank and inter connection of process tank. |
| 79 | supply, laying, Installation of a 100 mm in diameter UPVC pipe , includes procuring the pipe in compliance with approved standards and ensuring careful jointing to achieve optimal functionality and long-term durability.Used for connecting product water tank with transfer pump for supply of Dm water to the tunnel. |
| 80 | supply, installation, jointing, testing, and commissioning of a 100 mm UPVC elbow. This includes procuring the elbow in compliance with approved standards and ensuring precise installation and jointing to guarantee proper flow direction, optimal functionality, and long-term durability. |
| 81 | supply, installation, jointing, testing, and commissioning of a 100 mm UPVC Coupling. This includes procuring the elbow in compliance with approved standards and ensuring precise installation and jointing to guarantee proper flow direction, optimal functionality, and long-term durability. |
| 82 | supply, installation, jointing, testing, and commissioning of a 100 mm UPVC Tee. This includes procuring the elbow in compliance with approved standards and ensuring precise installation and jointing to guarantee proper flow direction, optimal functionality, and long-term durability. |
| 83 | supply, installation, jointing, testing, and commissioning of a 100 mm UPVC Non Return Valve (NRV). This includes procuring the elbow in compliance with approved standards and ensuring precise installation and jointing to guarantee proper flow direction, optimal functionality, and long-term durability. |
| 84 | supply, installation, jointing, testing, and commissioning of a 100 mm UPVC Ball Valve. This includes procuring the elbow in compliance with approved standards and ensuring precise installation and jointing to guarantee proper flow direction, optimal functionality, and long-term durability. |
| 85 | supply, fixing, jointing, testing, and commissioning of a UPVC elbow with a 3- inch diameter, includes procuring the elbow in compliance with approved standards and ensuring precise jointing to achieve optimal functionality and long-term durability. |
| 86 | supply, fixing, jointing, testing, and commissioning of a 3-inch UPVC coupling joint, includes procuring the coupling in compliance with approved standards and ensuring precise jointing to achieve optimal functionality and long-term durability. |
| 87 | supply, fixing, jointing, testing, and commissioning of a 3-inch UPVC TEE, includes procuring the TEE in compliance with approved standards and ensuring precise jointing to achieve optimal functionality and long-term durability. |
| 88 | supply,fixing, jointing, testing, and commissioning of 3-inch UPVC ball valves, includes procuring the ball valves in compliance with approved standards and ensuring precise jointing to ensure optimal functionality and long-term durability. |
| 89 | supply,fixing, jointing, testing, and commissioning of 3-inch UPVC MTA and FTA , includes procuring the MTA and FTA in compliance with approved standards and ensuring precise jointing to ensure optimal functionality andlong-term durability. |
| 90 | supply, fixing, jointing, testing, and commissioning of a 50 mm Non-Slam Non- Return Valve (NRV) made of SS 304, includes procuring the valve in compliance with approved standards and ensuring precise installation and jointing to ensure optimal functionality, preventing backflow, and ensuring long-term durability. |
| 91 | supply,fixing, jointing, testing, and commissioning of a 2-inch ball valve madeup of UPVC, includes procuring the ball valve in compliance with approved standards and ensuring precise installation and jointing to guarantee optimal functionality, efficient flow control, and long-term durability. |
| 92 | supply, fixing, jointing, testing, and commissioning of a 2-inch union madeup of UPVC, ncludes procuring the union in compliance with approved standards and ensuring precise jointing to ensure proper functionality, easy maintenance, and long-term durability. |
| 93 | supply,fixing, jointing, testing, and commissioning of a 2-inch tee madeup of UPVC, includes procuring the tee in compliance with approved standards and ensuring precise jointing to ensure optimal functionality, efficient flow distribution, and long-term durability. |
| 94 | supply, fixing, jointing, testing, and commissioning of a 2-inch elbow madeup of UPVC, includes procuring the elbow in compliance with approved standards and ensuring precise jointing to ensure proper functionality, efficient flow direction, and long-term durability. |
| 95 | supply, fixing, jointing, testing, and commissioning of a 2-inch female threaded tee,madeup of UPVC, includes procuring the tee in compliance with approved standards and ensuring precise jointing to ensure optimal functionality, secure connections, and long-term durability. |
| 96 | supply, fixing, jointing, testing, and commissioning of a 4-inch x 2-inch flange connector madeup of UPVC, includes procuring the flange connector in compliance with approved standards and ensuring precise jointing to ensure secure connections, optimal functionality, and long-term durability. |
| 97 | supply, fixing, jointing, testing, and commissioning of a 2-inch Male MTA madeup of UPVC, includes procuring the MTA in compliance with approved standards and ensuring precise jointing to ensure secure connections, optimal functionality, and long-term durability. |
| 98 | supply, fixing, and securing of a GI hex head bolt, madeup of UPVC, size M30 x 100 mm in length includes procuring the boltin compliance with approved standards and ensuring proper installation to ensure secure fastening, optimal functionality, and long-term durability. |
| 99 | supply of 10-meter Teflon tape includes procuring the Teflon tape in compliance with approved standards and ensuring it is used for sealing threaded joints to prevent leaks, ensuring optimal performance and long-term durability. |
| 100 | supply, fixing, and jointing of a 2-inch dummy threaded component procuring the dummy threaded piece in compliance with approved standards and ensuring proper installation to seal or close off pipes, ensuring secure connections and long-term durability. |
| 101 | supply, fixing, and use of rubber gaskets, includes procuring the rubber gaskets in compliance with approved standards and ensuring they are properly fitted to seal joints, prevent leakage, and ensure optimal performance and long-term durability. |
| 102 | supply, fixing, and securing of a hex head nut made of SS 304, size M10, includes procuring the nut in compliance with approved standards and ensuring proper installation to ensure secure fastening, optimal functionality, and long-term durability. |
| 103 | supply, fixing, and securing of a hex head nut made of SS 304, size M8 procuring the nut in compliance with approved standards and ensuringproper installation to ensure secure fastening, optimal functionality, and long-term durability. |
| 104 | supply, fixing, and securing of a hex head bolt made of SS 304, size M6 x 25 mm in length includes procuring the bolt in compliance with approved standards and ensuring proper installation to ensure secure fastening, optimal functionality, and long-term durability. |
| 105 | supply, fixing, and use of a rubber gasket with an inner diameter (ID) of 1 inch, an outer diameter (OD) of 4 inches, and 4 holes, includes procuring the gasket in compliance with approved standards and ensuring proper installation to provide a secure seal, prevent leakage, and ensure optimal functionality and long-term durability. |
| 106 | supply,fixing, and use of a stainless steel (SS 304) washer, size M10 with a thickness of 2 mm, includes procuring the washer in compliance with approved standards and ensuring proper placement to distribute the load, prevent damage to the surface, and ensure long-term durability. |
| 107 | supply,fixing, and securing of a hex head nut made of SS 304, size M6, includes procuring the nut in compliance with approved standards and ensuring proper installation to ensure secure fastening, optimal functionality, and long-term durability. |
| 108 | supply, fixing, and use of a stainless steel (SS 304) washer, size M8 with a thickness of 2 mm, includes procuring the washer in compliance with approved standards and ensuring proper placement to evenly distribute the load, prevent surface damage, and ensure long-term durability. |
| 109 | supply, fixing, and use of a stainless steel (SS 304) washer, size M6 with a thickness of 2 mm includes procuring the washer in compliance with approved standards and ensuring proper placement to distribute the load, prevent surface damage, and ensure long-term durability. |
| 110 | supply, fixing, jointing, testing, and commissioning of a ¾-inch UPVC ball valve. This includes procuring the ball valve in compliance with approved standards and ensuring precise installation and jointing to ensure efficient flow control, optimal functionality, and long-term durability. |
| 111 | supply, laying , jointing, testing, and commissioning of a 1-inch UPVC pipe. This includes procuring the pipe in compliance with approved standards and ensuring precise installation and jointing to ensure optimal functionality, secure connections, and long-term durability. |
| 112 | supply,laying, jointing, testing, and commissioning of a 1/2-inch UPVC pipe. This includes procuring the pipe in compliance with approved standards and ensuring precise installation and jointing to ensure optimal functionality, secure connections, and long-term durability. |
| 113 | supply, fixing, jointing, testing, and commissioning of a 1-inch UPVC elbow, includes procuring the elbow in compliance with approved standards and ensuring precise installation and jointing to ensure proper flow direction, optimal functionality, and long-term durability. |
| 114 | supply, fixing, jointing, testing, and commissioning of a 1-inch UPVC tee, includes procuring the tee in compliance with approved standards and ensuring precise installation and jointing to ensure efficient flow distribution, optimal functionality, and long-term durability. |
| 115 | Notes for DM Water Plant |
| 116 | (i) The DM Plant shall be SCADA compatible (ii) The quoted rate shall include any type of civil work required for proper installation of pumpsets, filters, valves, tanks etc and making good to the existing structure etc. (iii) The quoted rate shall include cost of starters, wiring, support structure etc required for satisfactory perfomance of DM plant (ii) Contractor shall visit the site with the prior permission from DGNP cell and ascertain raw water parameters before quoting rates (iv) The all dimensions shown in the tender drawings are to be rechecked and verified at site by the contractor (iii) Contractor shall submit requisite drawings, details, MOC, electrical circuits etc duly obtained from OEMs for the approval of users/accepting officer before procurement. (iv) Pre-commissioing test of DM water plant shall be carried out as per standard practice or as per OEM recommendation in presence of Testing Officer and the cost deemed to be included in the quoted rate. The DM water sample shall be tested and test report to be submitted without extra cost (vi) Completion drawings, piping layout, test certificates/reports, maintenance manuals, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 117 | DISMANTLING |
| 118 | Taking down dismantling and handover to the user with the exisitng plant of 72 TPD DM plant along with associated equipments. |
| 119 | Taking down dismantling of existing PVC/UPVC pipe of dia upto 100mm or any other size complete including gate valves, sluice valves, ball valves with any type fittings and handover to user |
| 120 | Dismantling water tanks and removing to store. |
| 121 | Dismantling water tanks and removing of existing PVC tank removal. |
| 122 | Dismantling of cylindrical 100/150 ton tank and handover to user. |
| 123 | Dismantling of existing Transfer pumps and handover to user. |
| 124 | Notes for Dismantling: (i) All dismantled items are to be properly accounted for and handed over to the users and receipt voucher to be obtained from users. (ii) The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 125 | SUPPLY PIPELINE INSIDE TUNNEL AREA |
| 126 | Supply and laying, Installation of Unplasticised PVC pipes of class \"A\" fixed complete to walls, ceilings or in floors etc.,of pipe 160 mm dia. The quoted rate shall include cost of MS supports, couplers, fittings, civil work etc |
| 127 | Supply and laying, Installation of Unplasticised PVC pipes of pressure rating class \"A\" fixed complete to walls, ceilings or in floors etc.,of pipe 110 mm dia. The quoted rate shall include cost of MS supports, couplers, fittings, civil work etc |
| 128 | Supply and laying, Installation of Unplasticised PVC pipes ofclass \"A\" fixed complete to walls, ceilings or in floors etc.,of pipe 50mm dia. The quoted rate shall include cost of MS supports, couplers, fittings, civil work etc |
| 129 | Note for PVC pipeline work(i) All dimension shoen in tender drawins are to be rechecked and verified at site by the contractor.(ii) The quoted rate shall include any of civil work required for proper installation of pipelines, valves etc making good to the existing structure etc.(iii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates.(iv) Contractor shall submit requisted layout drawing, details for the approval of user/accepting officer before procurement.(v) Pre commissioning test of popeline shall be carried out as per standard practice in presence of Testing officer and the cost deemed to included in quoted rate.(v) Completin drawings, layout, test certificates/reports, PRBs etc required for proper handing taking users be provided by the contractor without etra cost. |
