| 1 | Taking down carefully old defective LT UG cables of any size including cable protection pre cast concrete cover / bricks from the trenches and keeping aside for reuse/disposal complete all as specified and directed. |
| 2 | Supply, laying, jointing and testing of LT undergroundXLPE insulated screened PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade of cross-sectional area 16 Sqmm 4core, conforming to IS-7098 (Part-I) of 1988 laid in trenches/wall/floors/ducts etc fixed with saddle and clamps or passing through pipes complete with cable and connection with proper thimbles, nuts, bolts and washers all as specified and directed. Note: Excavation & earth work, sand cushioning and PCC cover for cable protection shall be measured & paid for separately. |
| 3 | Description all as per item No 2 here in before but cross sectional area 10 Sqmm 4 core |
| 4 | Description all as per item No 2 here in before but cross sectional area 25 Sqmm 4 core |
| 5 | Description all as per item No 2 here in before but cross sectional area 6 Sqmm 2 core |
| 6 | Supply, laying, jointing and testing of LT undergroundXLPE insulated screened PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade of cross-sectional area 10 Sqmm 2core, conforming to IS-7098 (Part-I) of 1988 laid in trenches/wall/floors/ducts etc fixed with saddle and clamps or passing through pipes complete with cable and connection with proper thimbles, nuts, bolts and washers all as specified and directed. Note: Excavation & earth work, sand cushioning and PCC cover for cable protection shall be measured & paid for separately. |
| 7 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth for laying/taking out cable and getting outin soft/loose soil all as specified and directed. |
| 8 | Returning, filling in soil including spreading levelling, watering and well ramming in layers not exceeding 25cmthick all as specified anddirected. |
| 9 | Removing excavated material/soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed. |
| 10 | Supply and spread dry sand in trenches for cable cushioning all as specified in clause 19.75 of SSR Part-I all as specified and directed. Note:- Punned thickness of sand only shall be measured & paid. |
| 11 | Supply and laying un-reinforced pre-cast concrete cable cover, class LV, type 1, flat, size 250mm x 150mm x 40mmcomplete all as specified and directed. |
| 12 | Supply and laying galvanised iron tubing, light grade of size 40 mm dia with all fittings as in cable protection, laid in trenches, including taking down existing unserviceable GI pipes & its connections complete all as specified and directed. |
| 13 | Demolition of un-reinforced cement Concrete in road and paving\"s not exc 15 cm thickness (below or above ground level) |
| 14 | M&L ofPCC 1:2:4 type B2 using 40mm graded crushed stone aggregate as in road filling as specified and directed. |
| 15 | M&L for LT Cable route marker of Cast Iron type Circle shape of 100 dia as specified and directed. |
| 16 | Supply & fixing in repair new generation, post top lantern fitting 30 W LED, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire complete all as specified and directed.Make: Havells Cat part No. RUBYNXTPT15WLED757PSYMTOPC/ equivalent in Wipro/CG |
| 17 | S&F in repairs for contactor MNX-40, 3 Pole, 415 volt coil voltage 230 volt complete as in street light timer assembly including removing old unserviceable contactor all as specified and directed |
| 18 | S&F astronomical digital timer switch 16 amp, LCD display, astronomical programmable by entering longitude and latitude, also adjustable up to plus/minus 2hrs turning on later and off earlier than sunset and sunrise, with battery backup,suitable for connection with three phase supply including taking down old unserviceable timer switch of any type complete all as specified and as directed. |
| 19 | Supply and fix in repairs MCB Triple Pole & Neutral, 40 to 100 Amp, 415 Volts, 10 KA capacity \"C\" curve series complete all as specified & directed. |
| 20 | S&F in repairs MCB, single pole 6 to 32 Amp, 240 Volts, 10 KA Capacity \"C\" curves series complete all as specified & directed. |
