| 1 | PART -I - SPL REP FOR REPLACEMENT OF BER CEILING/EXHAUST FANS WITH CONNECTED WORK OF MTTI |
| 2 | M & L for point wiring with 1.5 Sqmm (nominal area) PVC insulated,FRLSH unsheathed, multistrand, 1100 volts grade copper conductor cable single core, drawn through with and including non metallic PVC conduit 25mm dia and its accessories surface type etc including one run of 1.5 Sqmm PVC insulated copper conductor cable green in colour for continuous earthing, 1.6 mm thick MS terminal box finished to wall/steel structure with 3 mm thick laminated hylam sheet top cover all as specified for :-(a) One Ceiling fan point controlled by one switch. |
| 3 | (b) One Exhaust fan point controlled by one switch. |
| 4 | S&F switch piano, flush type single pole, one way 5 Amps complete all as specified. |
| 5 | M&L ceiling rose, 3 phase/PVC/Polycarbonate, isolated body complete all as specified. |
| 6 | S&F Electronic fan regulator, flush type phenolic laminated sheet etc as required. |
| 7 | Supply & fix ceiling fans ceiling BLDC type complete with accessories 230 V,1200 mm sweep. BEE 5 star rated with provn of necesary hanging hook on ceiling complete all as specified and directed. |
| 8 | Supply & fix ceiling fans ceiling BLDC type complete with accessories 230 V,1400 mm sweep. BEE 5 star rated with provn of necesary hanging hook on ceiling complete all as specified and directed. |
| 9 | S&F of Exhaustfan, heavy duty, 450 mm sweep, 1425 RPM, with louvers, metal body conforming to IS, AC singlephase, 240 Volts, 50 Hzand connecting including provision of two way PVC connectors, 1.50 sqmm flexible three core multistranded copperconductorcablefromceilingroseor connectorto fan including earthing and fixing arrangements like making hole in wall and finishing to shape to match adjoining surface complete all as specified and directed. |
| 10 | PART -II - SPECIAL REPAIR/REPLACEMENT OF INTERNAL ELECTRICAL FIXTURES AND WIRING OF BASIC WORKSHOP AND MTR & S SECTION AT MTTI |
| 11 | Taking down copper/aluminium point wiring for (light, fan, socket or power) complete including unserviceable fittings such as switches, ceiling rose, holders, sockets etc. and making good the disturbed surfaces on wall/floor etc complete all as specified and directed. |
| 12 | M & L for point wiring with 1.5 Sqmm (nominal area) PVC insulated,FRLSH unsheathed, multistrand, 1100 volts grade copper conductor cable single core, drawn through with and including non metallic PVC conduit 25mm dia and its accessories Concealed in wall and fixing on ceiling/trusses necessary fixing arrangmentswith suitable clamps, screws etc including one run of 1.5 Sqmm PVC insulated copper conductor cable green in colour for continuous earthing, 1.6 mm thick MS terminal box finished to wall with 3 mm thick laminated hylam sheet top cover all as specified for :-(a)One light point controlled by one switch. |
| 13 | (b)One Ceiling/Exhaust fan point controlled by one switch. |
| 14 | (c)One wall mountedfan/ Air Circulation Fans point controlled by one switch. |
| 15 | (d)One 3 pin 5 amps socket point on same board |
| 16 | (e)One 3 pin 5 amps socket point on independent board |
| 17 | M & L for pointing wiring with 4 Sqmm (nominal area) PVC insulated,FRLSH unsheathed, multistrand, 1100 volts grade copper conductor cable single core, drawn through with and including non metallic PVC conduit 25mm dia and its accessories Concealed in wall and fixing on ceiling/trusses with necessary fixing arrangements suitable clamps , screws etc including one run of 4 Sqmm PVC insulated copper conductor cable green in colour for continuous earthing, 1.6 mm thick MS terminal box finished to wall with 3 mm thick laminated hylam sheet top cover all as specified forOne 5 pin 5/15 amps socket point on independent board complete all as specified. |
| 18 | S&F switch piano, flush type single pole, one way 5 Amps |
| 19 | S&Fswitch socket 3 pin 5 amps , multi pin , flush type |
| 20 | S&F switch socket outlet 2 in 1, 3 pin, 5 and 15 Amps flush type(Through ponit wiring) |
| 21 | S&F switch socket outlet 2 in 1, 3 pin, 5 and 15 Amps flush type complete with MS terminal box and laminated hylam sheet with accessories complete all as specified. (Through Submain wiring) |
| 22 | S&F electronic fan regulator, flush type phenolic laminated sheet etc; as required. |
| 23 | M&L ceiling rose, 3 phase/PVC/polycarbonate, isolated body complete all as specified. |
| 24 | Supply and Fixing of Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps complete all as specified. |
| 25 | Taking down carefully Power / Sub main wirings with PVC aluminum conductor cables in PVC/STEEL conduits / TW battens up to 3 runs of 4/6/10 Sq.mm removing materials from site, taken ascredit ,making good thedisturbed surfaces all as specifiedand as directed. |
| 26 | M&L for wiring for circuit / power/sub main wire with two runs of single core 4 Sqmm size and one run of 4 Sqmm (green colour as earth continuity conductor) PVC insulated, unsheathed, multi stranded copper conductor FRLSH cable drawn through including suitable dia PVC conduit concealed in wall and fixing arrangement on ceiling/trusses suitable clamps,screws etc., for fixing arrangments as per site requirement complete with accessories all as specified. |