| 130 | LT PANELS |
| 131 | 150 TPD DM UNIT BOM DM PLANT CONTROL PANEL(DM PLANT-1) |
| 132 | Panel consisting of the following |
| 133 | Incomers:- |
| 134 | 400A, 4P, MCCB of 35KA breaking capacity with O/C, S/C andThermal Magnetic based Releases -1 Nos. Each consisting of following. 6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No, LED Type R-Y-B Phase Indication Lamps. -(1 set),On,Off & Trip Indications: (1 sets ), 400/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 135 | Outgoings:- |
| 136 | 100A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Magnetic based Releases -3 Nos (2 DEDICATED + 1SPARE). Each consisting of following. 6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port - 1Nos, LED Type R-Y-B Phase Indication Lamps. -(1 set), On,Off & Trip Indications: (1 sets ), 100/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 137 | 32A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Magnetic based Releases -10 Nos (6 DEDICATED + 4SPARE). Each consisting of following. 6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No, LED Type R-Y-B Phase Indication Lamps. -(1 set), On,Off & Trip Indications: (1 sets ),32/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 138 | Busbar: 415V, 400A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 35KA for 1 Sec. - LS (with 50% Neutral) |
| 139 | SPD |
| 140 | This panel shall include Protection at the Main Distribution Board / Sub distribution board or in LT panel of the power supply system.Protection at the Main Distribution Board / Sub distribution board or in LT panel of the power supply system.Class B+C/Class I+II (according to IEC 61643 - 1)(THREE PHASE+ NEUTRAL) Class B+C/Class I+II (according to IEC 61643 - 1) Pluggable type SPD with potential free contact and thermal disconnector has to be connected between Line and Neutral and SPD of Spark Gap type between Neutral and Earth of following ratings should include base element & pluggable arresters. If required, remote signaling should be provided for remote monitoring purpose.Nominal Voltage, Un -230V, 50/60 Hz,Line to Neutral-MOV with built in thermal fuse,Neutral to Earth- Spark Gap Encapsulated / Non-exhausting,MCOV of 320V Nominal current -90 kA (8/20µ sec) - 30 kA each.Voltage protection level <1.4 kV. Protection Modes for : L & N toPE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec) Mounting on -Din railMax. Back-up fuse-Up to 160 amps max. Depending up on panel design & breaking capacity. Approvals: OVEDegree of Protection:IP 20Operating temperature range:-40°C to +85°C Response Time-< 25nano secondsMake: -OBOModel Number- V50 3+ NPE,FS ,BACK UP FUSE NEEDED 160 A, 3PHASE , 4 WIRE SYSTEM DIN RAIL MOUNTED SPDClass B+C/Class I+II Quantity-1No |
| 141 | 150 TPD DM UNIT BOM DM PLANT CONTROL PANEL(DM PLANT-2) |
| 142 | Panel consisting of the following |
| 143 | Incomers:- |
| 144 | 100A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Magnetic based Releases -1 Nos. Each consisting of following. 6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 Nos, LED Type R-Y-B Phase Indication Lamps. -(1 set), On,Off & Trip Indications: (1 sets ), 100/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 145 | Outgoings:- |
| 146 | 32A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Magnetic based Releases -10 Nos (6 DEDICATED + 4SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 Nos,LED Type R-Y-B Phase Indication Lamps. -(1 set), On,Off & Trip Indications: (1 sets ), 32/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 147 | Supplying, laying, testing and commissioning of cables of the following sizes of cables on trays built up trenches or through GI pipes or clamping to column wall or structure using GI spacers and saddles (atan interval of 300mm for cables of OD up to 25mm and 500mm for the cables) scope shall includes supply of these saddles, hardware and consumables. Cables laid in trays shall be dressed and tied with black nylon ropes in the horizontal portions and clamped using the GI saddles at every 750mm in the vertical portion. What ever cables are laid through GI pipes scopes shall also include sealing the mouth of the GI pipes. Where ever cables are to be laid in built up trenches workshall be includes opening the RCC slabs before laying and replacing them after laying. The work shall be carried out as per the specification and as per the directions of the Engineer-in-charge.NOTE:All Aluminium Cable(Size) complying to IS 7098 Part 1,XLPE insulation,Inner & Outer Sheath complying ST2, Armoured Cable. |
| 148 | Supply & Laying of below mentioned sizes of LT FRLS Cables 11KV (Makes : KEI / HAVELLS POLYCAB). |
| 149 | 3.5 CAluminium,Ar XLPE Cable |
| 150 | 3.5 C x 240 Sq.mm Aluminium,Ar XLPE Cable |
| 151 | 3.5 C x 70 Sq.mm Aluminium,Ar XLPE Cable |
| 152 | 4 C x 25 Sq.mm Aluminium,Ar XLPE Cable |
| 153 | CABLE TERMINATIONS (including supply of cable glands and lugs) |
| 154 | 3.5 C AL,Ar XLPE Cable |
| 155 | 3.5 C x 240 Sq.mm Aluminium,Ar XLPE Cable |
| 156 | 3.5 C x 70 Sq.mmAluminium,Ar XLPE Cable |
| 157 | 4 C XLPE Cable |
| 158 | 4 C x 25 Sq.mm Aluminium,Ar XLPE Cable |
| 159 | CABLE TRAYS |
| 160 | Supply & Installation ofheavy duty hot dipped galvanized perforated type Cable trays of following sizes, suspended from ceiling or fixed vertically on wall / column as per including necessary supports like anchor bolts, hangers, brackets etc. and accessories like Elbows, Bends, Tee, requisite support / suspenders, hardware etc. as per site requirement.All supporting structure & hardware including nuts & bolts etc. shall be of galvanized iron as approved. Height of cable tray will be 50 mm. these all elbows, Bends, Reducers, Tees should be factory made. All the cable trays should be providedwith2mm thickness. |
| 161 | Without Cover |
| 162 | 600 MM widthperforated cable tray |
| 163 | 300 MM width perforated cable tray |
| 164 | 150 MM width perforated cable tray |
| 165 | 75 MM width perforated cable tray |
| 166 | Steel for supporting the above Cable Trays |
| 167 | Ladder trays Without cover |
| 168 | 600 MM widthLadder cable tray |
| 169 | 300 MM width Ladder cable tray |
| 170 | Busbar : 415V, 1000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 25KA for 1 Sec. - LS (with 50% Neutral) |
| 171 | SPD |
| 172 | This panel shall include Protection at the Main Distribution Board / Sub distribution board or in LT panel of the power supply system.Protection at the Main Distribution Board / Sub distribution board or in LT panel of the power supply system.Class B+C/Class I+II (according to IEC 61643 - 1)(THREE PHASE+ NEUTRAL) Class B+C/Class I+II (according to IEC 61643 - 1)Pluggable type SPD with potential free contact and thermal disconnector has to be connected between Line and Neutral and SPD of Spark Gap type between Neutral and Earth of following ratings should include base element & pluggable arresters. If required, remote signaling should be provided for remote monitoring purpose.Nominal Voltage, Un -230V, 50/60 Hz,Line to Neutral-MOV with built in thermal fuse,Neutral to Earth-Spark Gap Encapsulated / Non-hausting,MCOV of 320V Nominal current -90 kA (8/20µ sec) - 30 kA each. Voltage protection level <1.4 kV. Protection Modes for : L & N toPE. Maximum Discharge Current Imax per pole-50 kA (8/20µsec) Mounting on -Din rail Max. Back-up fuse-Up to 160 amps max. Depending up on panel design & breaking capacity. Approvals: OVEDegree of Protection:IP 20 Operating temperature range:-40°C to +85°C Response Time-< 25nano secondsMake: -OBO/legrand/ABB/L&T Model Number- V50 3+ NPE,FS ,BACK UP FUSE NEEDED 160 A, 3PHASE , 4 WIRE SYSTEM DIN RAIL MOUNTED SPDClass B+C/Class I+II Quantity-1No |
| 173 | Design , Supply, installation, Testing and commissioning of a PLC- based control panel for complete system automation, featuring data transfer to the local server and a 12\" HMI for local display of all operating and quality parameters Note:(i) System should have provision of both manual and automatic operation of Dm palants.(ii) Operating systems software and programming shall not be intellictual property of any agency. (iii) Quated rate shall include suitable communication system including payment of bills to a telecom service provider till expiry of Defect Liablity period. |
| 174 | Notes for LT Panels(i) Panels shall be SCADA compatible (ii) The quoted rate shall include any type of civil work required for proper installation of panels, making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (iii) Contractor shall submit requisite drawings, details, MOC, electrical circuits etc duly obtained from OEMs for the approval of users/accepting officer before procurement. (iv) Completion drawings, test certificates/reports, maintenance manuals, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 175 | HT/LT CABLE SUPPLYING AND LAYING (Makes: KEI/HAVELLS POLYCAB) |
| 176 | Steel for supporting the above Cable Trays |
| 177 | EARTHING SYSTEM |
| 178 | Supply, Laying and fixing of 50 x 6mm GI flat |
| 179 | Supply, Laying and fixing of 25 x 6mm GI flat |
| 180 | Supply, Laying and fixing of 25 x 3mm GI flat |
| 181 | 8 SWG GI wire |
| 182 | EARTH PITS |
| 183 | SITC earth pit for the BODY with 100mm dia \"B\" class 2.5 long CI pipe withproviding GI funnel covered with mesh of suitable size enclosed in a CC chamber of 450mm X 450mm X 3mm with suitable reinforced CI cover duly providing staggered holes of 16 nos of 12mm dia to the earth electrode filling salt and charcoal around 150mm from the bottom of the pipe to the bottom of CC chamber. The connections from the electrode through GI strip of 40 X 6mm length provided with suitable size of 14 nos holes with GI washers, nuts, bolts and all labour charges etc., complete. |
| 184 | Note: All Earth Pit Chambers need to be Constructed with 100mm Solid Blocks. All Earth Pit Chambers to be Numbered and Painted with Reputed make Paint. |
| 185 | EXTERNAL WATER SUPPLY |
| 186 | FRESH WATER-POTABLE |
| 187 | PIPE |
| 188 | Supply, installation, jointing, testing, and commissioning of 4-inch (100mm) Ductile Iron (DI) pipes for raw water applications, in accordance with IS 8329 standards. This includes handling, transportation to the site, and all related civil works, supports, and necessary infrastructure as per the approved specifications and drawings. The rate shall cover all associated costs for materials, labor, and equipment. |
| 189 | ELL 90 LR |
| 190 | Supply, installation, testing, and commissioning of 4-inch (100mm) Ductile Iron (DI) 90° Elbow (Long Radius) conforming to ISO 2531/EN 545 standards for raw water application.The item shall include necessary excavation, backfilling, pipe supports, and all incidental civil works required for proper installation, alignment, and testing to ensure leak-proof operation under operating conditions. The unit rate shall be inclusive of allmaterials, labor, transport, and handling costs to the site. |
| 191 | ELL 45 LR |
| 192 | Supply, installation, testing, and commissioning of 4-inch (100mm) Ductile Iron (DI) 45° Elbow (Long Radius) conforming to ISO 2531/EN 545 standards for raw water application.The item shall include necessary excavation, backfilling, pipe supports, and all incidental civil works required for proper installation, alignment, and testing to ensure leak-proof operation under operating conditions. The unit rate shall be inclusive of allmaterials, labor, transport, and handling costs to the site. |
| 193 | FLANGE SO |
| 194 | Supply, installation, and testing of 4-inch Ductile Iron (DI) Flanged Socket Outlet (SO) for raw water application, including necessary fittings, flanges, gaskets, bolts, and nuts. The ductile iron pipe shall conform to the latest IS/ISO standards for raw water applications testing as per standard procedures, ensuring leak-proof performance and adherence to project specifications. Complete with all necessary civil works |
| 195 | Gasket, SWG |
| 196 | Ductile iron gasket with a nominal diameter of 4 inches, compliant with IS/BS/ASTM standards, The gasket material should be of high-grade ductile iron capable of withstanding operational conditions, all components must be corrosion-resistant, durable, and designed for a secure and leak-proof connection between flanges in pipeline systems. |
| 197 | VALVES &INSTRUMENATION |
| 198 | Supply, installation, and testing of a 4 inch diameter gate valve (Isolation valve)made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining the working pressure. The valve shall be equipped with a resilient sealing mechanism to prevent backflow and ensure proper unidirectional flow. The valve body, seat, and disc materials should be corrosion-resistant and suitable for high-pressure applications, The scope of work includes the necessary fittings for a complete installation, as well as testing and commissioning to verify the performance under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. |
| 199 | Supply and fixing of cope points including necessary end fitting, 50mm dia MS pipe heavy tapped from main pipe 4inch dia laying inside tunnel upto cope outside tunnel including core cutting, securring arrangements and related accessories for jetty installation. Note-Cope point valves, backflow prevention valve, coupling will be measured and paid under seperate item. |
| 200 | Supply, fixing, testing and commissioning of Globe valves (40mm) diameter made of high-grade ductile iron, confoming to IS/BS standards, capable of withstanding and maintaining the working pressure. The valve body, seat, and disc materials should be corrosion-resistant and suitable for high- pressure applications. The scope of work includes the necessary fittings for a complete installation as well as testing and commissioning to verify the performnce under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. |