| 21 | S&F in repairs FRP cable looping boxes of 300 mm x 200 mm x 105 mm size containing TPN aluminium bus bar and MCB SP 6 Amp- 01 No, 10 KA breaking capacity, C curve series, factory made with PVC sheet including heavy duty connector for connection of 4 core cable & fixed to pole with suitable size flat iron clamp, nuts & bolts complete all as specified and directed. |
| 22 | M&L for closing the existing street light cable box in coping with suitable weather proof Hylam/Bakelite sheet including dismantling of old accessories, terminating incoming and outgoing cables and connecting the circuit to a new FRP looping box fitted with TPN aluminium bus bar, including all materials, excavation upto 1cum, labour, hardware and suitable cable glands, ferrules, lugs (Al/Cu as required), and making good all disturbed surfaces complete all as specified and as directed. Note: FRP Cable looping box, measured and paid separately under relevant item in the schedule. |
| 23 | Supply & fix in repair PVC insulated and sheathed copper multistranded cablethree core 2.5 sqmm, heavy dutythrough or on pole connecting to cable looping box of street light fitting all as specified and directed. |
| 24 | Supply & fix in repair PVC insulated and sheathed copper multistranded cablethree core 4 sqmm, heavy dutythrough or on pole connecting to cable looping box of street light fitting all as specified and directed. |
| 25 | Supply & fix in repair two way heavy duty PVC connector suitable for 10 to 25 Sqmm cable connection in looping box complete all as specified and directed. |
| 26 | S&F in repair aluminium thimble/lugs of size 10 to 25 Sqmm for cable connection in the junction box as per site requirement complete all as specified and directed. |
| 27 | M&L for providing and making cable terminations at the existing street light cable light fitting, including stripping insulation, crimping and fixing suitable size aluminium/ copper lugs to the cable cores, connecting the lugged ends to terminal blocks at both ends, ensuring tight and carbonisation-free contact, insulating exposed portions, arranging the wiring neatly and testing the lighting circuit complete all as specified and directed. Note: cable will be measured and paid separately under relevant item in the schedule. |
| 28 | M&L for preparation of old surface by scraping down old pealed off paint using sand paper, removing dirt/dust from steel tubular pole and painting to steel tubular pole (9 mtr long) including street light bracket with applying two coats of synthetic aluminium paint over one coat of primer, including marking the pole number etc complete all as specified and directed. Note: The job should also include whitewashing of the PCC foundation of the poles. |
| 29 | S&F in replacement ,street light mounting bracket made out of 50 mm dia galvanized steel tubing medium grade 1.5 m long including bending if required as direct ,02 nos clamps made out of MS flat iron 25 x 3 mm of suitable size fixed with bolts, nuts and washer including drilling holes and grouting with the same for fixing bolts and applying two coat of synthetic enamelled grey paint after removing all dust & rust complete all as specified and directed |
| 30 | S&F in repairs 90 watt LED roadway luminaire, made up of pressure die cast housing with toughened glass and individual LEDs with secondary optics and IP66 protection with high power LEDs as light source and HF electronic driver of 90W capacity including making necessary connection & taking down old unsv fittingcomplete all as specified and directed.make : Havells Cat part no. ENDURASUNBEAMGENXSL90WLED757SASYBOPC / Equivalent in Wipro/CG |
| 31 | S&F in repairs 120 watt LED street/roadway luminaire made up of pressure die cast housing with toughened glass and individual LEDs with secondary optics and IP66 protection with high power LEDs as light source and HF electronic driver of 120W capacity including making necessary connection complete all as specified and directed. make : Havells Cat part no. ENDURASUNBEAMGENXSL120WLED757SASYBOPC / Equivalent in Wipro/CG |
| 32 | Supply & fixing in repair LED driver suitable for 90 watt LED street light fittings of existing make complete all as specified and directed. |
| 33 | Supply & fixing in repair LED driver suitable for 120 watt LED street light fittings of existing make complete all as specified and directed. |