| 27 | M&L for wiring for circuit / power/sub main wire with two runs of single core 6 Sqmm size and one run of 6 Sqmm (green colour as earth continuity conductor) PVC insulated, unsheathed, multi stranded copper conductor FRLSH cable drawn through including suitable dia PVC conduit concealed in wall and fixing arrangement on ceiling/trusses with suitable clamps,screws etc.,for fixing arrangments as per site requirement complete with accessories all as specified. |
| 28 | M&L for wiring for circuit / power/sub main wire with Four runs of single core 04 Sqmm size and one run of 04 Sqmm (green colour as earth continuity conductor) PVC insulated, unsheathed, multi stranded copper conductor FRLSH cable drawn through including suitable dia PVC conduit concealed in wall and fixing arrangement on ceiling/trusses with suitable clamps,screws etc., for fixing arrangments as per site requirement complete with accessories all as specified. |
| 29 | M&L for wiring for circuit / power/sub main wire with two runs of single core 10 Sqmm size and one run of 10 Sqmm (green colour as earth continuity conductor) PVC insulated, unsheathed, multi stranded copper conductor FRLSH cable drawn through including suitable dia PVC conduit concealed in wall and fixing arrangement on ceiling/trusses with suitable clamps,screws etc.,for fixing arrangments as per site requirement complete with accessories all as specified. |
| 30 | S&F Load line vertical distribution Board, TPN 4 way double door, fixed on wall semi flush, loadline DB are fitted with Bus bars, neutral links, blanking plates, including incommer MCCB125/160 Amps,TP and suitable outgoingMCB 40 /63Amps,SP/DP/TPN with all accessories suitable for DB including taking down old unserviceable DB all as specified and as directed. Note : Incoming MCCB and Out going MCBs measured seperately relevent items. |
| 31 | S&F MCB DB SPN 12 way, doubledoor, powder coated, 240 volts, AC, 50Hz, IP 43 protected, with provision for MCBdouble pole as incomer andSP MCBs as outgoing with tinned copper bus bar, neutral link, earth linkand connecting up complete all as specified and as directed. Note : Incomingand Outgoing MCB measured separately relevent items. |
| 32 | S&F MCB DB SPN 4 way, doubledoor, powder coated, 240 volts, AC, 50Hz, IP 43 protected, with provision for MCBdouble pole as incomer andSP MCBs as outgoing with tinned copper bus bar, neutral link, earth linkand connecting up complete all as specified and as directed. Note : Incomingand Outgoing MCB measured separately relevent items. |
| 33 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified. |
| 34 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of SPN and current carrying capacity 40-63 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified. |
| 35 | Supply and fixing 415V, 16 KA \"B\" curve miniature circuit breaker (MCB) of TPN and current carrying capacity 40 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified. |
| 36 | S&F MCCBs100 Amps 415V,16KA, 4 Pole complete all as specified . |
| 37 | S&F Surface and wall mounted LED tube light fitting, 20 W, batten type, extruded channel thermally conductive material,integrated electronic driver complete with all accessories , suitable for operation on AC, single phase 220 / 230 Volts , 50 Hz supply, and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting complete all as specified and as directed. |
| 38 | S&FLED panel light 30/32 watt (2 x2 ),white powder coated CRCA full glow recess mounting LED Backlit Panel, integrated electronic driver complete including connection from ceiling rose to light fitting with twin core cable 23/0.0076 Sqmm complete all as directed. |
| 39 | S&FLED energy saving High bay light fitting for capacity 150 watt, IP66 with high efficancy integrated electronic driver complete, additional safety chain including connectionto light fitting with suitable size of connection cable complete with suitbale fixing arrangements of trusses controlled by one suitable MCB complete all as directed. |
| 40 | Supply and fix Flood light luminaries LED energy saving 100 Watt LED exlusive innovative designed, long life versatile pressure die-cast aluminium IP 65 flood light luminaire high power LED in single peace deep drawn housing complete with all accessories and glass cover with suitable bracket or with grouted spring pressure fasterner/steel rawal plugs as directed including connection from juction box to lilght fittings with 2.5 Sqmm 2 single core PVC insulated and unsheathed, multi stranded FRLS copper conductor cable drawn in flexible conduit complete controlled by MCB complete all as specified. |
| 41 | S&F LED building security light fitting 45W made up of pressure die cast housing with toughened glass and individual high power LEDscomplete pre-wired and connecting up with suitable twin core flexble copper wireincluding provision of necessary GI tubing medium grade 25 mm bore of pipe 1.5 bent to shape with necessary clamps made out of mild steel, nuts and bolts etc. fixing the fitting to Bldg etc complete all as specified and as directed. |