| 201 | Supply, fixing, testing and commissioning of Gate valves (50mm) diameter made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining the working pressure. The valve body, seat, and disc materials should be corrosion-resistant and suitable for high-pressure applications. The scope of work includes the necessary fittings for a complete installation as well as testing and commissioning to verify the performnce under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. |
| 202 | Supply, foxing, testing and commissioning of Ball valves (100mm) diameter made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining the working pressure. The valve body, seat, and disc materials should be corrosion-resistant and suitable for high-pressure applications. The scope of work includes the necessary fittings for a complete installation as well as testing and commissioning to verify the performnce under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes |
| 203 | Supply, fixing, testing and conmmissioning of Ball valves (50mm) diameter at above the jetty made of high-grade SS, conforming to IS/BS standards, capable of withstanding and maintaining the working pressure. The valve body, seat, and disc materials should be corrosion-resistant and suitable for high- pressure applications. The scope of work includes the necessary fittings for a complete installation as well as testing and commissioning to verify the performnce under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. |
| 204 | Supply, fixing, testing and commissioning of Non Return Valves (50mm) diameter made of Bronze, conforming to IS/BS standards, capable of Withstanding and maintaining the working pressure. The valve body, seat, and disc materials should be corrosion-resistant and suitable for high-pressure applications. The scope of work includes the necessary fittings for a complete installation as well as testing and commissioning to verify the performnce under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. Supply and fixX of female connector with 50mm diameter, with bronze material including necessary end |fittings, Securing arrangements, and related accessories for jetty installation. |
| 205 | Supply and fix of female connector with 50mm diameter, with bronze material including necessary end fittings, securing arrangements and related accessories for jetty installation. |
| 206 | TEE |
| 207 | Supply, installation, testing, and commissioning of 4-inch (100mm) Ductile Iron (DI) TEE conforming to ISO 2531/EN 545 standards for raw water application.The item shall include necessary excavation, backfilling, pipe supports, and all incidental civil works required for proper installation, alignment, and testing to ensure leak-proof operation under operating conditions. The unit rate shall be inclusive of all materials, labor, transport, and handling costs to the site. |
| 208 | REDUCER |
| 209 | supply and installation of a 4-inch to 2-inch ductile iron pipe reducer. The ductile iron reducer must be designed and manufactured according to ISO 2531 or equivalent standards. |
| 210 | 20MM TAPPING CONNECTION |
| 211 | M&L for 20mm dia tapping from main 4-inch dia pipe all as per existing complete with necessary fittings ball valve 20mm dia-01 No, bolts, nuts, gaskets, and sealing materials; including all necessary pipework, testing and commissioning to verify operational effectiveness, and all required labor for installation, corrosion protection, and compliance with applicable IS/IEC standards. |
| 212 | Notes for Pipeline work |
| 213 | (i) The all dimensions shown in the tender drawings are to be rechecked and verified at site by the contractor (ii) The quoted rate shall include any type of civil work required for proper installation of pipelines, valves etc, making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (iii) Contractor shall submit requisite layout drawings, details for the approval of users/accepting officer before procurement. (iv) Pre-commissioning test of pipeline shall be carried out as per standard practice in presence of Testing Officer and the cost deemed to be included in the quoted rate. (ii) Completion drawings, test certificates/reports, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 214 | DISMANTLING |
| 215 | Dismantling of existing pipe upto 4 inch nominal diameter and loading, transporting, unloading and handing over to users. The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 216 | ELL 90 LR, 45 LR |
| 217 | Taking down & dismantling of existing upto 4inch (100mm) 90° Long Radius Elbow complete and handover to user. |
| 218 | Taking down & dismantling of existing upto 4inch (100mm) 45° Long Radius Elbow complete and handover to user. |
| 219 | FLANGE SO |
| 220 | Taking down & dismantling of existing upto 4-inch Flanged Socket Outlet complete and handover to user |
| 221 | VALVES &INSTRUMENATION |
| 222 | Dismantling of existing isolation valve 100mm dia and loading, transporting, unloading and handing over to users. |
| 223 | Dismantling of existing coping point complete with MS pipe(excluding valve, connectors etc) and loading transporting, unloading and handing over to user. |
| 224 | Dismantling of existing globe valves (40mm) diameter and loading, transporting, unloading and handing over to users. |
| 225 | Dismantling of existing globe valves (50mm) diameter and loading, transporting, unloading and handing over to users. |
| 226 | Dismantling of existing Ball valves (100mm) diameter and loading, transporting, unloading and handing over to users. |
| 227 | Dismantling of existing Ball valves (50mm) diameter and loading, transporting, unloading and handing over to users. |
| 228 | Dismantling of existing non Return valves (50mm) diameter and loading, transporting, unloading and handing over to users. |
| 229 | Dismantling of existing non Female connector (50mm) diameter and loading, transporting, unloading and handing over to users. |
| 230 | TEE |
| 231 | Taking down & dismantling of 4-inch (100mm) Ductile Iron (DI) TEE complete and handover to user |
| 232 | REDUCER |
| 233 | Taking down & dismantlingductile iron pipe reducer complete and handover to user |
| 234 | HYDRANTS |
| 235 | Taking down & dismantlingexisting 20mm dia tapping connectioncomplete and handover to user |
| 236 | Notes for Dismantling: (i) All dismantled items are to be properly accounted for and handed over to the users and receipt voucher to be obtained from users. (ii) The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 237 | EXTERNAL ELECTRIC SUPPLY |
| 238 | 11KV INDOOR HT PANELS |
| 239 | CONSTRUCTION - The Switch Gear Panel shallbe compartmentalisedDesigned with cubicles frabicatedout of High Quality Sheet Steel and the panels shall be dust and vermin proof and with degree of protection IP 42 as per IS 2147. The panels shall be designed having the Following Segregations separately.a)Breaker compartmentb) Busbar compartmentc) Cable and CT compartmentd) Instrument and Relay CompartmentThe Cubical shall be designed for insertion of circuit breaker, which shall be horizontal draw out/horizontal isolation type. Automatic operating type shutters to be provided to ensure no direct access to the live parts.The clearances between phase to phase and phase to earth shall be provided in accordance with the relevant standards.The bus bars shall be supported by bus support insulators placed at regular intervals. The panels shall be powder coated with epoxy base paint to give an aesthetically pleasing appearance. The paint shade shall be as per the requirement.Medium High Voltage Vaccum Circuit Breaker should consist of manual and motor operated spring charged mechanism, mounted on withdrawable truck with three vacuum interrupters. The operating mechanism shall be simple and robust in design.The mechanism shall be trip free and suitable for rapid reclosing. The vacuum interpters shall be capable of withstanding for switching capacitive currents and also magnetising currents. The closing operation shall be followed by motor operated spring charge mechanism with electrical anti pumping feature.SAFETY FEATURES:a) Interlocks to be provided in such away that breaker closing to be prevented in intermediate position between service, test and isolated positions.b) Mechanical interlock to be provided in order to prevent truck racking in and out when breaker is in closed possition.d) Control plug and socket shall be removed only in isolated position.e) Earthing through a draw-out earthing truck with solid links on the bus bar and feeder side to be provided.f) Integral earthing switch, slow closing type or with making capacity to be provided. |
| 240 | (11KV 5WAY HT RMU PANEL)11KV 5 Way H.T Switch Gear Panel (INDOOR TYPE)With 2 Incomer and 3 No\"s Outgoingfeeders.(CONSUMER SIDE) |
| 241 | INCOMING - 1: (2 No) |
| 242 | 11KV, 3P,1250A, 26.1KA Horizontal Draw out type VCB Manually and Motor Operated spring charging mechanism, With 230V AC Supply for Motor,110V DC for shunt Trip coil and Closing Coil.Axu. Contact 4No+4Nc, Mechanical ON and OFF indicator and Push button, Mechanical operation counters with lightining surge arrester.The Each VCB Shall be Provided with DC Power Pack.POTENTIAL TRANSFORMER:(1No)Cast resin PT with HT and LT HRC Fuses, Ratio:11 KV/110V+ Three Phase, Burden 150 VA, Acc. CI, 0.2.CURRENT TRANSFORMER:(3 No’s) Ratio: 150-100/1A, Core 1 : 10VA, CI – 0.2 for Metering, Core 2 : 15VA, CI - 5P 10 for Protection.METERING: ( 1set)96Sq.mm Digital Ammeter with selector switch Digital type 0-250A. 96 Sq.mm Digital Voltmeter with selector switch Digital voltmeter 0- 11KV. PROTECTION RELAYS:1) TRIPLE POLE NON DIRECTIONAL IDMT -2 O/C + 1 E/F Relay of EEmake Equivalent to CDG 31 or Digital Numerical relay and shall be compatable for BMS with communication port.-1 No.2) Master Trip Relay -(1No)3) Trip Circuit Super Vision Relay -(1No) INDICATION LAMPS:1) ON, OFF and Trip Indication Lamps for RYB.-(1 set)2) Trip Circuit Healthy lamp.- (1 set)3) Spring Charging lamp. - (1 set)4) Auto trip. - (1 set)5) LED Type R-Y-B Phase Indication Lamps.-(1 set)CONTROL SWITCHES/PUSH BUTTONa) T-N-C Switch (Breaker Control Switch) - (1 set)b) Trip circuit Healthy Push Button -(1 set)Control Wiring with appropriate colors -(1 set) 230V AC/110V DC Power Pack - 1 No Alarm scheme with hooter, Accept and Reset Button with 8Way Annunciation window. - (1 set) Bus Bar with 800Amps Aluminium (Electrical Grade). - (1 set) Note: The CT\"s/PT\"s specified are Cast Resin and Testing / Approval are as per the ERDA |
| 243 | OUTGOING VCB: (3 No’s) Each Consisting of |
| 244 | 11KV, 3P,800A, 26.1KAHorizontal Draw out type VCB Manually and Motor Operated spring charging mechanism, With 230V AC Supply for Motor,110V DC for shunt Trip coil and Closing Coil.Axu. Contact 4No+4Nc, Mechanical ON and OFF indicator and Push button, Mechanical operation counters with lightining surge arrester.The Each VCB Shall be Provided with DC Power Pack.POTENTIAL TRANSFORMER:(1No) Cast resin PT with HT and LT HRC Fuses, Ratio: 11KV/110V+ Three Phase, Burden 30 VA, Acc.CI 0.2.CURRENT TRANSFORMER: (2 No’s)Ratio: 100-50/1A, Core 1 : 7.5VA, CI – 0.2 for Metering, Core 2 : 10VA, CI - 5P 10 for Protection. Ratio: 100/5A,CI –PS for Special Protection. METERING:( 1set) 96 Sq.mm Digital Ammeter with selector switch Digital type 0- 50A. 96 Sq.mm Digital Voltmeter with selector switch Digital voltmeter 0-11KV. PROTECTION RELAYS:1) TRIPLE POLE NON DIRECTIONAL IDMT -2 O/C + 1 E/F Relay of EEmake Equivalent to CDG 31 or Digital Numerical relay and shall be compatable for BMS with communication port.-1 No. The necessary aux. relays for Transformer WTI, OTI and Buchholz relay alarm and trips to be included. 2) Master Trip Relay-(1No)3) Trip Circuit Super Vision Relay -(1No)4) 3-element Auxillary Relays - 4 No’s (For transformer Protection) INDICATION LAMPS: 1) ON, OFF and Trip Indication Lamps for RYB.-(1 set) 2) Trip Circuit Healthy lamp.-(1 set) 3) Spring Charging lamp. -(1 set)4) Auto trip. - (1 set) 5) LED Type R-Y-B Phase Indication Lamps. -(1 set) CONTROL SWITCHES/PUSH BUTTON b) Trip circuit Healthy Push Button - (1 set) Control Wiring with appropriate colors -(1 set) 230V AC/110V DC Power Pack - 1 No Alarm scheme with hooter, Accept and Reset Button with 8 Way Annunciation windows. -(1 set) Bus Bar with 800 Amps Aluminium (Electrical Grade). - (1 set) Note: The CTS/PTS specified are Cast Resin and Testing / Approval are as per ERDA Test Lab. |
| 245 | (11KV 4WAY HT RMU PANEL)11KV 4 Way H.T Switch Gear Panel (INDOOR TYPE)With 2 Incomer and 2 No\"s Outgoingfeeders.(CONSUMER SIDE) |
| 246 | INCOMING - 1: (2 No) |
| 247 | 11KV, 3P,1250A, 26.1KA Horizontal Draw out type VCB Manually and Motor Operated spring charging mechanism, With 230V AC Supply for Motor,110V DC for shunt Trip coil and Closing Coil.Axu. Contact 4No+4Nc, Mechanical ON and OFF indicator and Push button, Mechanical operation counters with lightining surge arrester.The Each VCB Shall be Provided with DC Power Pack. POTENTIAL TRANSFORMER: (1No) Cast resin PT with HT and LT HRC Fuses, Ratio:11 KV/110V+ Three Phase, Burden 150 VA, Acc. CI, 0.2.CURRENT TRANSFORMER: (3 No’s) Ratio: 150-100/1A, Core 1 : 10VA,CI – 0.2 for Metering, Core 2 : 15VA, CI - 5P 10 for Protection. METERING: ( 1set) 96Sq.mm Digital Ammeter with selector switch Digital type 0-250A. 96 Sq.mm Digital Voltmeter with selector switch Digital voltmeter 0-11KV. PROTECTION RELAYS:1) TRIPLE POLE NON DIRECTIONAL IDMT -2 O/C + 1 E/F Relay of EEmake Equivalent to CDG 31 or Digital Numerical relay and shall be compatable for BMS with communication port.-1 No.2) Master Trip Relay -C21(1No) |
