| 1 | Soil Resistivity survey _Rajasthan Loc_ | Data to be recorded up to 100 Meter _linear to and perpendicular to pipe__6 nos per crossing _1.5 Km span and 10 Km per crossing_, pre mitigation survey_ |
| 2 | Soil Resistivity survey _Gujarat Loc_ | Data to be recorded up to 100 Meter _linear to and perpendicular to pipe__6 nos per crossing _1.5 Km span and 10 Km per crossing_, pre mitigation survey_ |
| 3 | Supplyand Instln of TLP Box _Raj Location_ | BOX SIZE- 450 X 450 X 400 MM- PIPE SIZE- 100 MM- THICKNESS- 4.5 MM- FOUNDATION PLATE- 400 X 400 MM- THICKNESS, FOUNDATION PLATE- 6 MM- TOTAL HEIGHT- 1800 MM- |
| 4 | Supplyand Instln of TLP Box _Guj Location_ | BOX SIZE- 450 X 450 X 400 MM- PIPE SIZE- 100 MM- THICKNESS- 4.5 MM- FOUNDATION PLATE- 400 X 400 MM- THICKNESS, FOUNDATION PLATE- 6 MM- TOTAL HEIGHT- 1800 MM- |
| 5 | 1 core 25 sqmm Cu Armoured cable_Raj Lo_ | 1c x 25 sq. MM armoured cable |
| 6 | 1 core 25 sqmm Cu Armoured cable_Guj Lo_ | 1c x 25 sq. MM armoured cable |
| 7 | 1 core 10 sqmm Cu Armoured cable_Raj Lo_ | 1c x 10 sq. MM armoured cable |
| 8 | 1 core 10 sqmm Cu Armoured cable_Guj Lo_ | 1c x 10 sq. MM armoured cable |
| 9 | Supply,Instln,comm test coupon_Raj Loc_ | Coupon material shall be same as of pipe material |
| 10 | Supply,Instln,comm test coupon_Guj Loc_ | Coupon material shall be same as of pipe material |
| 11 | Pin brazing _Raj location_ | Connection of Copper Wire with Pipe |
| 12 | Pin brazing _Guj location_ | Connection of Copper Wire with Pipe |
| 13 | Data logging 24 hrs_Raj location_ | Data Logging by 24 hours recording at suseptible TLPs _pre and post mitigation survey_ |
| 14 | Data logging 24 hrs_Guj location_ | Data Logging by 24 hours recording at suseptible TLPs _pre and post mitigation survey_ |
| 15 | Supply,Instn,comm of SSD as per Att. 3 _Raj location_ | I- 40A, Impulse I- 5000A, Blocking DC- Positive1.75V, IP55, Basis AC pick up survey Refer scope of job- Att-I and II_all activities shall be witnessed and certified by HPCL representative_ |
| 16 | Supply,Instn,comm of SSD as per Att. 3_Guj location_ | I- 40A, Impulse I- 5000A, Blocking DC- Positive1.75V, IP55, Basis AC pick up survey Refer scope of job- Att-I and II_all activities shall be witnessed and certified by HPCL representative_ |
| 17 | Supply and Installation of Zinc ribbon- Raj location _Length 250 feet | as per tender documents |
| 18 | Supply and Installation of Zinc ribbon-Gujarat Location _Length 250 feet_ as per tender documents | as per tender documents |
| 19 | Supply and Installation of zinc anode- Rajasthan Location _10 m _for each anode_ 1core 25 sqmm Cu armoured cable and Excavation is also in scope of vendor, vendor shall quote suitably_ | as per tender documents |
| 20 | Supply and Installation of zinc anode- Gujarat Location _10 m _for each anode_ 1core 25 sqmm Cu armoured cable and Excavation is also in scope of vendor, vendor shall quote suitably_ | as per tender documents |
| 21 | Supply and Installation of Magnesium anode- Rajasthan Loc _10 m _for each anode_ 1core 25 sqmm Cu armoured cable and Excavation is also in scope of vendor, vendor shall quote suitably_ | as per tender documents |
| 22 | Supply and Installation of Magnesium anode-Gujarat Location _10 m _for each anode_ 1core 25 sqmm Cu armoured cable and Excavation is also in scope of vendor, vendor shall quote suitably_ | as per tender documents |