| 34 | S&F in repairs LED flood light luminaire 150 watt with secondary optics made in pressure die cast housing and heat sink in aluminium extruded with IP66 protection & taking down old unsv fitting complete all as directed. Make: Havells cat part No. JETAADORNNXTFLS150WLED757SSYMTOTGV2/ equivalent in Wipro/CG |
| 35 | S&F in repairs LED flood light luminaire 200 watt with secondary optics made in pressure die cast housing and heat sink in aluminium extruded with IP66 protection & taking down old unsv fitting complete all as directed.Make : Havells cat part No. JETAADORNNXTFLS200WLED757SSYMTOTGV2/ equivalent in Wipro/CG |
| 36 | Supply only LED driver suitable for flood light 150 watt to 250 watt , out door type of existing make and model as approved. |
| 37 | Supply & Fixing in repairs LED lamps of capacity 15 W used for garden light all as specified and directed. |
| 38 | Supply and fixing in repairs surge protector, 10 KV, rated frequency 48 HZ - 62 HZ,, 230 V suitable for 90W LED street light fitting complete all as specified and as directed. |
| 39 | Supply and fixing in repairs surge protector, 10 KV, rated frequency 48 HZ - 62 HZ,, 230 V suitable for 120W LED street light fitting complete all as specified and as directed. |
| 40 | Supply and fixing in repairs surge protector, 10 KV, rated frequency 48 HZ - 62 HZ,, 230 V suitable for 150W LED flood light fitting complete all as specified and as directed. |
| 41 | Supply and fixing in repairs surge protector, 10 KV, rated frequency 48 HZ - 62 HZ,, 230 V suitable for 200W LED flood light fitting complete all as specified and as directed. |
| 42 | S&F in repairs CS mounted high intensity LED search light, long range, manually swivel in all direction, 250 W, beam range 700 meters,Single, LED Efficiency > 140 lm/w, PF > 0.95, CCT 5500K - 6500K, Optical grade PMMA/PC lens/reflector efficiency > 95%, multiple circuit to avoid complete run-down, anti UV, narrow beam 5 degree, die cast LM6 body with air fins, powder coated, constant current,average lux at 5 meter - 15000 with circle of approx. 600 mm,working temp : -20 to +60 degree C, input Volt 150-270 V, 50 Hz, P.F. > 0.95, IP-65, confirming to LM79/LM80 as per IS : 10322/ IS: 13383.The stand of this search light should be suitable for fixing on railing/platform of watch tower or other plain surface.It is made by steel and suitable for manual rotation of the light on the horizontally (more than 360 degree) and vertically (more than 45 degree) with provision of both locking arrangement at desired position. |
| 43 | Taking down old defective/unserviceable gate light/bulk head/garden light/street light of any size or typecomplete all as specified and directed. |
| 44 | S & F in repairs aviation obstruction light with neon lamp yellow coloured die cast aluminium alloy housing, with built in 75 VA step up transformer complete all as specified and directed. |
| 45 | M & L for testing of resistance of earth pits of poles/panels or any other indicated place etc after testing report will be furnished to Engr-in Charge in standard format approved by Engr-in Charge. |
| 46 | M&L in replacement of Earthing complete withgalvanisedsteelearthelectrode 60Cm x 60Cm x 6 mm thick directly buried in ground (earth pit not less than 2.25 M deep below the normal ground levelconnected togalvanised earth lead dia 4 mm dia by means ofbolts, nuts, check nuts and washersof galvanisediron steel includingnecessary excavationearth workPCC chamberCI chamber cover protectionpipe wateringpipe etc. (Complete all as shown in electrical plate No 3 and connectedto earthing testpointcompleteincluding excavation earthwork,PCC chamber, chamber cover ,funnel watering and protection pipe etc allspecified anddirected and testing on completion. |
| 47 | M&L for Earthing continuity galvanised earth lead dia 4 mm dia or main earthing lead fixed to wall with clamps or recess or crosses or buried in ground or drawn in conduits/pipe or fixed to poles or any other indicated situationfor loop earthing etc as required all as specified and directed. |
| 48 | S&F in repair synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and as directed. |