| 248 | 3) Trip Circuit Super Vision Relay -(1No)INDICATION LAMPS:1) ON, OFF and Trip Indication Lamps for RYB.-(1 set)2) Trip Circuit Healthy lamp.- C19(1 set)3) Spring Charging lamp. - (1 set)4) Auto trip. -(1 set)5) LED Type R-Y-B Phase Indication Lamps.- (1 set)CONTROL SWITCHES/PUSH BUTTONa) T-N-C Switch (Breaker Control Switch)- C21(1 set)b) Trip circuit Healthy Push Button - (1 set)Control Wiring with appropriate colors -(1 set) 230V AC/110V DC Power Pack - 1 No Alarm scheme with hooter, Accept and Reset Button with 8Way Annunciation window. - (1 set)Bus Bar with 800Amps Aluminium (Electrical Grade). - (1 set)Note: The CT\"s/PT\"s specified are Cast Resin and Testing / Approval are as per the ERDA Test Lab. |
| 249 | OUTGOING VCB: (2 No’s) Each Consisting of |
| 250 | 11KV, 3P,800A, 26.1KAHorizontal Draw out type VCB Manually and Motor Operated spring charging mechanism, With 230V AC Supply for Motor,110V DC for shunt Trip coil and Closing Coil.Axu. Contact 4No+4Nc, Mechanical ON and OFF indicator and Push button, Mechanical operation counters with lightining surge arrester.The Each VCB Shall be Provided with DC Power Pack. POTENTIAL TRANSFORMER:(1No) Cast resin PT with HT and LT HRC Fuses, Ratio: 11KV/110V+ Three Phase, Burden 30 VA, Acc.CI 0.2.CURRENT TRANSFORMER: (2 No’s) Ratio: 100-50/1A, Core 1 : 7.5VA,CI – 0.2 for Metering, Core 2 : 10VA, CI - 5P 10 for Protection. Ratio: 100/5A,CI –PS for Special Protection. METERING: ( 1set)96 Sq.mm Digital Ammeter with selector switch Digital type 0-50A. 96 Sq.mm Digital Voltmeter with selector switch Digital voltmeter 0- 11KV. PROTECTION RELAYS: 1) TRIPLE POLE NON DIRECTIONAL IDMT-2 O/C + 1 E/F Relay of EE make Equivalent to CDG 31 or Digital Numerical relay and shall be compatable for BMS with communication port.-1 No. 1)The necessary aux. relays for |
| 251 | Transformer WTI, OTI and Buchholz relay alarm and trips to beincluded.2) Master Trip Relay -(1No)3) Trip Circuit Super Vision Relay -(1No)4) 3-element Auxillary Relays - 4 No’s (For transformer Protection) INDICATION LAMPS:1) ON, OFF and Trip Indication Lamps for RYB.-(1 set)2) Trip Circuit Healthy lamp.- (1 set)3) Spring Charging lamp.- (1 set)4) Auto trip.- (1 set)5) LED Type R-Y-B Phase Indication Lamps.- (1 set) CONTROL SWITCHES/PUSH BUTTON Trip circuit Healthy Push Button- (1 set) Control Wiring with appropriate colors - (1 set)230V AC/110V DC Power Pack - 1 No Alarm scheme with hooter, Accept and Reset Button with 8 Way Annunciation windows.- (1 set )Bus Bar with 800 Amps Aluminium (Electrical Grade). - (1 set) Note: The CTS/PTS specified are Cast Resin andTesting / Approval are as per ERDA Test Lab. |
| 252 | (11KV 4WAY HT RMU PANEL)11KV 4 Way H.T Switch Gear Panel (INDOOR TYPE)With 2 Incomer and 3 No\"s Outgoingfeeders.(CONSUMER SIDE) |
| 253 | INCOMING - 1: (1 No) |
| 254 | 11KV, 3P,1250A, 26.1KA Horizontal Draw out type VCB Manually and Motor Operated spring charging mechanism, With 230V AC Supply for Motor,110V DC for shunt Trip coil and Closing Coil.Axu. Contact 4No+4Nc, Mechanical ON and OFF indicator and Push button, Mechanical operation counters with lightining surge arrester.The Each VCB Shall be Provided with DC Power Pack.POTENTIAL TRANSFORMER: (1No)Cast resin PT with HT and LT HRC Fuses, Ratio:11 KV/110V+ Three Phase, Burden 150 VA, Acc. CI, 0.2. CURRENT TRANSFORMER:(3No’s)Ratio: 150-100/1A, Core 1 : 10VA, CI – 0.2 for Metering, Core 2 : 15VA, CI - 5P 10 for Protection.METERING: ( 1set) 96Sq.mm Digital Ammeter with selector switch Digital type 0-250A.96 Sq.mm Digital Voltmeter with selector switch Digital voltmeter 0-11KV. PROTECTION RELAYS: 1) TRIPLE POLE NONDIRECTIONAL IDMT -2 O/C + 1 E/F Relay of EE make Equivalent to CDG 31 or Digital Numerical relay and shall be compatable for BMS with communication port.-1 No. 2) Master Trip Relay -(1No)3) Trip Circuit Super Vision Relay -(1No) INDICATION LAMPS:1) ON, OFF and Trip Indication Lamps for RYB.-(1 set)2) Trip Circuit Healthy lamp.- (1 set)3) Spring Charging lamp. - (1 set)4) Auto trip. - (1 set)5) LED Type R-Y-B Phase Indication Lamps.- (1 set) |
| 255 | CONTROL SWITCHES/PUSH BUTTON a) T-N-C Switch (Breaker Control Switch) - C21(1 set) b) Trip circuit Healthy Push Button - (1 set) Control Wiring with appropriate colors -(1 set) 230V AC/110V DC Power Pack - 1 No Alarm scheme with hooter, Accept and Reset Button with 8Way Annunciation window. - (1 set) Bus Bar with 800Amps Aluminium (Electrical Grade). - (1 set) Note: The CT\"s/PT\"s specified are Cast Resin and Testing / Approval are as per the ERDA Test Lab. |
| 256 | OUTGOING VCB: (3 No’s) Each Consisting of |
| 257 | 11KV, 3P,800A, 26.1KAHorizontal Draw out type VCB Manually and Motor Operated spring charging mechanism, With 230V AC Supply for Motor,110V DC for shunt Trip coil and Closing Coil.Axu. Contact 4No+4Nc, Mechanical ON and OFF indicator and Push button, Mechanical operation counters with lightining surge arrester.The Each VCB Shall be Provided with DC Power Pack.POTENTIAL TRANSFORMER:(1No)Cast resin PT with HT and LT HRC Fuses, Ratio: 11KV/110V+ Three Phase, Burden 30 VA, Acc.CI 0.2.CURRENT TRANSFORMER: (2 No’s)Ratio: 100-50/1A, Core 1 : 7.5VA, CI – 0.2 for Metering, Core 2 : 10VA, CI - 5P 10 for Protection.Ratio: 100/5A,CI –PS for Special Protection. METERING: ( 1set)96 Sq.mm Digital Ammeter with selector switch Digital type 0-50A. 96 Sq.mm Digital Voltmeter with selector switch Digital voltmeter 0- 11KV.PROTECTION RELAYS:1) TRIPLE POLE NON DIRECTIONAL IDMT -2 O/C + 1 E/F Relay of EEmake Equivalent to CDG 31 or Digital Numerical relay and shall be compatable for BMS with communication port.-1 No. The necessary aux. relays for Transformer WTI, OTI and Buchholz relay alarm and trips to be included.2) Master Trip Relay -(1No)3) Trip Circuit Super Vision Relay -(1No)4) 3-element Auxillary Relays - 4 No’s (For transformer Protection) INDICATION LAMPS:1) ON, OFF and Trip Indication Lamps for RYB.-(1 set)2) Trip Circuit Healthy lamp.- (1 set)3) Spring Charging lamp.- (1 set)4) Auto trip.- (1 set)5) LED Type R-Y-B Phase Indication Lamps.- (1 set) CONTROL SWITCHES/PUSH BUTTON |
| 258 | DRY TYPE, INDOOR TYPE TRANSFORMERS |
| 259 | Supply, erection, testing, commissioning and installation of 11KV / 433V, 2000KVA, 50Hz, Z=6.25%, DRY TYPE, INDOOR TYPE,F CLASS- INSULATIONCLASS transformer with OLTC, RTCC & AVR with ±10% instep of 1.25% manufactured as per IS 11171 Energy Efficiency Level 2 with all standard accessories and as per KSEB / HESCOM Karwar approved standards as per Technical Specification and SLD.(Refer Technical Specifications also ) |
| 260 | Supply, erection, testing, commissioning and installation of 11KV/288V/188V(Wdg-1:188V), 2000KVA, 50Hz, Z=6.25%, DRY TYPEINDOOR TYPE,F CLASS- INSULATION CLASS transformer with OLTC and provision to adjust the output voltage using inbuilt OLTC RTCC & AVR with t10% instep of 1.25% manufactured as per lS 11171 Energy Efficiency Level 2 with all standard accessories and as ger KSERI HESCOM Karwar approved standards as per Technical Specification and SLD. (Refer Technical Specifications also ) |
| 261 | LT SWITCH BOARDS (INDOOR TYPE) |
| 262 | Supply, erection, testing & commissioning of the following Outdoor/Indoor typepanel boards |
| 263 | MPCC ( The MPCC Consisting of the Following )(LV SWITCH BOARD -1) |
| 264 | PLC PROGRAMMING |
| 265 | Incoming Feeders on BUS SECTION-1 |
| 266 | Incomer-1(From EB - Transformer - 1)EB I/C-1 |
| 267 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"s Each consisting of following. 6A,control MCBof C-Curve - 3NosMultifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y-B Phase Indication Lamps.- (1 set)On,Off & Trip Indications: (1 sets )4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 268 | Incoming Feeders on BUS SECTION-2 |
| 269 | Incomer-1(From EB - Transformer - 2)EB I/C-2 |
| 270 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3NosMultifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y-B Phase Indication Lamps.- (1 set)On,Off & Trip Indications: (1 sets )4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 271 | Incoming Feeders on BUS SECTION-3 |
| 272 | Incomer-1(From EB - Transformer - 3)EB I/C-3 |
| 273 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3NosMultifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y-B Phase Indication Lamps.- (1 set)On,Off & Trip Indications: (1 sets )4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 274 | ELECTRICAL + MECHANICALINTERLOCKING (ALL THE NECESSARY ACCESSORIES SHOULD BE TAKEN INTO THE PANEL FOR E+MINTRACTION) |
| 275 | Outgoing Feeders on BUS SECTION-1 |
| 276 | 630A, 4P, MCCB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -8 Nos(8DEDICATED). Each consisting of following. 6A, control MCBof C-Curve - 3Nos Multifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y B Phase Indication Lamps.- (1 set) On,Off & Trip Indications: (1 sets ) 630/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos Busbar 415V, 4000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of65KA for 1 Sec. - LS (with 50% Neutral) |
| 277 | SPD This panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1Quantity-1No |
| 278 | BUS COUPLER |
| 279 | 4000A, 4P, EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and MicroProcessor based Releases |
| 280 | Outgoing Feeders on BUS SECTION-2 |
| 281 | 630A, 4P, MCCB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -14 Nos(14DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3NosMultifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y-B Phase Indication Lamps.- (1 set)On,Off & Trip Indications: (1 sets )630/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 282 | 25A, 4P, MCCB of 25KA breaking capacity with O/C, S/C and Thermal Magnetic based Releases -1 Nos(1DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos Multifunction Meter(MFM) With RS485 communication port -1 No.LED Type R-Y-B Phase Indication Lamps.- (1 set)On,Off & Trip Indications: (1 sets )25/5A, CL-1,15VA, Tape wound CT\"s - 3NosBusbar 415V, 4000A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65KA for 1 Sec. - LS (with50% Neutral) |
| 283 | SPD This panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1Quantity-1No |
| 284 | BUS COUPLER |
| 285 | 4000A, 4P, EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and MicroProcessor based Releases |
| 286 | Outgoing Feeders on BUS SECTION-3 |
| 287 | 630A, 4P, MCCB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -11 Nos(8DEDICATED + 3SPARE). Each consisting of following.6A, control MCBof C-Curve - 3NosMultifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y-B Phase Indication Lamps.- (1 set)On,Off & Trip Indications: (1 sets )630/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 288 | 25A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Mangnetic based Releases -2 Nos(1DEDICATED + 1SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos Multifunction Meter(MFM) With RS485 communication port -1 No. LED Type R-Y-B Phase Indication Lamps.- (1 set) On,Off & Trip Indications: (1 sets )25/5A, CL-1, 15VA, Tape wound CT\"s - 3NosBusbar 415V, 4000A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65KA for 1 Sec. - LS (with50% Neutral) |
| 289 | SPD This panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1Quantity-1No |
| 290 | 240KVAR CAPACITOR BANK APFC PANEL - 1No |
| 291 | Panel consisting of the following |
| 292 | Incomers |
| 293 | 1000A, 4P, ACB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases with RS485 communication port -1 No. Each consisting of following.6A, Control MCB - 3Nos LEDtype R Y B Phase indicating lamps - 1 setVoltmeter of range (0-415V) with selector switch - 1 set Ammeter ofrange (0-1000A) with selector switch - 1 set 1000/5A, CL-1,10VA CT\"s with tape wound - 3 nos.7 Stage APFCR Controller. |
| 294 | Outgoings |
| 295 | 200A, TP ,25KA Thermal Magnetic MCCB with OverLoad & Short circuit Protections-2 No\"s. Each consisting of following 170A POWER CONTACTOR 7% DETUNED COPPER REACTOR 75KVAR CAPACITORBANK @ 480V MPP HEAVY DUTY CAPACITOR BANK |
| 296 | 63A, 3P , MCCB of 25KA breaking capacity with O/C, S/C, E/F and Thermal Magnetic based Releases- 2No\"s.Each consisting of following 110A POWER CONTACTOR7% DETUNED COPPER REACTOR 30KVAR CAPACITOR BANK @ 480VMPP HEAVY DUTY CAPACITOR BANK |
| 297 | 40A, 3P, MCCB of 10KA breaking capacity with O/C, S/C, E/F and Thermal Magnetic based Releases -1Nos. Each consisting of following.50A POWER CONTACTOR 7%DETUNED COPPER REACTOR 20KVAR CAPACITOR BANK @ 480VMPP HEAVY DUTY CAPACITOR BANK |
| 298 | 32A, 3P, MCCB of 10KA breaking capacity with O/C, S/C, E/F and Thermal Magnetic based Releases -2Nos. Each consisting of following.50A POWER CONTACTOR 7%DETUNED COPPER REACTOR5KVAR CAPACITOR BANK @ 480V MPP HEAVY DUTY CAPACITORBANK Note - All Capacitors Should be with DETUNED FILTERS. |
| 299 | Bus Bar.415V, 1000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 50 KA for 1 Sec. - LS |
| 300 | SPD This panel shall include Protection at the Main Distribution Board / Sub distribution board or in LT panel of the power supply system.Protection at the Main Distribution Board / Sub distribution board or in LT panel of the power supply system.Class B+C/Class I+II (according to IEC 61643 - 1)(THREE PHASE+ NEUTRAL) Class B+C/Class I+II (according to IEC 61643 - 1)Pluggable type SPD with potential free contact and thermal disconnector has to be connected between Line and Neutral and SPD of Spark Gap type between Neutral and Earth of following ratings should include base element & pluggable arresters. If required, remote signaling should be provided for remote monitoring purpose. Nominal Voltage, Un -230V, 50/60 Hz,Line to Neutral-MOV with built in thermal fuse,Neutral to Earth-Spark Gap Encapsulated / Non- exhausting,MCOV of 320V Nominal current -90 kA (8/20µ sec) - 30 kA each.Voltage protection level <1.4 kV. Protection Modes for : L & N toPE. Maximum Discharge Current Imax per pole-50 kA (8/20µsec) Mounting on -Din railMax. Back-up fuse-Up to 160 amps max. Depending up on panel design & breaking capacity.Approvals: OVEDegree of Protection:IP 20Operating temperature range:-40°C to +85°C Response Time-< 25nano seconds Make: -OBOModel Number- V50 3+ NPE,FS ,BACK UP FUSE NEEDED 160 A,3PHASE , 4 WIRE SYSTEM DIN RAIL MOUNTED SPD Class B+C/Class I+II Quantity-1No |