| 42 | Taking down unserviceable ceiling fans,sealing cable end, dismantling blades and removing fan and deposit blades to store complete all as specified and as directed. |
| 43 | Supply & fix ceiling fans ceiling BLDC type complete with electronic type regulator and accessories 230 V,1400 mm sweep. BEE 5 star rated with provn of necesary hanging hook on ceiling complete all as specified and directed. |
| 44 | Taking down unserviceable Exhaust fan /Air circulator fan/Wall mounted fans, sealing cable end, dismantling blades and removing fan and deposit blades to store complete all as specified and as directed. |
| 45 | S&F of Exhaustfan, heavy duty, 300 mm sweep, 1425 RPM, with louvers, metal body conforming to IS, AC singlephase, 240 Volts, 50 Hzand connecting including provision of two way PVC connectors, 1.50 sqmm flexible three core multistranded copperconductorcablefromceilingroseor connectorto fan including earthing and fixing arrangements like making hole in wall and finishing to shape to match adjoining surface complete all as specified and directed. |
| 46 | Supply & fix wall mounted fans 450 mm sweep PVC blades 230 volts single phase oscillatingsuitable for wall mounting with all fixing arangemnts on wall/trusses complete all as specifed and directed. |
| 47 | Supply & fix Air circulator fans AC single phase 230/ 240 V of size 600 mm sweep with all necessary fixing arrangemtns on wall/ trussescomplete all as specified and directed. |
| 48 | Material and labour for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawing in conduit or any other situation for loop earthing etc as reqd 20 x 3 mm diacopper strip complete all as specified and directed. |
| 49 | M&L for earthing complete with copper earth plate electrode of size60cm x 60cm x 3.15mm thick burried directly in ground vertically at a depth not less than 2.25 metredeep below normal ground level with top edge of the plate not lessthan1.5 metre below normal groundlevel surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using copper strip 20 x 3mm dia by means of bolts, nuts, check nuts and washers made of copper or brass and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (2009)all as specified and directed by Engr-in-Charge. |
| 50 | M&L for Chemical earthing with copper earth plate 90x60cmx5mm & copper earth strip 32x6mm complete all as specified and directed. |
| 51 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed. |
| 52 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out any type of soil for laying cables / pipes / erection of poles etc all as specified and as directed. |
| 53 | Removing excavated material (soil) not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and as directed. |
| 54 | Returning filling in soil including spreading leveling watering well ramming in layers not exceeding 25 cm each all as specified and as directed. |
| 55 | Laying in trenches fine sieved excavated dry soilincluding spreading/ leveling, cushioning for underground cables all as specified and as directed. |
| 56 | Supply and laying of common burnt clay building bricks, sub class B sizefor cable protection all as specified and as directed. |
| 57 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 3.5 core complete all as specified and directed. |
| 58 | Supply.install,testing and commissioning of cubical indoor LT Electrical distribution feeder pillar box CPRI approved platform mounted factory made totally enclosed dust and vermin proof (protection class IP-65) double shutter front opening with locking arrangement complete made of 1500mm x 1100mm x 500mm thick frame work and 2mm thick CRCA sheet duly painted over outside and inside with detachable sheets with holes for cable glands,separate bus bars,cable entry and exit mounted on PCC pillers with bolts grounted complete .The panel comprising of Aluminium bus bars of 500A capacity,415 volt 50Hz,3 phase 4 wire system with insulators and internal wiring complete with following requirements :-Incoming:-(i) MCCB,300 Amp 4 pole, FE Frame,Ics=100% of Icu, 36 KA breaking capacity with adjustable Microprocessor release -01No(ii) On load change over siwtch 300 Amps ,4 pole 415 volts ,3 phase ,50 Hz AC - 01 NoOutgoing:- (i) MCCB,100 Amp 4 pole, FE Frame,Ics=100% of Icu, 25 KA breaking capacity with adjustable Microprocessor release -02Nos(ii) MCCB,63 Amp 4 pole, FE Frame,Ics=100% of Icu, 25 KA breaking capacity with adjustable Microprocessor release -04 Nos(iii) Indicating Lamp LED Type - 01 set(iv) Multifunction meter digital type -01 No |
| 59 | M&L for earthing complete with copper earth plate electrode of size60cm x 60cm x 6 mm thick burried directly in ground vertically at a depth not less than 2.25 metredeep below normal ground level with top edge of the plate not lessthan1.5 metre below normal groundlevel surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using copper strip 32x6 mm dia by means of bolts, nuts, check nuts and washers made of copper or brass and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (2009)all as specified and directed by Engr-in-Charge. |