| 49 | S&F in repair Cable termination, heat shrinkable type Cable jointing kit for 1.1 KV (Earthed) grade cable for straight through joint kit, outdoor type with jointing material and accessories suitable foraluminium conductor cable of size 3.5 core x 10 to 25 sq.mm complete all as specified and directed. |
| 50 | S&F in repair Cable termination, heat shrinkable type Cable jointing kit for 1.1 KV (Earthed) grade cable for straight through joint kit, outdoor type with jointing material and accessories suitable foraluminium conductor cable of size 3.5 core x 25 to 50 sq.mm, fixed in repair, including testing after jointing, complete all as specified. |
| 51 | M&L for cutting and clearing of tree branches obstructing the illumination of street-light, including trimming of overgrown branches around the pole and light fitting, removing foliage blocking the beam spread, safe lowering of cut branches, clearing and stacking/ disposal of debris as directed, ensuring no damage to existing cables, pole, bracket or street light fitting, including all labour, tools and safety precautions required for proper visibility restoration complete all as specified and as directed. |
| 52 | M&L for Surface dressing not exc 15 cm deep and 2.5 X 2.5 meter surrounding area of street light pole / stay / stay pole/HT poleincluding cutting and cleaning away grass, bushes, small plant, vegetable shrubs, bushes of under roots all as specified and directed. |
| 53 | M&L for DWC pipe of 75 mm dia for electrical ducting laid in trenches and jointed including necessary jointing material, tees/ union/ socket etc completeall as per manufacturer\"s instructions including taking out old pipe complete all as specified and directed. |
| 54 | S&F Bollard light, New generation, energy saving, environmental friendly, long life of size Height 900 mm, Diameter 120 mm, Base plate 160 mm aesthetically designed aluminium landscape IP 65 luminaire for diffused lighting with 8W, 3000K high power LED as light source, Providing and laying PCC 1:2:4 (M15) foundation of size 300×300×450 mm with sand bedding, conduit provision, foundation bolts, curing and finishing for mounting bollard light including all materials and labour, complete all as specified and directed.Make : Havells cat part No.BAMBOOBL8WLED857SSYMTOPCM / Equivalent in Wipro/CG |
| 55 | SITC of LED post top luminaire 40Watt , IP 66, IK 07, 3000K , mounted on and including 6 feet height MS bollard pole ( as per IS standards with 76mm top, including excavation of pit, providing PCC foundation block( 300x300x450mm, M15), fixing of anchor bolts, providing conduit for cable entry and connecting with cable, earthing and all accessories complete all as specified and as directed by Engr in charge.Make : Havells Cat part No. SIMBOLPT40WLED757SYMPCGRYCMP/ equivalent in Wipro/CG |
| 56 | M&L for providing and fixing retro reflective high intensity prismatic (HIP) tape on steel tubular pole in specified colour, 75-100mm width, including surface cleaning, rust removal, wiping with solvent, cutting tape to required length, wrapping around pole with firm adhesion, and ensuring uniform alignment and finishing, labour, tools and incidental charges complete all as specified and as directed. |
| 57 | M&L for Providing and fixing tri-colour LED light strip of 18 metre (saffron, white and green) around the pole, outdoor-grade IP65 LED strip with uniform illumination, complete with clamps, driver, wiring and commissioning all as specified and as directed. |
| 58 | M&L for Carrying out routine and preventive maintenance of the high mast, including checking and tightening of all electrical/mechanical connections, cleaning of luminaires, inspection and lubrication of winch, wire rope and pulleys, lowering and raising system operation check, replacement of defective lamps/drivers/ballasts if required (materials extra), cleaning of mast surface, testing of aviation light, earthing verification and ensuring safe operation of the entire high mast system, complete as directed. |
| 59 | Supply and laying of multi core flexible cable from mast base to lantern carriage including cable holders/clamps, termination with lugs, and testing during raising/lowering complete all as specified and as directed. |