| 301 | MPCC ( The MPCC Consisting of the Following ) (LV SWITCH BOARD -2) |
| 302 | PLC PROGRAMMING |
| 303 | Incoming Feeders on BUS SECTION-1 |
| 304 | Incomer-2(From EB - Transformer - 4)EB I/C-4 |
| 305 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3NosMultifunction Meter(MFM) With RS485 communication port -1 No.,LED Type R- Y-B Phase Indication Lamps.- (1 set) , On,Off & Trip Indications: (1 sets), 4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 306 | Incoming Feeders on BUS SECTION-2 |
| 307 | Incomer-2(From EB - Transformer - 5)EB I/C-5 |
| 308 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R- Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications:(1 sets),4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 309 | Incoming Feeders on BUS SECTION-3 |
| 310 | Incomer-2(From EB - Transformer - 6)EB I/C-6 |
| 311 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R- Y-B Phase Indication Lamps. - (1 set), On,Off & Trip Indications: (1 sets ),4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 312 | Outgoing Feeders on BUS SECTION-1 |
| 313 | 630A, 4P, MCCB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -8 Nos(8DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R-Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications: (1 sets ), 630/5A, CL-1, 15VA, Tape woundCT\"s - 3Nos |
| 314 | 25A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Magnetic based Releases -1 Nos(1DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R-Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications: (1 sets ), 25/5A, CL-1, 15VA, Tape wound CT\"s - 3NosBusbar415V, 4000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65KA for 1 Sec. - LS (with 50% Neutral) |
| 315 | SPD This panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1Quantity-1No |
| 316 | BUS COUPLER |
| 317 | 4000A, 4P, EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and MicroProcessor based Releases |
| 318 | Outgoing Feeders on BUS SECTION-2 |
| 319 | 630A, 4P, MCCB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -11 Nos(11DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R-Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications: (1 sets ), 630/5A, CL-1, 15VA, Tape woundCT\"s - 3Nos |
| 320 | 25A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Magnetic based Releases 1 Nos(1DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R-Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications: (1 sets ), 25/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos, 415V, 4000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65KA for 1 Sec. - LS(with 50% Neutral) |
| 321 | SPD This panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1Quantity-2No |
| 322 | BUS COUPLER |
| 323 | 4000A, 4P, EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and MicroProcessor based Releases |
| 324 | Outgoing Feeders on BUS SECTION-3 |
| 325 | 630A, 4P, MCCB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -14 Nos(11DEDICATED + 3SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R-Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications: (1 sets ), 630/5A, CL-1,15VA, Tape wound CT\"s - 3Nos |
| 326 | 25A, 4P, MCCB of 25KA breaking capacity with O/C, S/C andThermal Mangnetic based Releases -2 Nos(1DEDICATED + 1SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos, Multifunction Meter(MFM) With RS485 communication port -1 No., LED Type R-Y-B Phase Indication Lamps.- (1 set), On,Off & Trip Indications: (1 sets ), 25/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos Busbar415V, 4000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65KA for 1 Sec. - LS (with 50%Neutral) |
| 327 | SPD This panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1 Quantity-1No |
| 328 | PUMP HOUSE SWITCH BOARD |
| 329 | Panel consisting of the following |
| 330 | Incoming Feeders on BUS SECTION-1 |
| 331 | Incomer-1(From Utility Switchboard Front )EB I/C-7 |
| 332 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No. , LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1sets ),4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 333 | Incoming Feeders on BUS SECTION-2 |
| 334 | Incomer-2(From EB - Transformer - 8)EB I/C-9 |
| 335 | 4000A, 4P, Motorized EDO ACB of 65KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1No\"sEach consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No. ,LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1sets ),4000/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos |
| 336 | Outgoing Feeders on BUS SECTION-1 |
| 337 | 1000A, 4P, EDO ACB of 50KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -1 Nos(1DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No.,LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1 sets ), 1000/5A, CL-1, 15VA, Tape woundCT\"s - 3Nos |
| 338 | 400A, 4P, MCCB of 35KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -5 Nos (4DEDICATED + 1SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No. ,LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1 sets ),400/5A, CL-1,15VA, Tape wound CT\"s - 3Nos |
| 339 | 250A, 4P, MCCB of 35KA breaking capacity with O/C, S/C, E/F and Micro Processor based Releases -3 Nos(2DEDICATED + 1SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No. ,LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1 sets ),250/5A, CL-1,15VA, Tape wound CT\"s - 3Nos |
| 340 | 100A, 4P, MCCB of 20KA breaking capacity with O/C, S/C and Thermal Magnetic based Releases -1 Nos(1SPARE). Each consisting of following. 6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port -1 No. ,LED Type R-Y- B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1 sets ), 100/5A, CL-1, 15VA, Tape wound CT\"s -3Nos |
| 341 | 63A, 4P, MCCB of 25KA breaking capacity with O/C, S/C and Thermal Magnetic based Releases -6 Nos(5 DEDICATED + 1SPARE). Each consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No. , LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off & Trip Indications: (1 sets ),63/5A, CL-1, 15VA, Tape woundCT\"s - 3Nos |
| 342 | 32A, 4P, MCCB of 25KA breaking capacity with O/C, S/C and Thermal Magnetic based Releases -4 Nos(4DEDICATED). Each consisting of following.6A, control MCBof C-Curve - 3Nos,Multifunction Meter(MFM) With RS485 communication port - 1 No. ,LED Type R-Y-B Phase Indication Lamps.- (1 set),On,Off &Trip Indications: (1 sets ), 32/5A, CL-1, 15VA, Tape wound CT\"s - 3Nos Busbar 415V, 4000A,3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65KA for 1 Sec. - LS (with 50% Neutral) |
| 343 | SPDThis panel shall include Mains Incoming Panel: Protection at the main incomer of the power supply system has to be connected at the Main Distribution Board after the incoming breaker. CLASS B SPD - TYPE I -MAIN DISTRIBUTION PANEL (THREE PHASE+ NEUTRAL). TheSPD should beconnected between Phase and Neutral and between Neutral and Earth with the following ratings:-1. Nominal Voltage, Un -230V, 50/60 Hz, Line to Neutral-MOV with built in thermal fuse, Neutral to Earth-Spark Gap Encapsulated / Non- exhausting, MCOV of 320V2. Total Impulse current -50 kA (10/350µ sec) - 12.5 kA each.3. Voltage protection level <1.5 kV.4.Protection Modes for: L & N to PE.Maximum Discharge Current Imax per pole-50 kA (8/20µsec)5. Mounting on -Din rail Max.6. Back-up fuse-Up to 500 amps max.7.Depending up on panel design & breaking capacity.8. Approvals :UL9. Degree of Protection : IP 2010. Operating temperature range:-40°C to +85°C11. Response Time-< 100 Nano seconds Remote signalling12. Visual Make: -OBO Model Number- ,MCD 50 B 0S -320 V+MCD 125 B NPE, BACK UP FUSE NEEDED 250 A, 3PHASE, 4 WIRE SYSTEM DIN RAIL MOUNTED SPD CLASS B SPD-TYPE-1Quantity-2No |
| 344 | EARTHING SYSTEM |
| 345 | Supply, Laying and fixing of 100 x 10mm GI flat |
| 346 | Supply, Laying and fixing of 50 x 6mm GI flat |
| 347 | Supply, Laying and fixing of 40 x 6mm GI flat |
| 348 | Supply, Laying and fixing of 30 x 6mm GI flat |
| 349 | Supply, Laying and fixing of 25 x 6mm GI flat |
| 350 | Supply, Laying and fixing of 25 x 3mm GI flat |
| 351 | Supply, Laying and fixing of 75 x 6mm Cu flat |
| 352 | 8 SWG GI wire |
| 353 | EARTH PITS |
| 354 | SITC Earth pit for the BODY with 100mm dia \"B\" class 2.5 long CI pipe with providing GI funnel covered with mesh of suitable size enclosed in a CC chamber of 450mm X 450mm X 3mm with suitable reinforced CI cover duly providing staggered holes of 16 nos of 12mm dia to the earth electrode filling salt and charcoal around 150mm from the bottom of the pipe to the bottom of CC chamber. The connections from the electrode through GI strip of 40 X 6mm length provided with suitable size of 14 nos holes with GI washers, nuts, bolts and all labour charges etc., complete.(For Transformers & HT panels Body) |
| 355 | SITC Earth station with copper plate Electrodes of 600mm X 600mm X 1.5mm with Connecting Wires are confriming to NBC - 2016,UL as well as Several National/International Standards.These maintenance free Plate Electrode offers Long Life , Electrode as well as Conductors are made of high Conductivity ,Non Corrosive Copper,Exothermically Welded to Copper conductor in order to offer Maximum Life ,Two Meter Long Two Rons of Connecting Wires Ensure deep burying of the Plates in Soil complete with excavation supply ,fixing and Conctructing brick chamber with cover plate having locking arrangements complete as per NBC-2016. Copper Plate need to be filled with 50Kgs of carbon based Low resistivity (0.0041 ohm per Mtr) Earth Enhancing compound as per IEC- 62561-7.The cost and coveyance of all materials, labour charges etc., complete for finished item of work. ( For TransformerNeutral)Note: All Earth Pit Chambers need to be Constructed with 100mm Solid Blocks. All Earth Pit Chambers to be Numbered and Painted with Reputed make Paint. |
| 356 | Design, supply ,Erection ,Testing and Commissioning of DC switch board of 0-550 V, DC, 1.5MWis required with all necessary accessories. Necessary incommer, outgoing all as per existing DC switch board are to be provided. |
| 357 | (a) Incomer Breaker 4000A DC Qty- 01(b) outgoing Breaker 630 Amps, Qty-16(c) MCB for control supply 230 V, Qty-01(d) Bus Bar rating 4000 Amps DC, CU, Bus Bar E91 Grade |
| 358 | Notes for Transformer, RMUs, VCBs, LT Panels, APFC Panels |
| 359 | (i) All installations shall be SCADA compatible (ii) The quoted rate shall include any type of civil work required for proper installation and making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (iii) Contractor shall submit requisite drawings, details, MOC, electrical circuits etc duly obtained from OEMs for the approval of users/accepting officer before procurement. (iv) All installations shall have provision for installation of Tube based fire suppression system (iv) The all dimensions shown in the tender drawings are to be rechecked and verified at site by the contractor (iv) Pre-dispatch Inspection and on-site inspection shall be carried out in presence of Testing Officer and necessary arrangement shall be made by the contractor without extra cost. (v) Completion drawings, test certificates/reports, maintenance manuals, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 360 | THIRD PARTY TECHNICAL INSPECTION |
| 361 | Contractor has to quote by considering the Third-Party TechnicalInspection of RMUs, Transformers, all LT Switchgears, APFC Panel, VCB Panel, DC Switch Board. TPTIshall be from any empaneled Testing agency. It shall include testing at factory premises before dispatch and at site while commissioning of installation. |
| 362 | SAFETY ACCESSORIES : ( Makes - OBO) |
| 363 | Supply and installation of following safety accessories. |
| 364 | 10 class dry powder type fire extinguishers |
| 365 | Pair of sand brockets (two buckets on one stand) |
| 366 | Shock treatment chart in Kannada and English duly framed |
| 367 | First Aid Box |
| 368 | Enamelled Danger Boards for 11KV |
| 369 | ABC Dry Chemical Powder fire Extingusher 1kg capacity stored pressure type fitted with guage and supplied complete with Intial charge wall bracket as per IS: 13489 with ISI mark. |
| 370 | ABC Dry Chemical Powder stored pressure type Fire extinuisher 2kg capacity fitted with pressure guage and supplied complete with Intial charge wall bracket as per IS: 13489 specificatioon. |
| 371 | ABC DCP stored pressure 5kgs. capacity Fired Extingushier. With discharge hose and Nozzle. Supplied complete with Intial charge wall bracket as per IS: 13489 with as ISI mark and ABC DCP powder is asper IS:14609 with ISI mark. |
| 372 | CO2 type Fire Extingushier 4.5kgs. Capacity made from Brand seam less drawn steel cylinder with High pressure Discharge hose and HORN supplied complete with Intial charge wall bracket as per IS:2878 specification with ISI mark. |
| 373 | 3 Buckets 9Ltr. Capacity with angle Iron stand |
| 374 | Dismantling, safe handling, and shifting of existing installations, including RMUs, HT < Panels, 2 MVA transformer,DC switch board system, LV Switchgears, APFC Panels, VCB Panels, frequencyconverter, Annunciation panel and associated accessories: |
| 375 | Dismantling of old serviceable or unserviceable outdoor/indoor transformers, switchgear panels, feeder pillar panels (floor-mounted cubicle type) along with associated busbars, metering units, fuses, switches, indication lamps, and accessories. This includes disconnecting power cables, safely handing over the dismantled equipment to the user, and completing all tasks as directed by the Engineer-in-Charge |
| 376 | Exisitng Transformer of various capacities upto 2 MVA |
| 377 | Exisitng HT panels including VCBs and RMUs |
| 378 | Existing LT switchgear panels, DC switch Panels and APFC panels ofvarious capaciters |
| 379 | Exisitng frequency converter, Annunciation panel |
| 380 | VENTILLATION : |
| 381 | Supply,Installation,TestinganddCommissioningofdoubleskin cabinettypeDIDWbackwardcurveddirectdrivencentrigugalfan with TEFC motor for Exhaust air. The fan assembly shall be enclosed inasheetmetalhousingof 22 gauge GSSand withnecessary inspection cover with proper gasket assembly. Flanges shall be providedon bothsides offan tofacilitate easyconnection. Flexible anti-vibration joints shall be provided to arrest vibration being transferred to other equipments connected to inline fan. Motor shall be single phase/three phase as per duty conditions. All single-phase fansshallbeprovidedwithspeedregulatorswhileallthreephase fans shall be provided with opposed blade dampers in GSS construction at fan outlet for air balancing. Including Necessary Stators. |
| 382 | 10000 cfm @ 50 mm TSP |
| 383 | 7500 cfm @ 50 mm TSP |
| 384 | 4800 cfm @ 50 mm TSP |
| 385 | 2400 cfm @ 50 mm TSP |
| 386 | Supply,Installation,TestinganddCommissioningofdoubleskin cabinet type DIDW forward curved direct driven centrigugal fan with TEFCmotorforFreshair.Thefanassemblyshallbeenclosedina sheet metal housing of 22 gauge GSS and with necessary inspection coverwithpropergasketassembly.Flangesshallbeprovidedon both sides of fan to facilitate easy connection. Flexible anti-vibration joints shall be provided to arrest vibration being transferred to other equipmentsconnectedtoinlinefan.Motorshallbesingle phase/three phase as per duty conditions. All single-phase fans shall be provided with speed regulators while all three phase fans shall be providedwithopposedbladedampersinGSSconstructionatfan outlet for air balancing.Including Necessary Stators. |
| 387 | 14000 cfm @ 50 mm TSP |
| 388 | 8000 cfm @ 50 mm TSP |
| 389 | 4800 cfm @ 50 mm TSP |
| 390 | 2400 cfm @ 50 mm TSP |
| 391 | DUCTING AND INSULATION |
| 392 | Supply, Installation, Testing and Commissioning of factory fabricated Box typeGSSDucting (with minimum 120 Gms /Sqmzinc coating) as per SMACNA/DW standards withsplitters, bends, elbows, vanes, suitable supports, minimum 6mm thick neoprene gasket, duct sealant (to be applied in all corners & joints), nuts, bolts, angle iron flanges (if required), GI full threaded rodshung to minimum 12 mm diaHILTImakeanchorfastnerasrequiredandPrepaintedslotted rail supports, etc. as per the specifications and approved drawings. |
| 393 | 24G |
| 394 | 22G |
| 395 | 20G |
| 396 | GRILLES, DIFFUSERS & DAMPERS |
| 397 | Supply, Installation, Testing and Commissioningof weather proof extruded aluminium powder coated Fresh Air louver withAluminium damper and washable GI wire mesh inside. |
| 398 | Supply, Installation, Testing and Commissioningof 6\" Height Extruded Al. Powder coatedDiscrete grills for supply air as per the specifications and approved drawings. (Colour to match the false ceiling as per the Client/ Consultant approval) |
| 399 | Supply, Installation, Testing and Commissioningof weather proof extruded aluminium powder coatedwith Aluminium collar damper and washable GI wire mesh inside. |
| 400 | Supply, Installation, Testingand Commissioning of Opposed type GI ZeroleakageVolumeControldamperswithmatchingflangesof sizes as per specification and approved drawings. |
| 401 | ELECTRICAL CONTROL PANEL OUTDOOR |
| 402 | Exhaust fan 5.5KWx2Nos,3.7KWx3Nos, Fresh air fan 7.5KWx 1 No, 3KW x 2Nos, Electrical starter panel consist of enclosure, ON/OFF push button, internal power, controllingwiring, ancillary contacts and accessories, indication, lamps etc. |
| 403 | Supply, installation, testing & commissioning of POWER CABLING of copper cable for indoor/outdoor units to be suitably laid in PVC conduit as per site requirment. |
| 404 | 4C x 4 sqmm (Copper) (from electrical panel to each unit) |
| 405 | 3C x 2.5 sqmm (Copper) (from electrical panel to each unit) |
| 406 | Dismantlingand Shifting of existing ventilation system, including ducts, fans, grilles, dampers, and associated components, with proper labeling. |
| 407 | Supply and installation of MS support/platform (channels/Angles) with painting and associated compontnts with pproper labeling. |
| 408 | Notes for Ventilation Fans |
| 409 | (i) Contractor shall provide suitable type & capacity starter panel without extra cost for ventilation fans with On/Off switch, LED indicators, electric protection devices, selector switches etc alongwith weather proof enclosure. (ii) Unless otherwise mentined in the tender dociment the following work shall be done by the contractor and therefore their cost shall be deemed to be inclided in in tendered cost wheather specially indicated in ;the schedule of the work or not:1) Sealing all slabs/filoor damaged for ducting, cabling etc with suitable plastering & painting as per site conditions 2)Opening, closing of all slab/floor for ducting, cabling etc with suitable plastering & painting as per site conditions3) Supports or cable trays for laying of cables 4) Three sets of completion drawings, Test certificates, catalogues etc shall be submitted by the contractor while handing over the system. 5) Testing and commissioning of complete ventilation system at site in presence of users and submissionof Test reports Notes for Dismantlingitaking down: |
| 410 | Notes for Dismantling: (i) All dismantled items are to be properly accounted for and handed over to the users and receipt voucher to be obtained from users. (ii) The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 411 | FIRE MAIN SYSTEM |
| 412 | PUMP |
| 413 | Supply, Transportation, Storing, Loading, Unloading, Positioning ,Handlling, Erection, Testing and Commissioning of the new salt water fire main vertical turbine pump and motor, 432.0 m3/hr of capacity and Bowl Head (H) =110.0 m with 250 mm Suction, 250 mmdischarge, Specific Gravity 1.2, Viscosity 31Cst, Motor Sq. Caghe Induction Motor, IE3, Bowl Efficiency 74%, Type of Pump - Vertical, Mounting - Vertical, Lubrication - Oil Lub, Starting Method - DOL, Sealing Type -MECHANICAL SEAL (DUPLEX BODY), Coupling Type- CI (FLEXIBLE), with all fittings, accessories, associated equipment and mandatory space complete as per Technical Specifications and as per relevant IEC / IS Specifications.MAKE: FLOWMORE, FLOWSERVE, SULZER, KSB |
| 414 | Supply, Transportation, Storing, Loading, Unloading, Positioning ,Handlling, Erection, Testing and Commissioning of the new salt watervertical turbine Jockey pump and motor, 180.0 m3/hr capacity and Bowl Head (H) =110.0m with 200 mm Suction,200 mm discharge, Specific Gravity 1.2, Viscosity 31 Cst, Bowl Efficiency 74%, Type of Pump - Vertical Turbine, Mounting - Vertical,Lubrication - Oil Lub, Starting Method - DOL, Sealing Type - MECHANICAL SEAL (DUPLEX BODY), Coupling Type- CI (FLEXIBLE), with all fittings, accessories, associated equipment and mandatory space complete as per Technical Specifications and as per relevant IEC / IS Specifications RECOMMENDED MAKE:FLOWMORE, FLOWSERVE, SULZER, KSB |
| 415 | Notes for pumpsets : (i) The pumpset shall be SCADA compatible (ii) The quoted rate shall include any type of civil work required for proper installation of pumpsets, making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (ii) The all dimensions shown in the tender drawings are to be rechecked and verified at site by the contractor (iii) Contractor shall submit requisite drawings, details, MOC, electrical circuits etc duly obtained from OEMs for the approval of users/accepting officer before procurement. (iv) Pre-commissioing test of Fire-main system shall be carried out as per standard practice or as per OEM recommendation in presence of Testing Officer and the cost deemed to be included in the quoted rate. (ii) Completion drawings, test certificates/reports, maintenance manuals, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 416 | Design, SITC of MCC PANEL: 1000A TPN EDO TYPE ACB 50KA -1, INDICATING LAMP – R / Y/ B -1set, DIGITAL AMMETER -1, DIGITAL VOLTMETER -1, CURRENT TRANSFORMER -3, INDICATING LAMP – R / Y/ B -1set, PLC -1, 6A SP MCB C-CURVE -1275 KW VFD STARTER – 2 NO. 275 KW VFD -1, 320A TPN MCCB MA TYPE 50KA -1,265A CONTACTOR-1, AUTO/MANUAL SEL. SW-1, INDICATING LAMP – ON / OFF/ TRIP1set, PUSH BUTTON - START-STOP 1set, 6A SP MCB, 10KA -1JOCKEY PUMP PANEL INCOMER : 630A TPN MCCB TM BASED 36KA -1, EXT.HANDLE-1 SPREDER-2, INDICATING LAMP – R / Y/ B -1set, DIGITAL AMMETER -1, DIGITAL VOLTMETER-1, CURRENT TRANSFORMER -3, INDICATING LAMP – R / Y/ B -1set, PLC -1, 6A SP MCB C-CURVE-1110 KW VFD STARTER – 2 NO. 110 KW VFD -1, 220A TPN MCCB MA TYPE 50KA -1,185A CONTACTOR -1, AUTO/MANUAL SEL. SW -1, INDICATING LAMP – ON / OFF/ TRIP-1 Set, PUSH BUTTON - START-STOP -1set, 6A SP MCB, 10KA-1.Outdoor MCC Panel (3.2mm): The Motor Control Center (MCC) panel is designed for outdoor installation and constructed with a robust 3.2mm thickness for enhanced durability and weather resistance. It features a powder-coated enclosure, IP55 protection for environmental safety, and accommodates modular compartments for motor starters, feeders, and control units. The panel ensures reliable performance under extreme conditions and complies with relevant IS/IEC standards. |
| 417 | Notes for Panels : (i) The panel shall be SCADA compatible (ii) The quoted rate shall include any type of civil work required for proper installation of panel, making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (ii) The all dimensions shown in the tender drawings are to be rechecked and verified at site by the contractor (iii) Contractor shall submit requisite design drawings, details, MOC, electrical circuits etc duly obtained from OEMs for the approval of users/accepting officer before procurement. (iv) The panel shall have SCADA feature and it shall becompetible with the Fire pumps catered here-above. (v) The quoted rate shall include taking down of existing panel, shifting to the users premises and handing it over to users |
| 418 | PIPE |
| 419 | Supply, Installation, Testing and commissioning of 14 inch (350 mm) nominal diameter ductile iron(DI) pipe confirming to ISO 2531/EN 545 standards of class K9. The pipe must be capable of withstanding a working pressure of 8.5 Barg. Rates of fittings shall be paid as measured at site. Cost of MS supports is deemed to be included in the quoted rate. |
| 420 | Supply, Installation, Testing and commissioning of 12 inch (300 mm) nominal diameter ductile iron(DI) pipe confirming to ISO 2531/EN 545 standards of class K9. The pipe must be capable of withstanding a working pressure of 8.5 Barg. Rates of fittings shall be paid as measured at site. Cost of MS supports is deemed to be included in the quoted rate. |
| 421 | Supply, Installation, Testing and commissioning of 10 inch (250 mm) nominal diameter ductile iron(DI) pipe confirming to ISO 2531/EN 545 standards of class K9. The pipe must be capable of withstanding a working pressure of 8.5 Barg. Rates of fittings shall be paid as measured at site. Cost of MS supports is deemed to be included in the quoted rate. |
| 422 | Supply, Installation, Testing and commissioning of 8 inch (200 mm) nominal diameter ductile iron(DI) pipe confirming to ISO 2531/EN 545 standards of class K9. The pipe must be capable of withstanding a working pressure of 8.5 Barg. Rates of fittings shall be paid as measured at site. Cost of MS supports is deemed to be included in the quoted rate. |
| 423 | Supply, Installation, Testing and commissioning of 6 inch (150 mm) nominal diameter ductile iron(DI) pipe confirming to ISO 2531/EN 545 standards of class K9. The pipe must be capable of withstanding a working pressure of 8.5 Barg. Rates of fittings shall be paid as measured at site. Cost of MS supports is deemed to be included in the quoted rate. |
| 424 | Supply, Installation, Testing and commissioning of 4 inch (100 mm) nominal diameter ductile iron(DI) pipe confirming to ISO 2531/EN 545 standards of class K9. The pipe must be capable of withstanding a working pressure of 8.5 Barg. Rates of fittings shall be paid as measured at site. Cost of MS supports is deemed to be included in the quoted rate. |
| 425 | REDUCER |
| 426 | Supply, installation, testing, and commissioning of a 14-inch to 12-inch ductile iron pipe reducer. The ductile iron reducer must be designed and manufactured according to ISO 2531 or equivalent standards, ensuring it is suitable for sea water or fluid conveyance systems. The reducer must be rated for a working pressure of 8.5 bar (PN 10). The reducer should be installed using proper pipe alignment techniques, andjointing must be completed |
| 427 | Supply, installation, testing, and commissioning of a 12-inch to 10-inch ductile iron pipe reducer. The ductile iron reducer must be designed and manufactured according to ISO 2531 or equivalent standards, ensuring it is suitable for sea water or fluid conveyance systems. The reducer must be rated for a working pressure of 8.5 bar (PN 10). The reducer should be installed using proper pipe alignment techniques, andjointing must be completed |
| 428 | Supply, installation, testing, and commissioning of a 12-inchto 8 -inch ductile iron pipe reducer. The ductile iron reducer must be designed and manufactured according to ISO 2531 or equivalent standards, ensuring it is suitable for sea water or fluid conveyance systems. The reducer must be rated for a working pressure of 8.5 bar (PN 10). The reducer should be installed using proper pipe alignment techniques, and jointing must be completed |
| 429 | Supply, installation, testing, and commissioning of a 12-inch to 6-inch ductile iron pipe reducer. The ductile iron reducer must be designed and manufactured according to ISO 2531 or equivalent standards, ensuring it is suitable for sea water or fluid conveyance systems. The reducer must be rated for a working pressure of 8.5 bar (PN 10). The reducer should be installed using proper pipe alignment techniques, and jointing must be completed |
| 430 | Supply, installation, testing, and commissioning of a 12-inch to 4-inch ductile iron pipe reducer. The ductile iron reducer must be designed and manufactured according to ISO 2531 or equivalent standards, ensuring it is suitable for sea water or fluid conveyance systems. The reducer must be rated for a working pressure of 8.5 bar (PN 10). The reducer should be installed using proper pipe alignment techniques, and jointing must be completed |
| 431 | ELL 90 LR |
| 432 | Supply, installation, testing, and commissioning of 12-inch (300mm nominal diameter) Ductile Iron (DI) 90° Long Radius (LR) Elbow with flange/socket end connections, conforming to ISO 2531/EN 545 standards. The DI elbow shall be manufactured from high-strength ductile iron.The fitting shall be rated to maintain a pressure of 8.5 bar |
| 433 | Supply, installation, testing, and commissioning of10-inch (250mm nominal diameter) Ductile Iron (DI) 90° Long Radius (LR) Elbow with flange/socket end connections, conforming to ISO 2531/EN 545 standards. The DI elbow shall be manufactured from high-strength ductile iron.The fitting shall be rated to maintain a pressure of 8.5 bar |
| 434 | Supply, installation, testing, and commissioning of 8-inch (200mm nominal diameter) Ductile Iron (DI) 90° Long Radius (LR) Elbow with flange/socket end connections, conforming to ISO 2531/EN 545 standards. The DI elbow shall be manufactured from high-strength ductile iron.The fitting shall be rated to maintain a pressure of 8.5 bar |
| 435 | Supply, installation, testing, and commissioning of 6-inch (150mm nominal diameter) Ductile Iron (DI) 90° Long Radius (LR) Elbow with flange/socket end connections, conforming to ISO 2531/EN 545 standards. The DI elbow shall be manufactured from high-strength ductile iron.The fitting shall be rated to maintain a pressure of 8.5 bar |
| 436 | ELL 45 LR |
| 437 | Supply, installation, testing, and commissioning of 6-inch (150mm nominal diameter) Ductile Iron (DI) 45° Long Radius (LR) Elbow with flange/socket end connections, conforming to ISO 2531/EN 545 standards. The DI elbow shall be manufactured from high-strength ductile iron.The fitting shall be rated to maintain a pressure of 8.5 bar |
| 438 | ELL 120 LR |
| 439 | Supply, installation, testing, and commissioning of 6-inch (150mm nominal diameter) Ductile Iron (DI) 120° Long Radius (LR) Elbow with flange/socket end connections, conforming to ISO 2531/EN 545 standards. The DI elbow shall be manufactured from high-strength ductile iron.The fitting shall be rated to maintain a pressure of 8.5 bar |
| 440 | FLANGE SO |
| 441 | Supply, installation, testing, and commissioning of 12-inch diameter Ductile Iron (DI) pipes with flanged ends (Flange Slip-On, SO) conforming to ISO/EN standards for ductile iron pipes. Pipe designed to withstand 8.5 bar pressure (PN10 or higher rating), including necessary flanged fittings, gaskets, bolts, and nuts. Hydrostatic pressure testing to be conducted at 1.5 times the design pressure (i.e., 12.75 bar) to ensure the integrity of the installation. The installation shall comply with all relevant standards and codes, including pressure class requirements and material standards, to ensure system reliability and longevity. |
| 442 | Supply, installation, testing, and commissioning of 10-inch diameter Ductile Iron (DI) pipes with flanged ends (Flange Slip-On, SO) conforming to ISO/EN standards for ductile iron pipes. Pipe designed to withstand 8.5 bar pressure (PN10 or higher rating), including necessary flanged fittings, gaskets, bolts, and nuts. Hydrostatic pressure testing to be conducted at 1.5 times the design pressure (i.e., 12.75 bar) to ensure the integrity of the installation. The installation shall comply with all relevant standards and codes, including pressure class requirements and material standards, to ensure system reliability and longevity. |
| 443 | Supply, installation, testing, and commissioning of 8-inch diameter Ductile Iron (DI) pipes with flanged ends (Flange Slip-On, SO) conforming to ISO/EN standards for ductile iron pipes. Pipe designed to withstand 8.5 bar pressure (PN10 or higher rating), including necessary flanged fittings, gaskets, bolts, and nuts. Hydrostatic pressure testing to be conducted at 1.5 times the design pressure (i.e., 12.75 bar) to ensure the integrity of the installation. The installation shall comply with all relevant standards and codes, including pressure class requirements and material standards, to ensure system reliability and longevity. |
| 444 | Supply, installation, testing, and commissioning of 6-inch diameter Ductile Iron (DI) pipes with flanged ends (Flange Slip-On, SO) conforming to ISO/EN standards for ductile iron pipes. Pipe designed to withstand 8.5 bar pressure (PN10 or higher rating), including necessary flanged fittings, gaskets, bolts, and nuts. Hydrostatic pressure testing to be conducted at 1.5 times the design pressure (i.e., 12.75 bar) to ensure the integrity of the installation. The installation shall comply with all relevant standards and codes, including pressure class requirements and material standards, to ensure system reliability and longevity. |
| 445 | Supply, installation, testing, and commissioning of 4-inch diameter Ductile Iron (DI) pipes with flanged ends (Flange Slip-On, SO) conforming to ISO/EN standards for ductile iron pipes. Pipe designed to withstand 8.5 bar pressure (PN10 or higher rating), including necessary flanged fittings, gaskets, bolts, and nuts. Hydrostatic pressure testing to be conducted at 1.5 times the design pressure (i.e., 12.75 bar) to ensure the integrity of the installation. The installation shall comply with all relevant standards and codes, including pressure class requirements and material standards, to ensure system reliability and longevity. |
| 446 | TEE |
| 447 | Supply, installation, testing, and commissioning of12-inch ductile iron TEE, designed to maintain a pressure of 8.5 bar,The TEE shall be constructed from ductile iron conforming to ISO 2531 or EN 545 standards,The pressure rating must be PN10 (10 bar) or higher, ensuring it withstands 8.5 bar of working pressure with a safety margin.Each TEE shall be hydrostatically tested at 1.5 times the working pressure (i.e., 12.75 bar) to ensure integrity and leak-proofperformance. |
| 448 | Supply, installation, testing, and commissioning of 10-inch ductile iron TEE, designed to maintain a pressure of 8.5 bar,The TEE shall be constructed from ductile iron conforming to ISO 2531 or EN 545 standards,The pressure rating must be PN10 (10 bar) or higher, ensuring it withstands 8.5 bar of working pressure with a safety margin.Each TEE shall be hydrostatically tested at 1.5 times the working pressure (i.e., 12.75 bar) to ensure integrity and leak-proof performance. |
| 449 | Supply, installation, testing, and commissioning of 8-inch ductile iron TEE, designed to maintain a pressure of 8.5 bar,The TEE shall be constructed from ductile iron conforming to ISO 2531 or EN 545 standards,The pressure rating must be PN10 (10 bar) or higher, ensuring it withstands 8.5 bar of working pressure with a safety margin.Each TEE shall be hydrostatically tested at 1.5 times the working pressure (i.e., 12.75 bar) to ensure integrity and leak-proof performance. |
| 450 | Gasket, SWG |
| 451 | Supply, installation, testing, and commissioning of Ductile iron gasket with a nominal diameter of 12 inches (DN300), compliant with IS/BS/ASTM standards, The gasket material should be of high-grade ductile iron capable of withstanding operational conditions up to 8.5 bar, All components must be corrosion-resistant, durable, and designed for a secure and leak-proof connection between flanges in pipeline systems. |
| 452 | Supply, installation, testing, and commissioning of Ductile iron gasket with a nominal diameter of 10 inches (DN300), compliant with IS/BS/ASTM standards, The gasket material should be of high-grade ductile iron capable of withstanding operational conditions up to 8.5 bar, All components must be corrosion-resistant, durable, and designed for a secure and leak-proof connection between flanges in pipeline systems. |
| 453 | Supply, installation, testing, and commissioning of Ductile iron gasket with a nominal diameter of 8 inches (DN300), compliant with IS/BS/ASTM standards, The gasket material should be of high-grade ductile iron capable of withstanding operational conditions up to 8.5 bar, All components must be corrosion-resistant, durable, and designed for a secure and leak-proof connection between flanges in pipeline systems. |
| 454 | VALVES &INSTRUMENATION |
| 455 | Supply and Fixing of Gate Valve, flanged of class 1.6 PN 350mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 456 | Supply and Fixing of Gate Valve, flanged of class 1.6 PN 300mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 457 | Supply and Fixing of Gate Valve, flanged of class 1.6 PN 250mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 458 | Supply and Fixing of Gate Valve, flanged of class 1.6 PN 200mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 459 | Supply, installation, testing, and commissioning of12\" (300mm) diameter non-return valve (NRV) made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. The valve shall be equipped with a resilient sealing mechanism to prevent backflow and ensure proper unidirectional flow. The valve body, seat, and disc materials should be corrosion- resistant and suitable for high-pressure applications, The scope of work includes the necessary fittings for a complete installation, as well as testing and commissioning to verify the performance under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. |
| 460 | Supply, installation, testing, and commissioning of 6\" (150mm) diameter non-return valve (NRV) made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. The valve shall be equipped with a resilient sealing mechanism to prevent backflow and ensure proper unidirectional flow. The valve body, seat, and disc materials should be corrosion- resistant and suitable for high-pressure applications, The scope of work includes the necessary fittings for a complete installation, as well as testing and commissioning to verify the performance under specified pressure conditions. All workmanship and materials must comply with relevant international standards and codes. |
| 461 | Supply and Fixing of Butterfly Valve, flanged of class 1.6 PN 300mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 462 | Supply and Fixing of Butterfly Valve, flanged of class 1.6 PN 300mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 463 | Supply and Fixing of Pressure reduced valve, flanged of class 1.6 PN 100mm dia made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. (At every cope point) |
| 464 | Supply and fixing of Globe valves 100mm Gun-metal, ball, globe or gate valves, with iron wheel head, screwed both endsfor iron pipe and fixed |
| 465 | Supply and fixing of Globe valves 150mm Gun-metal, ball, globe or gate valves, with iron wheel head, screwed both endsfor iron pipe and fixed |
| 466 | Supply and Fixing of Sluice Valve, flanged of class 1.6 PN 300mm dia made of high- grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 467 | Supply and fixing of pressure switch. |
| 468 | Supply and fix of cope points with 200mm to 100mm diameter, including necessary end fittings, securing arrangements, and related accessories for jetty installation. |
| 469 | Supply and fixing of Ball valves 100mm dia madeup of SS including end fittings, securing arrangements and related accessories for jetty. |
| 470 | Supply and fix of cope points with 100mm diameterwith bronze material including necessary end fittings, securing arrangements, and related accessories for jetty installation. |
| 471 | Supply and fixing of 300mm dia electricity operated valve made of high-grade ductile iron, conforming to IS/BS standards, capable of withstanding and maintaining a working pressure of 8.5 bar. |
| 472 | STUD BOLTS SET |
| 473 | supply and delivery of ductile iron stud bolt sets suitable for a 4-inch piping system in a raw water application. The stud bolts shall be manufactured from high-strength, corrosion-resistant ductile iron material in accordance with ASTM A536 or equivalent standards. Each set shall include fully threaded studs with nuts and washers, designed for flange connections. The stud bolt set shall be provided in compliance with IS/BS/ISO standards for water treatment and distribution systems. The quantity, size, and threading shall match the specifications of the associated flanges, ensuring secure and leak-proof assembly. Each set shall be delivered complete with all accessories required for proper installation. |
| 474 | supply and delivery of ductile iron stud bolt sets suitable for a 6-inch piping system in a raw water application. The stud bolts shall be manufactured from high-strength, corrosion-resistant ductile iron material in accordance with ASTM A536 or equivalent standards. Each set shall include fully threaded studs with nuts and washers, designed for flange connections. The stud bolt set shall be provided in compliance with IS/BS/ISO standards for water treatment and distribution systems. The quantity, size, and threading shall match the specifications of the associated flanges, ensuring secure and leak-proof assembly. Each set shall be delivered complete with all accessories required for proper installation. |
| 475 | supply and delivery of ductile iron stud bolt sets suitable for a 8-inch piping system in a raw water application. The stud bolts shall be manufactured from high-strength, corrosion-resistant ductile iron material in accordance with ASTM A536 or equivalent standards. Each set shall include fully threaded studs with nuts and washers, designed for flange connections. The stud bolt set shall be provided in compliance with IS/BS/ISO standards for water treatment and distribution systems. The quantity, size, and threading shall match the specifications of the associated flanges, ensuring secure and leak-proof assembly. Each set shall be delivered complete with all accessories required for proper installation. |
| 476 | supply and delivery of ductile iron stud bolt sets suitable for a 10-inch piping system in a raw water application. The stud bolts shall be manufactured from high-strength, corrosion-resistant ductile iron material in accordance with ASTM A536 or equivalent standards. Each set shall include fully threaded studs with nuts and washers, designed for flange connections. The stud bolt set shall be provided in compliance with IS/BS/ISO standards for water treatment and distribution systems. The quantity, size, and threading shall match the specifications of the associated flanges, ensuring secure and leak-proof assembly. Each set shall be delivered complete with all accessories required for proper installation. |
| 477 | supply and delivery of ductile iron stud bolt sets suitable for a 12-inch piping system in a raw water application. The stud bolts shall be manufactured from high-strength, corrosion-resistant ductile iron material in accordance with ASTM A536 or equivalent standards. Each set shall include fully threaded studs with nuts and washers, designed for flange connections. The stud bolt set shall be provided in compliance with IS/BS/ISO standards for water treatment and distribution systems. The quantity, size, and threading shall match the specifications of the associated flanges, ensuring secure and leak-proof assembly. Each set shall be delivered complete with all accessories required for proper installation. |
| 478 | HYDRANTS &INSTRUMENATION |
| 479 | Supply, Storing, Positioning ,Handlling, Installation, Testing and Commissioning of Electromagnetic Flowmeter system & Fixing Flow Meters, Explosion Protection Certification Y0 Without, Housing Type / Housing Material / Cable Glands S1 Single compartment / Aluminium / M20 x 1.5, Meter Size 0040 DN 40 (1-1/2 in.),Process Connection Type D4 Flanges DIN PN 40, Liner Material T1 PTFE, Process Connection Material B Carbon steel, Electrode Design 1 Standard, Measuring Electrodes Material D Alloy C-4 (2.4610), Grounding Electrode / Full Pipe Detection 0 No grounding electrode / No full pipe detection, Grounding Accessories A Without, Protection Class Transmitter / Protection Class Sensor 70 IP 67 / IP 67, Power Supply A 100 … 230 V AC, 50 Hz, Display 2 Display with Keypad, Outputs G0 1 Current output (active or passive), 2 Digitial Outputs (passive), HART, Design Level A Design Level A, Option Card 1 DR0 Without, Option Card 2 DS0 Without, Usage Certifications C0 Without, Calibration Certification, Other Usage Certifications CRP Meter tube with PED certificate, Sensor Length J6 ,Other Options K0 Without, Pressure Bearing Parts material Source MS0 Standard, Tests and Reports CR0 Without, Sensor Housing Material, Configuration Type NC1 Parameters set to factory defaults, Transmitter Software Function Package, Calibration Type RCD 0,4 % Factory Calibration, Signal Cable SC0 Without, Device Identification PlateAdhesive label, Temperature Range of Installation / Ambient Temperature Range -20 … 60 °C (-4 … 140 °F), Number of Testpoints TV2 2 Points, Verification Capability V0 Disabled. |
| 480 | Supply & Fixing Pressure Guages |
| 481 | Supply, Transportation, Storing, Loading, Unloading, Positioning ,Handlling, Erection,Testing and Commissioning of the High performance 8\" gauge pressure transmitter & Fixing Pressure Transmitters, Sensor Span Limits / Sensor Overpressure / Base Accuracy: 24 and 2400 kPa (0.24 and 24 bar, 3.5 and 348 psi) / 21M Diaphragm Material / Fill Fluid: Hastelloy C-276 / Silicone oil (NACE) Process Connection Material / Type: Hastelloy C-276 / 1/2-14 NPT female (NACE) Housing Material / Electrical Connection: Aluminium alloy (Barrel version) / 1/2-14 NPT Output: Standard HART digital communication and 4 to 20 mA |
| 482 | M&L for temporary arrangement for uninterrupted firemain water supply during the replacement of pumps and its pipeline for the fire main system, it is essential to ensure uninterrupted firemain water supply to the isolated jetty to achieve this, the contractor shall arange a comprehensive temporary setup this temporary arrangement shall provide continuous and reliable fire water flow to a minimum of four hydrants throughout rhe replacement work. |
| 483 | Notes for Firemain pipelines |
| 484 | (i) The all dimensions shown in the tender drawings and hydraulic calculations are to be rechecked and verified at site by the contractor (ii) The quoted rate shall include any type of civil work required for proper installation of pipelines, valves etc, making good to the existing structure etc. (ii) Contractor shall visit the site with the prior permission from DGNP cell before quoting rates (iii) Contractor shall submit requisite layout drawings, details for the approval of users/accepting officer before procurement. (iv) Pre-commissioning test of pipeline shall be carried out as per standard practice in presence of Testing Officer and the cost deemed to be included in the quoted rate. (ii) Completion drawings, test certificates/reports, PRBs etc required for proper handing taking with users shall be provided by the contractor without extra cost. |
| 485 | SCADA |
| 486 | Design supply, install, Testing 7 Commissioning SCADA system for FIreMain System including all required items consisting of Hardware :Programmable Logic Controller - 24 VDC, 2x ETHERNET, 1x RS232/485 - Qty -1,Analog Input Module 16AI U/I/PT100 12bit+sign, 2-wire -Qty-1, Analog IO Mod 4AI/2AO U/I 12bit+sign 24VDC 2 wire in 1 wire out-Qty -3 ,Digital Input Mod 16DI 24VDC DI 24VDC Sink/source 1 wire-Qty - 1, Digital Out Mod 8DO Transistor DO Transistor 24VDC/0 5A 1 wire Qty - 1, SCADA SOFTWARE : ABB - SCADA for 1 Engineering /Operator station and 1 Operator station with license dongle for USB support Qty - 1, 8-port Ethernet Switch,D-LinkQty -2,Ethernet CAT 6 UTP STANDARD CABLE Mtr, Reputed , Qty100, RJ 45 Connectors, D Link qty -10, Ethernet to OFC Converters, Reputed qty 2,LI Unit - 6 Port ,D-Link 2, Patch Cords, D-Link, qty 4 ,OFC Cable , D-Link , qty 3000, RJ 45 Connectors, D Link qty 20,PC for Engineering/Operations :Dell Optiplex Desktop - Intel Core i7 14th Gen Processor / 16 GB DDR-IVRam / 1 TB Sata HDD / DVD-Rw / Dell USB KB+ Mouse / 2 DP Port /Windows LTSC License / Giga Lan Port / 6 USB Port / Dell 24\" LED Monitor dell, qty-2 |
| 487 | Comprehensive backup of all project-related software including PNC, SCADA ststem, HMIs and associated configuration, files shall be provided in a sedured external storage device. The backup shall include the latest commissioned version along with necessary installation files and documentation. |
| 488 | Complete administrative access credentials(admin rights) for all PLCs, SCADA, HMI and software interfaces including those for variables frequency device (VFDs) shall be handed over to the end user to ensure full control configuratio and future maintenance capabilities. |
| 489 | Note for SCADA : (i) SCADA shall be designed, developed, integrated and commissioned consisting of all required accessories. (ii) Contractor shall submit OEM approved design, drawings, layout etc for the approval of users/accepting officer before procurement. (iii) Cloud based server/data storage/communication shall not be used and only local server based system shall be designed. (iv) SCADA system should have provision of both manual and automatic operation of installations (v) Suitable communication system including payment of bills to telecom service provider till expiry of Defect Liability Period without extra cost to the department (vi) COst of Items not mentioned here-in but required invariably for proper functioning of SCADA system is deemed to be included in the quoted rate |
| 490 | CABLES |
| 491 | Supply and laying 2 core x 1.5 Sqmm multistrand armoured RM control cable for connecting pressure sensor to loop control panel |
| 492 | Supply and Laying of Fibre optic cable for networking of RM addressable panel with HDPE conduit |
| 493 | HYDRO PNEUMATIC TANK: Supply & fixing Zilmet Hydro Pro expansion tank with fixed membrane,Carbon Steel Construction, Capacity - 500 litres,Type - Vertical,connection - G1 1/4,Max working pressure - 10kg/cm2,. |
| 494 | DISMANTLING: |
| 495 | Removal of pump, motor, and all associated accessories from Pump Houses. Disconnecting power supply and safely detaching the equipment from its current position. Disassembly of the pump and motor unit, including any necessary dismantling of mounting brackets, piping, and connections. Proper handling and shifting to the contractorlocation of removed components in compliance with local regulations and environmental standards. Cleaning and tidying of the work area post- removal. Note: All the dismantled Pumps have to be handedover to the End user. |
| 496 | Dismantling of existing pipe upto 14 inch nominal diameter alongwith fittings and loading, transporting, unloading and handing over to users. The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 497 | Dismantling of existing any type of valve of size 350mm to 200 mm dia and loading, transporting, unloading and handing over to users. The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 498 | Dismantling of existing any type of valve of size upto 150mm dia and hydrants, instantaneous female outlets etc and loading, transporting, unloading and handing over to users. The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 499 | Dismantling of existing pipe fittings bends, reducers, tee etc of any type and loading, transporting, unloading and handing over to users. The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 500 | Taking down existing Cable any size from MCC to Starter panel and from starter panel to motor for Jockey Pumps and handing over to users |
| 501 | Notes for Dismantling: (i) All dismantled items are to be properly accounted for and handed over to the users and receipt voucher to be obtained from users. (ii) The quoted rate shall include cost of making good to the damages caused during dismantling and shifting to the users premises. |
| 502 | PLATFORM FOR STORAGE TANKS |
| 503 | M&L for cutting into RCCwall/roof of jetty upto depth 1.08m and trimming surface as required girth exc 30cm. |
| 504 | S&F of PVC pipe 300mm dia 1.08m length into holes with necessary repair work in RCC 1:1:5:3 at jetty for cope point at places in jetty where directed. |
| 505 | Providing. fixing, testing, commissioning, operating and maintaining temporary arrangement for uninterrupted fire-fighting water supply during replacement of existing fire main pipeline to be executed in sectional lengths (typical isolation about 30 m). complete all as directed by GE (DD) including temporary by pass/bridging across each isolated section using adequately sized fire-duty hoses/MS/HDPE pipeline (PN16/PN20 or higher) with restrained couplings.supports, thrust restraint/anchoring, road-crossing protection and safety barricading, complete with all required approved tie-ins/tapping, isolation valves, NRVs, fittings/specials, gaskets/fasteners, pressure gauges and approved flow measurement arrangement, operation manpower, continuous monitoring emergency restoration readiness, dismanting/removal after reinstatement of permanent pipeline and making good disturbed surfaces, the temporary arrangement shall conform to latest editfions of IS 13039 (Fire Hydrant Systems - Code of Practice) and relevant IS provisions for fire pumps/installation as applicable, and shall mandatorily be capable of supplying minimum 3 hydrants x 960 LPM each (total 2880 LPM) simultaneously while maintaining residual pressure 6.0 to 8.0 bar at identified critical hydrant point under discharge inclusive of all losses. |
| 506 | NOTES-REPLACEMENT OF TWO (02) MAIN FIRE PUMPS WITHOUT INTERRUPTION (DUTY- STANDBY CHANGE OVER BASIS): Replacement/renewal of existing salt-water vertical turbine main fire pumps (02 Nos) with new pumps of identical rated duty and specifications, to be carried out in a staged manner ensuring uninterrupted firemain service at all times, i.e.. one existing (old)main pump shall remain continuously aperational/available as duty to the common discharge header while the other existing (old) main pump, being standby is isolated and removed and replaced with the new pump: upon completion, testing and commissioning of the first new pump and making it available on auto as standby/duty-ready, the contractor shall thereafter keep the newly installed pump available and proceed to isolate, remove and replace the remaining existing (old) main pump such that at no time both main pumps are simultaneously out of service and fire water supply to the firemain network is not interrupted, the item shall include all required isolations. changeover operations, dismantling, erection. alignment.mechanical seal/coupling fitment, electrical terminations and protections integration, pre-commissicnig checks, trial run, functional proving on header pressure, and final restoration of duty/siandby arrangement complete, all as directed by GE and to the satisfaction of the Accepting Officer |
| 507 | Subtotal |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail