| Sl. No. | Item Description |
| 1 | Schedule \"A\" Part – I to Schedule \"A\" Part – XIX:NOTE: Schedule \"A\" Part – I to Part – XIX are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only |
| 2 | Lumpsum price worked out by the contractor for \"BUILDINGS & STRUCTURES\",as listed in Schedule \"A\" Part – I |
| 3 | Lumpsum price worked out by the contractor for \"SITE CLEARANCE / AREA DEVELOPMENT/EARTH WORK/EXCAVATION\",as listed in Schedule \"A\" Part – II |
| 4 | Lumpsum price worked out by the contractor for \"INTERNAL ELECTRIFICATION\", as listed in Schedule \"A\" Part – III |
| 5 | Lumpsum price worked out by the contractor for \"INTERNAL WATER SUPPLY\", as listed in Schedule \"A\" Part – IV |
| 6 | Lumpsum price worked out by the contractor for \"SEWAGE DISPOSAL\",as listed in Schedule \"A\" Part – V |
| 7 | Lumpsum price worked out by the contractor for \"EXTERNAL WATER SUPPLY\",as listed in Schedule \"A\" Part – VI |
| 8 | Lumpsum price worked out by the contractor for \"EXTERNAL ELECTRIFICATION\", as listed in Schedule \"A\" Part – VII |
| 9 | Lumpsum price worked out by the contractor for \"ROADS /PATH/HARD STANDING/ CULVERT\",as listed in Schedule \"A\" Part – VIII |
| 10 | Lumpsum price worked out by the contractor for \"AREA DRAINAGE\",as listed in Schedule \"A\" Part – IX |
| 11 | Lumpsum price worked out by the contractor for \"FIRE FIGHTING SYSTEM\",as listed in Schedule \"A\" Part – X |
| 12 | Lumpsum price worked out by the contractor for \"TV/TELEPHONE \",as listed in Schedule \"A\" Part – XI |
| 13 | Lumpsum price worked out by the contractor for \"\"HOT WATER \",as listed in Schedule \"A\" Part – XII |
| 14 | Lumpsum price worked out by the contractor for \"LIGHTENING PROTECTION\",as listed in Schedule \"A\" Part – XIII |
| 15 | Lumpsum price worked out by the contractor for \"RAIN WATER HARVESTING\",as listed in Schedule \"A\" Part – XIV |
| 16 | Lumpsum price worked out by the contractor for \"STP 75 KLD\",as listed in Schedule \"A\" Part – XV |
| 17 | Lumpsum price worked out by the contractor for \"ARBORICULTURE\",as listed in Schedule \"A\" Part – XVI |
| 18 | Lumpsum price worked out by the contractor for \"PILE FOUNDATION\",as listed in Schedule \"A\" Part – XVII |
| 19 | Schedule \"A\" Part - XVIII: [Miscellaneous Items] [ Internal Electrification, Internal water supply, External Water Supply, External Electrification, Fire fighting & Fire alarm, Sewage Disposal,Lifts, DG Set,Earthing, STP 75 KLD, Water treatment Plant, Arboriculture, Pile foundation and Outsourcing of M&O/ Comprehensive Maintenance of Lifts] |
| 20 | Internal Electrification |
| 21 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne lightpoint controlled by one switch :-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 22 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne bell point controlled by one bell push :-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 23 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne fan (ceiling fan/Ex.fan) point controlled by one switch:-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 24 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne 3 Pin socket outlet 6 amps socket on independent board:-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete |
| 25 | M&L forPonit wiring with 1.5 sqmmPVC insulated and unsheathed copper conductorcable multistranded 1100 volts grade,FRLS, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pre fabricated pressed steel terminal box of suitable size made out of 2 mm thick sheets,for mounting modular brackets, including modular brackets and plates as required at site for fixing modular type switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity green in colour, connected to earth duly complete all as specified and directed forOne 3 Pin socket outlet 6 amps socket on same board with other switches :-Note: (a) The PVC conduit shall be concealed and switch boards shall be flush to wall. (b) On columns/ pillars the box type switchboards surface mounted with necessary PVC conduit upto ceiling/nearest junction tapping shall be surface type conduitand quoted rate deemed to be inclusive for the same.(c) The quoted rate inclsuive necessary modules any type as per requirement incl all accessories complete. |
| 26 | All as per item No. 16 above but One3 pin socket outlet 15 amps socket on independent board with 4 sqmm FRLS PVC wire for phase and neutral and one run of 4 sqmm copper cable green in colourfor earth continuty conductor complete all as specefied and directed. |
| 27 | All as per item No. 16 abovebut one light point controlled by two Nos of two way switch complete all as specefied and directed. |
| 28 | Supply and fixing LED adore lamp for AC 240Volt supply, B22 type,CDS five star, 10 watts of five star rated complete all as specified and as directed. |
| 29 | Supply and fixing ceiling fan, AC single phase 230 V of size 1200 mm sweep, copper wound with complete set and fixtures such as canopy, down rod etc.5 Star rating, metallic body complete with and inclussive of making necessary electric connection from ceiling rose to fan through twin core flexible wireall as specefied and directed. |
| 30 | S&F Exhaust fan 350 mm sweep or nearest size, plastic body(Heavy duty), complete with louvers suitable for operation on 230 V AC, 50 HzAC supply fixed on wall making opening,fixing and making good the distrubered surfaces etccomplete with and inclussive of making necessary electric connection from ceiling rose to fan through twin core flexible wire all as spcified and as directed. |
| 31 | S&F Exhaust fan 450 mm sweep , (Heavy duty),complete with louvers suitable for operation on 240 V AC, 50 HzAC supply fixed on wall including making of neccessary opening ,fixing and making good the disturbed surfaces etccomplete with and inclussive of making necessary electric connection from ceiling rose to fan through twin core flexible wire all as specified and as directed. |
| 32 | Supply and fixingEnergy efficient LED tube light fitting with tube 5 watts or nearest size ,240V, 50hz surface mounted, decorative ultra slim square profile LED lighting fixture with extruded polycarbonate environmental friendly, energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed |
| 33 | Supply and fixingEnergy efficient LED tube light fitting with tube 10 wattsor nearest size ,240V, 50hz surface mounted, decorative ultra slim square profile LED lighting fixture with extruded polycarbonate environmental friendly, energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed |
| 34 | Supply and fixingEnergy efficient LED tube light fitting with tube 2 x 20 wattsor nearest size ,240V, 50hz surface mounted, decorative ultra slim square profile LED lighting fixture with extruded polycarbonate environmental friendly, energy efficient ready to use pack of complete with mounting bracket etc including connecting up with 1.0 sq mm 3 core flexible copper conductor cable complete all as specified and directed |
| 35 | Supply and fixing LED Security light fitting with tube 30W New generation Energy saving &environmental frindly long lifemade up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having top opening seperate driver compartment with IP66 protectionpre wired with 1.0 Sq mm copper conductor cable upto connector including 1.5 m long GI Tubing light grade of 32mmdia bend to shape for fixing on wall/pole withsuitable MS brackets nuts and bolts etccompelte all as specified and as directred. |
| 36 | Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclussive of suitable size PVC rigid counduit concealed to wall, and PVC wire of size 2x4sqmm for phase and neutral duly colour coded and 1x4 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note :(i) Two run of 4.0 Sqmm + one run of 4.0 Sqmm as a earth wire cable + one run of PVC conduitshall be measured as an one Unit. |
| 37 | Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclussive of suitable size PVC rigid counduit concealed to wall, and PVC wire of size 2x6sqmm for phase and neutral duly colour coded and 1x6 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note :(i) Two run of 6.0 Sqmm + one run of 6.0 Sqmm as a earth wire cable + one run of PVC conduitshall be measured as an one Unit. |
| 38 | Material and labour for submain wiring complete with earth wire of PVC insulated multistranded copper conductor FRLS cable, ISI marked with and inclussive of suitable size PVC rigid counduit concealed to wall, and PVC wire of size 4x10sqmm for phase and neutral duly colour coded and 1x10 sqmm for earth continuity conductor green in colour complete all as specified and as directed.Note :(i) Four run of 10.0 Sqmm + one run of 10.0 Sqmm as a earth wire cable + one run of PVC conduitshall be measured as an one Unit. |
| 39 | Supply and fixing concealed in wall VTPN DB double door type, 6 way 415V, 50Hz , IP 43 protection, including provision for fixingMCB TPN as incommer andoutgoing circuits MCB SP/TP complete,fill empty way with blanking plates complete all as specefied and directed. |
| 40 | S&F MCCB 4 pole 415V, 50Hz, 10KA of capacity 100 Amp. |
| 41 | S&F MCB TPN 63 Amps 50Hz, 10KA ,415 Volts, C curve |
| 42 | S&F MCB SPN, 6to 32Amps 240 Volts , 10KA, C curve |
| 43 | S&F MCB SP, 6to 32Amps 240 Volts , 10KA, C curve |
| 44 | M & L for earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 32 x 6 mm by meams of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown electrical plate No.3, connected to earthing test point all as specified and directed and testing on completion.Note- i) Rate quoted deemed to be include excavation and earth work in any type of soil with PCC workcomplete all as specefied and directed.ii) GI earth strip upto 7.5 m shall be deemed to be included in the quoted lumpsum and beyond 7.5 m shall be measured and paid separately under relavent item. |
| 45 | Internal Water Supply |
| 46 | S&F Bib taps two way, cast copper alloy fancy typechromium plated screwed down for size of15 mm inner dia, suitable fo 16 mm outer dia CPVC pipes complete all as specified and as directed. Note: The maximum flow rate will be 03 LPM |
| 47 | S&F health faucet chromium plated , fancy type with steel flexible complete of size of15 mm dia suitable for 16 mm dia outer dia CPVC pipes complete all as specified and as directed.Note: The maximum flow rate will be 03 LPM |
| 48 | Sewage Disposal |
| 49 | M&L for DWCPE (SN8) of 200mm Inner dia , laid and jointed with solvent as manufacturer instructions laid in trenches etc complete all as specified |
| 50 | M&L for DWCPE (SN8) of 150mm Inner dia , laid and jointed with solvent as manufacturer instructions laid in trenches etc complete all as specified |
| 51 | M& L for SRFC factory mademanhole cover square/rectangular/ circlar shape for using cover to maholescomplete all as specified and as directed. |
| 52 | External Water Supply |
| 53 | Testing of water from approved Govt lab for potability by doing chemical analysis ofElectrical Conductivity,Total Dissolved Solids,pH , Total Hardness ,Total Alkalinity,Chloride , Fluoride,Sulphate,Nitrate,Iron,Manganese, Residual Chlorine, Faecal Coli form as per IS 10500 for drinking waterand submission of test reports to the entire satisfaction of Engineer-in-Charge. |
| 54 | Supply and fix submersible cable with 3 core multistranded copper conductor PVC insulated, water proof and ISI marked of size 2.5 sqmm for connecting bore well submersible pump sets complete all as specified and as directed. |
| 55 | Supply andlaying double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 40 mm forsubmersible cable protection complete all as specified and as directed. |
| 56 | Supply, install and test openwell submersible pump three Phase, 3 HP , Three Phase, Size 80mm X 80mm, No. of Stages -01 , Min. Submergence From Bottom (in mm) - 1000 mm , Head : 7-13 m, Discharge :9.5 to 16 LPS,complete all as specified and as directed |
| 57 | Supply and fixing Polypropylene Ropes as per IS 5175 ,15mm dia , Rope Construction : 3-Strand Z Twist, Lay Structure: Hawser Lay, withHigher-strength to weight ratiofor fixing of submersible pump set complete all as specified and as directed. |
| 58 | Supply, install and test Centrifugal pump three Phase,7.5 HP,Three Phase , Size 65 mm X 50 mm, Head : 50 m, Discharge :7LPS ,complete all as specified and as directed |
| 59 | Supply and fix Cast Iron Foot Valve Dia 65 mmFlanged End IS 4038 PN 0.2 with strainer |
| 60 | Supply and installation LT Electric control panel , cubical type, for indoor use floor mounted made out of CRCA outer sheet of 3 mm thick and inner sheet of 2 mm thick and angle iron legs of size 50mmx50mmx5mm having front and rear open hinged doors with front openable shutters for each MCCB with spreader with fully enclosed bus bar chamber, having insulated bas bar made but of aluminium strips of rating 250 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter , Ammeter,CTs and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete and nut,bolt,washers for connection of cable, including necessary PCC work of height 45 cm from ground level and white washing to the platform all as specified and equipped with the following items :- ( Loc : Pump House). INCOMERI.MCCB, 4pole, 125 Amps , rupturing capacity 25 KAmagnetic thermal release - 01 Nos. II. Digital Ammeter 0-500 Amps CT Operated with selector switch - 01 No III. Digital Volt Meter 0-500 Volts with selector switch - 01 No (L&T)IV. LED Indicator lamp in three colour RYB - 03 Nos (L&T)OUT GOINGI.MCCB, 3pole,40 Amps , rupturing capacity 16 KA magnetic thermal release- 07 NosII. Starter 3 phase upto 7.5 HP Centrifugal Pump - 02 NoIII. Starter 3 phase upto 3 HP Submersible Pump - 02 No |
| 61 | Material and labour for brick masonry valve chamber of size 1.2x1.2x0.9m (internal size) by providing PCC 1:2:4 type B-2 foundation 100mm thick and brick work in CM 1:4 plastering 10mm thick in CM 1:4 internal surfaces and external surfaces completely and at external surfaces upto 150mm below GL, 75mm thick PCC 1:2:4 type B-2 as in coping for valve chamber cover made up of 40x40x5mm thick angle iron frame and 3 mm thick MS sheet cover complete with locking arrangements and handle including painting all steel surfaces with two coat of synthetic enamel paint over a coat of red oxide primer and removing debris away from the premises incl necessary earth work complete all as specified and as directed. |
| 62 | External Electrification |
| 63 | Supply , Installation , testing and commmisioning of 11 KV Compact Sub Station with non extensible RMU consisting of 1 No manually operated 11 KV/630 Amps VCB in SF6 insulated stainless enclosure,HT Cable/Bus bar ,1 No transformer 500 KVA,11KV/433 CRT dry type & associated LT devices(ACB/MCCB/bus bar/Cable) included foundation as recommended by OEMcomplete all as specified and directed.The detailed specification are mentioned below.HT Section : RMU-NON-Extensible 1 way, 11KV, 1 SF6 circuit breaker along with connected accessories etc. Type: - Free Standing, Metal Clad, SF6 insulated Ringmaster with 01 no. Direct Cable Module & 01 no. 630A Fixed Manual SF6 Circuit breaker a. Self Powered Relay, Type IDMT b. Ring Switches and T OFF SF6 circuit breaker with Integrated Earthing Switches c. Live Cable Indicator for Ring Switches d. Padlocking facilitye. Shunt trip coil rating – 230V ACf. Padlocking facility Transformer Section :500 KVA, 11/0.433 KV, Copper Wound Dry Type Cast Resin Step Down Transformer having 5 Position Off Circuit Tap Links of +5% to -5% in steps of 2.5% each with all standard fittings & accessories including Digital Type WTI with Alarm& trip contacts & RTDSensors as per IS-2026 (Part-11)/IS : 11171. Total Losses @50% Load –2800W,Total Losses @100% Load –7250W |
| 64 | LT Section : LT Panel comprising of LV Side Incomer- 01 No. - 800 Amp 4 Pole 415V 50KA MDO Air Circuit Breaker microprocessor based with O/L, S/C & E/F Protection. RYB Indication Lamp,Ammeter , 800A/5A LTCT Cl:1.0,Voltmeter Enclosure: Space Heater with ON/OFF Switch and Thermostat, Single phase switch with socket, LT Cubical illumination Lamp with Door Limit switch andMCB’s for AC / DC Control , MS Steel Sheet enclosure suitable for Outdoor Installation with MS base channel and PCC foundation , Provision for receiving Incoming cables thro Bottom entry and out going through Bus bar to Trf panel, Excluding Termination Kit & Glands,Provision for receiving Incoming through bus duct by bus bar and Outgoing thro cable box bottom entry Excluding Termination Kit & Glands.Bus Bar – Aluminum , Earth Bus – Aluminum , Paint shade: Siemens Grey ( RAL 7032) |
| 65 | Supply and fixDrop out fuse, 11 kV, H.T. Pole Operated, Outdoor type, vertical mounted Expulsion type, DROP OUT FUSE each pole consist of M.S. Base, Original Porcelain type Insulators & Fiber glass fuse carrier Confirming to ISS 9385/1985 Or BSS 2692/1956(without fuse element) , Current Carrying Capacity 200 Ampscomplete all as specified and as directed |
| 66 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm Completeall as directed. |
| 67 | Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm complete all as directed. |
| 68 | Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm complete all as directed. |
| 69 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 3.5 core 120 sq mm Complete complete all as specified and directed. |
| 70 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 3.5 core 50 sq mm complete all as specified and directed. |
| 71 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 4 core 25 sq mm complete all as specified and directed. |
| 72 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 4.0 core 16 sq mm complete all as specified and directed. |
| 73 | Material and Labour charges forspreading of riddled earth obtained from trenchesfor cable cushioning on top and bottom of cable as specified.for cable protection complete all as specified and directed. (Note: Only punned thickness of riddled earth shall be measured) |
| 74 | Supply and lay double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 90 mm, complete all as specified |
| 75 | Supply and lay double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 75 mm, complete all as specified |
| 76 | Supply and lay double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 50mm, complete all as specified |
| 77 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3.5 C x 120 sqmm (37-41 mm dia) complete all as specified. |
| 78 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3.5 C x 50 sqmm (26-30 mm) dia complete all as specified. |
| 79 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3.5 C x 25 sqmm (20-23 mm) dia complete all as specified. |
| 80 | Supply , installation, testing and Commissioning offactory built floor mounted auto-manual APFC panel of 100 KVAR capacity having 3 phase APP type with threaded terminals (total power loss not exceeding 0.5W/KVAR) ISI marked power capacitor in six steps (5+10+15+20+50(25x2)) provided with single phase Electronic switching of below given rating to suppress switching of inrush current and reducing harmonics to improve capacitor life complete with all accessories. The system shall have micro processor based power factor controller provided in the command module for target P. F setting with digital P. F. display. The panel shall be made of 2 mm thick CRCA Sheetincluding powder coated painting provided with exhaust fans (with thermostat) and grills for proper ventilation, interconnections with suitable size conductor cables & lugs and accommodating the following switchgears& accessories:a. 250 Amp TP MCCB 25 KA : 1 No.b. LED type Indicating lamp with holder:5 Nos.c. Six step APFC relay:1 No.d. Electronic switching suitable for max 25A Load Current, 480V:6Nos.e. Electronic switching suitable for max 50A Load Current, 480V: 6 Nosf. Electronic switching suitable for max 100A Load Current, 480V: 6 Nosg. Heat Dissipaters for ES: 3 setsh. 25 Amp MCB TP: 2 Nos.i. 50 Amp MCB TP: 2 Nosj. 100 Amp MCCB TP: 2 Nosk. Selector switches: 6 Nos.l. APP Shunt capacitors ISI mark 3phase, 440V :5 KVAR -1 No, 10 KVAR-1 No, 15 KVAR -1 No, 20 KVAR-1 No, 50(25x2) KVAR-2 No |
| 81 | Supply and installation LT Electric control panel , cubical type, for indoor use floor mounted made out of CRCA outer sheet of 3 mm thick and inner sheet of 2 mm thick and angle iron legs of size 50mmx50mmx5mm having front and rear open hinged doors with front openable shutters for each MCCB with spreader with fully enclosed bus bar chamber, having insulated bas bar made but of aluminium strips of rating 1200 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter , Ammeter,CTs and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete and nut,bolt,washers for connection of cable, including necessary PCC work of height 45 cm from ground level and white washing to the platform all as specified and equipped with the following items :- (Main LT Panel, Loc : Sub Station). INCOMERI.ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 800 Amps- 01 Nos. II. Digital Ammeter 0-800 Amps CT Operated- 01 No (L&T)III. Digital Volt Meter 0-500 Volts - 01 No (L&T)IV. LED Indicator lamp in three colour RYB - 03 Nos (L&T)OUT GOINGI. MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA - 06 Nos. II.MCCB, 4pole,63 Amps , rupturing capacity 16 KA magnetic thermal release- 01 Nos. Note : The LT panel should be integrated with CSS by suitable size of Bus Bar, the rate for bus bar is deemed to be included in the quoted rate. |
| 82 | Supply and installation LT Electric control panel, cubical type, for out door use floor mounted made out of CRCA outer sheet of 3 mm thick and inner sheet of 2 mm thick and angle iron legs of size 50mmx50mmx5mm having front and rear open hinged doors with front openable shutters for each MCCB with spreader with fully enclosed bus bar chamber, having insulated bas bar made but of aluminium strips of rating 400 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter , Ammeter,CTs and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete and nut,bolt,washers for connection of cable, including necessary PCC work of height 45 cm from ground level and white washing to the platform all as specified and equipped with the following items :- (Loc : Near Bldg). INCOMERI.MCCB, 4pole,160 Amps , rupturing capacity 36 KAmagnetic thermal release - 01 Nos. II. Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No (L&T)III. Digital Volt Meter 0-500 Volts with selector switch - 01 No (L&T)IV. LED Indicator lamp in three colour RYB - 03 Nos (L&T)OUT GOINGI. MCB, 2pole,40 to 63 Amps , rupturing capacity 10 KA- 24 Nos. II.Single phase Pre paid Meter- 24 Nos. |
| 83 | Supply and fixpole mounting type FRP cable looping box of size 155 x 210 x 92mm, IP66 , with connector / terminal for connecting cable,with 40 x 6mm flat iron for fixing in street light pole,including Double Compression Weather ProofBrass Cable Glands all as specified and as directed. |
| 84 | Supply and fix GI bracket made out of 32 mm dia GI pipe length 1.50m,bent to an angle of 30 degree andfixed with 40mm x 6mm flat iron, including suitable 02 setofclamps withnut , bolts ,and washers for fixingof light to pole, complete all as directed. |
| 85 | Supply, installation , testing and commissioning ofbus bar trunking sandwich type with Aluminium Conductor of rating630 Amps IP 66 Ingress protection including following items:-(a) 630A Sandwich Type Busduct [ Type Tested ] for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-66 Ingress Protection enclosure made of 1.6mm thick steel sheet duly powder coated in convenient sections with External Metal Canopy [ MIN 1.2 MM Sheet duly powder coated] for Outdoor complete with 4 Nos aluminium bus bars with 40KA short time current withstand capacity for 1 sec for three Phase fault including 90 deg elbow, Flanged End, Adopter Box, Cu braided Flexibles with continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including MS support structure to Install Busduct in outdoor at height around 4 mtrs . (b) Straight Run Feeder IP-66 Protection (c)90 Deg Elbow (d) Flange End (e) Phase Inversion Element (f) Adopter Box (g) Cu Braided Flexibles (h) External Canopy (j) MS Support Structure (with corrosion resistance painting ) upto 2000Kg.Note : Supply only rate for the item sl no (b) to (j) mentioned herewith shall be measured and paid seperately |
| 86 | Supply only 90 Deg Elbow for the busbar trunking system |
| 87 | Supply onlyFlange End for the busbar trunking system |
| 88 | Supply onlyPhase Inversion Element for the busbar trunking system |
| 89 | Supply only Adopter Box for the busbar trunking system |
| 90 | Supply only Cu Braided Flexibles for the busbar trunking system |
| 91 | Supply only External Canopy for the busbar trunking system |
| 92 | Supply only MS Support Structure for the busbar trunking system |
| 93 | Earthing |
| 94 | Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 32x6mm [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per Electrical Plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified |
| 95 | Fire Fightingwith Automatic Sprinker & fire alarm System |
| 96 | Supply and fix ball foot valve 200 mm diawith flanged endwith strainer, Body-Cast Iron ,Ball-Nitrile Rubber Coated ,Seat Ring-Nitrile, Fastener-Carbon Steel CL4, Adaptor-Cast Iron, Pressure rating 25 - 100NB PN 6 complete. |
| 97 | Supply and fix ball foot valve 80 mm dia with flanged endwith strainer., Body-Cast Iron ,Ball-Nitrile Rubber Coated ,Seat Ring-Nitrile, Fastener-Carbon Steel CL4, Adaptor-Cast Iron, Pressure rating 25 - 100NB PN 6 complete. |
| 98 | Supply and fix ball foot valve 25 mm dia with flanged endwith strainer, Body-Cast Iron ,Ball-Nitrile Rubber Coated ,Seat Ring-Nitrile, Fastener-Carbon Steel CL4, Adaptor-Cast Iron, Pressure rating 25 - 100NB PN 6 complete. |
| 99 | Supply and fix Y- Strainer 200 mm, Ductile Iron body, 300 psi, Flanged ends ANSI, UL Listed, |
| 100 | Supply and fix Y- Strainer 80 mm dia, Ductile Iron body, 300 psi, Flanged ends ANSI, UL Listed |
| 101 | Suplply and fix Air release valve dia 40 mm /25 mm, of gunmetal body complete all as specified and as directed |
| 102 | Supply and fix Self priming pump 0.5 HP, Single Phase , Suction & Deilvery size -25 mm, Discharge- 2439 LPH, Head - upto 34 m including foundation and making necessary pipe connection at suction and deleivery side complete all as specified and as directed |
| 103 | Supply and lay XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 3 core 95 sq. mm complete all as specified and directeed. |
| 104 | Supply and lay XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 3 core 16 sq. mm complete all as specified and directeed. |
| 105 | Supply and lay XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 2 core 4 sq. mm complete all as specified and directeed. |
| 106 | S&F Motor control panel. 110 HP, to automatic and manual controlling of following pumps : Electrial driven hydrant main motor (01 No.), Sprinkler Pump Electric drive (01 No.)& Jockey pump Electrical driven (02 Nos ) and diesel Engine (01 No.) , Priming Pump Electrical driven (01 No.) complete all as specified and as directed. Note : 1. The system shall be designed for operation automatically so that as and when water is drawn from the system through any hydrant / sprinkler , the pumps will operate automatically and feed water in to the system. However once a fire pump starts working, it will be stopped only manually (except jockey pump).2. The control system shall be designed to provide the following sequence of operation:i) The Pressurization Pump shall maintain pressure in the system and shall operate only on account of slow pressure loss. In case of sudden pressure loss the Pressurization Pump shall not operate. The pump shall start when the water pressure in the system falls to a pre-set value (about 0.35 kgf/cm2 below normal system pressure) and shut down when the system pressure reaches the set value. Both limits shall be adjustable.ii) Main Electric Fire Pump / Sprinkler pump shall operate on account of sudden pressure loss. So long as Main Electric Fire Pump is working, other Fire Pumps will not operate. The pump shall start when the water pressure falls to a pre-set value in the system (about 1 kgf/cm2).In case, Normal Electric Supply fails while the Main Electric Fire Pump is running, the DG Set for essential supply will start within 5 seconds. |
| 107 | iii) The Diesel Fire Pump will start on sudden pressure loss, only in case supply to Main Electric Fire Pump is not available or within a pre-set time the Main Electric Fire Pump fails to start or fails during operation. No other pump will be working when Diesel Engine Fire Pump is in operation. Audio-Visual Alarm shall be available to indicate failure of Main Electric Fire Pump.iv) A three attempts starting facility will be provided for diesel pump.v) If within a pre-set time, the standby pump also fails to start or fails to develop pressure, the standby pump shall also be shut down and locked out. An audio visual alarm indication shall be given at the control panel. vi) In case sprinkler pump is also provided :a) Sprinkler pump will start on pressure loss (about 1 kgf/cm2) in the sprinkler header.b) If sprinkler pump does not start in preset time or fails during operation, the main electric fire pump shall start and feed water to sprinkler system.c) Diesel pump will start and feed water only in case supply to main electric pump is not available or within a preset time the main electric pump fails to start or fails during operation. No other pump will be working when diesel pump is in operation. Audio-visual alarm shall be available to indicate failure of both sprinkler and main electric pump.viii) Only one pump will be working at a time. In manual mode more than one pump can be started. An audio-visual alarm shall be given at the control panel. |
| 108 | M& L forpainting MS Pipe with a coat of primer of red oxide paint and finished with two coats of synthetic enamel paint,complete all as specified and as directed. |
| 109 | M & L for wraping 4 mm thick PYPKOTE Pipe Wrapping Coating for Corrosion protection conform to requirement of IS : 10221 and applying a final coat of bitumastic paints for anti rustprotection for GI pipe laid in trench.Holiday Testing for wrapping and coating is essential. Holiday testing may preferably be carried by flexible and detachable ring probe, which will enable the entire 360o of the surface of the pipe to be scanned.Note : Before application of corrosion protection tape all foreign matter on pipe shall be removed with the help of wire brush and suitable primer shall be applied over the pipe thereafter. The primer shall be allowed to dry until the solvent evaporates and the surface becomes tacky. Both primer and tape shall be furnished by the same manufacturer. Corrosion protection tape shall then be wound around the pipe in spiral fashion and bounded completely to the pipe. There shall be no air pocket or bubble beneath the tape. The overlaps shall be 15 mm and 250 mm shall be left uncoated on either end of pipe to permit installation and welding. This area shall be coated insitu after the pipe line is installed. The tapes shall be wrapped in accordance with the manufacturer’s recommendations. |
| 110 | Supply and fix Pressure reducing device to control pressure not to exceed 7 kgf/ cm2BibNose type ,Made of Gunmetal, Having 3” Flanged inlet & 2.1/2” female instantaneous bib nose type outlet as per BS: 336, Spindle made of brass, & C.I hand wheel, Complete with ABS blank cap & SS chain, Flange dimensions as per ANSI # 150 class FM Approved Complete |
| 111 | Supply and fixhose, re-enforced rubber lined (RRL) all synthetic fiber circular woven jacketed, EPDM synthetic rubber lining fire hose, working pressure 14kg/cm2, proof pressure 22kg/cm2, burst pressure 38kg/cm2, bearing IS: 636-2018 Type-1, in 30mtr length, 63mm dia., duly bound with SS-304 Coupling, 63mm size, pair of male & female parts, inst. type, bearing IS: 903 mark – SS wire binding |
| 112 | Supply and fix Zonal Control Assembly 50mm consisting of one no. each followingitems :(1) Butterfly Valve 2\" (Wafer Type) with Micro Switch & Position indicator; 300PSI Rating. UL Listed & FM Approved. , (2) Water Flow Detector 2\"- Flow Switch(UL/FM), (3) Pressure Relief Valve , Factory rated at 175 PSI. Size 1/2 inch, UL Listed & FM Approved, (4) Test and Drain Valve, 1 inch NPT, UL & FM Approved, (5)Pressure Gauge , 1/4 inch BSPT, 0-300PSI, 3.5 inch Dial, UL & FM Approved with ball valve, (6) Manifold - C.S. and (7) Hose Assembly - Stainless steel braidedand connectingto Sprinker pipe system , wetriser pipe and drain pipeline complete all as specified and as directed |
| 113 | Supply and fix Fire alarm control panel complying with BS EN 54 2 loop panel with 99 detectors & 99 modules & upto 200 detectors and modules (per each loop). The addressable Fire Alarm Control Panel (FACP) shall function as a network panel & also as a fully stand alone panel.Note : The FACP should have integrated power distribution module and fixed cabling done internally to guarantee a clear and tidy cable feed(c) The panel should have an LCD display with minimum 300 characters and keypad. The Display should enable a flexible design of the operating menu with variable keys and message windows fixed keys should be used for standard operating steps e.g. for fire alarm securities supervisory trouble andother events. The current status of the system should be displayed by LED\"s interfaces (RS232) enable the connection to a PC.FACP switches shall allow authorized personnel to accomplish the following,independent of the central console.(a) Acknowledge a general alarm condition.(b) Silence the local audible alarm.(c) It shall be possible to silence the alarm indicating devices (hooters). (d) Reset all zones (logical Point Group) / points, after all initiating devices have returned to normal.(e) Perform a complete operational test of the memory with a visual indication.(f) Test all panel LED\"s for proper operation without causing a change in the condition of any zone (Logical Point Group). (g) Walk test –The system shall provide both a basic and advanced walk test for testing the entire fire alarm system including testing of all devices, detectorsmodule etc. in the complete system. |
| 114 | Power supply unit of FACP shall have following characters:(a) The main power supply shall be 230V AC ±10% 50Hz ± 3% and shall in turn provide all necessary power of FACP.(b) It shall provide a separate battery control module with charger. The battery should last for 24 hours minimum in normal operation upon power failure & 30 minutes in alarm condition.(c) For ease of service, all wiring terminal blocks shall be plug-in type.(d) The fire alarm panels shall have a possibility of being interlinked by directconnectivity or an optical cable link between the various locations and should further have connectivity to the main control center. |
| 115 | Supply and fixMild Steel Announciation Panel (LED display) with zone identification facility & both audio andvisual alarm complied with EN54-2 & EN54-4 Standards and making necessary control connections . Note : In the event of operation of sprinkler(s) in an affected area,( Water flow switches shall be installed in main distribution pipes which shall be wired to sprinkler annunciation panel.)the annunciation panel shall give audio-visual alarm and indicate the affected zone. This arrangement will be independent of fire alarm system. |
| 116 | Supply and fixAnalogue Addressable Fire Alarm Repeater Panelandshall duplicate the alarm indications (audio as well as visual) of the Main Fire alarm panel. Operating Voltage24VDC, UL listed (9th Edition), 32 bit processor, Construction:18 Gauge (1.22 mm) CRCA sheet with powder‐coated Finish, RS 485 : Baud rate 19200. Connector RS 485Cable Length 1200m (Twisted pair cable recommended)Fire Relays : Type Form C, No of Relays 1, Relay contact rating 2A @ 30 VDC, 0.5A @ 125 VAC with following features :- Touch Keypad., 160 (40X4) character LCD Display, 2000 Event with Real Time Clock, RS 485 communication for Network / Repeater, One form C relay for fire, Extensive built in transient protection,Lamp test facility. Common fire, supervisory, fault LED indication complete all as specified and as directed |
| 117 | M&L for 2 core of 1.5 Sq.mm. Fire Survival Armoured Cable 600/1000 Volts Grade, Circular Stranded Plain Annealed Bare Copper Conductor, Two Layers Of Glass Mica Tapes Wrapped, XLPE Insulation, Cores Laid Up Together, Extruded LSZH Inner Sheathed, Galvanised Steel Round Wire Armoured, Extruded LSZH Compound .Outer sheath colour: Red ,drawn through steel conduit heavy duty including mounting with all accessories complete all as specified and as directed. |
| 118 | S&FPowder Fire Extinguisher (Stored Pressure type) Capacity 06 Kg duly ISI marked conforming to IS: 15683:2018, HLD (Helium Leak Detection) Tested, with UL Listed MAP 90% ABC powder complete with squeeze grip release valve, discharge pipe, locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: -30oC to + 60oC.complete all as specified and as directed. |
| 119 | S&F CO2 type Fire Extinguisher ISI marked conforming to IS: 15683. Capacity 4.5 Kg. complete with delivery hose horn, wheel type release valve, locking arrangement, operation manual and bracket. Operating Temperature: - 30oC to +60oC. complete all as specified and as directed. |
| 120 | S&F Water Fire Extinguisher Stored pressure type ISI marked conforming to IS: 15683. Capacity 9 litre. complete with delivery hose, squeeze grip release valve, locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: +5oC to + 60oC. complete all as specified and as directed. |
| 121 | S&F Mechanical Foam (AFFF) Fire Extinguisher Stored pressure type ISI marked conforming to IS: 15683. Capacity 9 litre. Complete with delivery hose, squeeze grip release valve, locking arrangement, pressure gauge, operation manual and bracket. Operating Temperature: +5oC to + 60oC. complete all as specified and as directed. |
| 122 | S& F Heavy-Duty Leak-Proof ISI Marked Fire Bucket made of Mild Steel conforming IS 2546:1974 Capacity 10 Liter. complete all as specified and as directed . |
| 123 | S&F Fire Bucket Stand suitable for 4 buckets (each bucket capacity 10 litres) complete all as specified and as directed. |
| 124 | Supply and fix Photoluminescence Emergency Glow signage, With Acrylic Base Single Side as specified and directed. |
| 125 | Supply and fix Photoluminescence Emergency Glow signage, With Acrylic Base double Side as specified and directed. |
| 126 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3 C x 95 sqmm (35.2 mm dia approx)complete. |
| 127 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3 C x 25 sqmm (21.7mm approx) dia complete . |
| 128 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 2 C x 4 sqmm (6-12 mm) dia complete. |
| 129 | WATER TREATMENT PLANT |
| 130 | 1. Design supply, fix test and commissiomimg of water treatment plant capacity 150KLD consisting of following items:-a) FILTER FEED PUMPNos.: Two Nos. (1W+1S) Flow Rate : 20,000 Litres /Hr, Head – tentative : 35 MWC 02. NAOCL DOSING SYSTEMNos.: One,Chemical to dosed : NAOCL,Capacity : 6 LPH.03. MULTIGRADE SAND FILTERNos.: One ,Design Pressure : 3.5 Kg/cm2Material of Construction : Mild Steel, Internal Protection : EpoxyExternal Protection : Red Oxide with enamel finish paintDiameter : 1000 mm, Height On Straight : 1875 mmDesign Operating Flow Rate : 20,000 Liters/HrMinimum Operating Pressure : 2.0 Kg/cm2Maximum Operating Pressure : 3.5 Kg/cm2Filtering Media : Graded Sand & GravelsType of Valve : Individual, Frontal Pipe work : One No.,Pressure Gauge : Two Nos. |
| 131 | 04. ACTIVATED CARBON FILTERNos.: One, Design Pressure : 3.5 Kg/cm2Material of Construction : Mild Steel, Internal Protection : EpoxyExternal Protection : Red Oxide with enamel finish paintDiameter : 1000 mm, Height On Straight : 1875 mmDesign Operating Flow Rate : 12,000 Liters/HrMinimum Operating Pressure : 2.0 Kg/cm2Maximum Operating Pressure : 3.5 Kg/cm2Filtering Media : Granular Activated CarbonType of Valve : Individual, Frontal Pipe work : One No.,Pressure Gauge : Two Nos. 05. SOFTNERNos. : One, design pressure 3.5Kg/cm2 , MSEDP Const. 1400 mm dia ,2500 mm height on straight (HOS) ,12000 ltrs/hrs operting flow rate , minimum operating pressure 2 kg/cm2, 3.5Kg/cm2 max operating pressure, resin cap 2100 ltr resin model indion 225 Na, Individually butterfly valve ,frontal pipe work 01 No. pressure gauge 2 Nos 07. ORP METER WITH DUMP VALVE Nos. : One, 08. ANTISCALANT DOSING SYSTEM Nos. : One, 09 REVERSE OSMOSIS SYSTEMNos. : OneFeed Flow Rate : 4000 Litres /Hr |
| 132 | Maximum Product Flow Rate : 2000 Litres/HrRecovery : 50%, Salt Rejection : 90-95% MEMBRANENo. of Membranes : 10, Dimensions ( In Inches-Dia*Length) : 8\"*40\" PRESSURE VESSELNos : 2, MOC : FRPHIGH PRESSURE PUMP AND MOTOR Nos : One No. Power supply : 415 Volts/50 Hz, MICRON FILTERMaterial of construction :PPLIMITING CONDTIONS FOR RO FEEDTotal Dissolved Solids : < 3000 ppm , Total Hardness as CaCO3 :< 1100 ppm , Silca as SiO2 : <35 ppmIron as Fe & mangnese as Mn : NilMicrobes & Organics : Nil ,Oil & Grease : Nil, Free Chlorine :Nil,SDI : <310. PH CORRECTION DOSING SYSTEM Nos: One,Capacity : 6 LPH Chemical to dosed : PH Booster11 UV SYSTEM12. INSTRUMENTS :Gauges : 1 lot, Mechanical flow meter : 3 Nos Level Switches : 1 lot, PressureNote: The rate quoted shall be include in the rate for comprehensive maintenance for two years after completion of work in phase I. The material/chemical required during DLP(outside scope of DLP) shall be measured separately. |
| 133 | AVIATION LIGHT |
| 134 | Supply and fix Aviation obstruction light LED 60 Watt type including standard fixing arrangements complete all as specified and as directedMake:- Bajaj 110731 BGAV 302 LED or equivalent |
| 135 | Supply and fixing LT panel out door type for street light & aviation light comprising of Astronomical time switches 415 v 40Amps MCBs,32A TP Contactor all as directed. Cat No. IHXTS0306A Make : Havells or equivalent |
| 136 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 core 6 sq mmcomplete all as specified |
| 137 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 4 Core 6 Sqmm (12-16 mm dia) complete all as specified and as directed. |
| 138 | TV/Telephone |
| 139 | Supply and fix TV sockets of suitable type complete all as specified and directed. Make: Legrand Cat part: 5734 25 . |
| 140 | Supply and fix Tele sockets of suitable type complete all as specified and directed . Make: Legrand Cat part: 5734 26 |
| 141 | STP 75 KLD |
| 142 | Designing (hydraulically, structurally & aesthetically), providing, constructing, hydraulic testing, commissioning and giving satisfactory trials of packaged sewage treatment plant (STP) of capacity 75 KLD complete includingOnline Monitoring System all as specified and as directed.INLETOUTLET BOD (ppm) 300-350less than 10COD (PPM)400-500 less than 20TSS (PPM)200-600 less than 20PH5-77.0-7.5Oil & grease 30-50less than 10The STP shall be based on Photo Microbial Filteration Process . The system shall includePMF Bed (Above ground tank) - 9.5m X 6.3m X 1.2m , Filter Feed Tank (UG Tank)- 3.5m X 1.8m X 1.5m (,Treated water Tank (UG Tank)- 3.5m X 1.8m X 1.5m, supply and laying of Supporting Material for PMF bed- Gravel (8”,4”,2”) & Coarse Sand, Bar Screen -01 (At the inlet of Septic tank), Filter Feed Pump (Capacity – 4.7 m3/hour,Head – 25 m Power rating – 1.0 HP ) - – Qty 2 (1 Working & 1 Stand By), Chlorine Dosing Pump- Qty 0.1 HP - 1 No., Chlorine Holding Tank Qty 1 No., - 100 Liters HDPE (Sintex or Similar makes) , Pressure sand filter – 1 unit , Dia– 0.63 m; Activated carbon filter – 1 unit , Dia – 0.71 m; Piping(UPVC) & fittings – Lot, Header pipe dia. 40 nb & laterals dia. 25 nb for PMF Bed ; Piping (UPVC) & fittings – Lot ,Balance piping & fitting for distribution system; including Control panel and cabling .Bio Culture - 6.0 Tonnes, Canna indica Saplings - 300 . The STP shall have Online Monitoring System - to measure Treated water flow meter, BOD, COD, TSS, pH |
| 143 | Supply and lay submersible copper cable 3 core x 4 sqmm for Sewage pump complte allas specified and as directed |
| 144 | Supply and laying double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 40 mm for submersible copper cable protection complete all as specified and as directed |
| 145 | Supplying, installing, testing and commissioning of electrically driven Submersible pumps 3 HP for pumping Sewage waterat14 - 22 mtr head.3-7.5lps with chrome steel impeller and cutter, non-clog to pass 40 mm size particles including Supply, installation with guide rail and lifting chain, testing complete( 2 working + 1 standby = 03 Nos) |
| 146 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core ( From Nearest panel to STP) |
| 147 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core (For Sewage/ Treated tank pump) |
| 148 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 2 C x 4 sqmm (6-12 mm) dia complete |
| 149 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3.5 C x 25 sqmm (20-23 mm) dia complete |
| 150 | Supply and installation LT Electruc control panel, cubicla type, for indoor use floor mounted made out of CRCA outer sheet of 03 mm thick and inner sheet of 2 mm thick and angle iron legs of size 50mmx50mmx5mm having front and rear open hined doors with front opennable shutters for each MCCB with spreader with fully enclosed bus bar chamber, having insulated bas bar made but of aluminium strips of rating 250 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter, Ammeter, CTs and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete and nut, bolit,washers for connection of cable, including necessary PCC work of height 45 cm from ground level and white washing to the platform all as specified and equipped with the following items :-(Loc : Pump House).INCOMER :I MCCB, 4 pole, 125 Amps, rupturing capacity 25 KA magnetic thermal release- 01 Nos.II Digital Ammeter 0-500 Amps CT Operated with saelector switch - 01 No III Digital Volt Meter 0-500 Volts with selector switch -01 Nos IV LED Indicator Lamp in three colour RYB-03 NosOUT GOING :-I MCCB, 3 pole , 40 Amps, rupturining capacity 16 KA magentic thermal release. - 06 NosII Starter 3 Phase upto 3 HP Centrifugal Pump - 02 NosIIIStrter 3 Phases upto 3 HP Submersible Pump - 3 No |
| 151 | Lift |
| 152 | Design, Supply, Install, Testing and Commisioning of Passenger Lift, with capacity of 8 Nos. passangers, Speed 1.5 metre/sec, Lift with single speed motor 415 Volts, 3 Phase, AC 50Hz supply conforming to IS-14665, suitable to serve G + 12 upper floors with AC Variable Voltage and Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (Electric motor driven mechanism), sliding stainless steel doors, Automatic Rescue Device(ARD) System (with+/-5mm with suitable dry maintenance free battery, automatic power operated Centre Opening & Sliding stainless door of 16 gauge with 3D infrared sensor in full height of door and built-in announcing system without hand set (03 Nos, One each in car, machine room and Near Ground floor landing door) complete all as specifiedinclnecessary joists for mouting machine in machine room and all civil works required with erecion of lift incl auto fan, LED lights, emergency lights all as specified .The lift shall be provided with and including the following:- (a)alarm speaker for alarm system to be fixed),stop button in car with rechargeable arrangement for battery, (b) four sleek circular LED lights fitting in false ceiling, (c) overload warning indicator both audio and visual type with tripping system having relay etc. (d) set of three nos limit switches at the bottom and top most position of lift.(e) display indicating panel, power control cables (f) testing of govt approved lift inspector including registration of lift with local body (h) Marking on lift\"s pit and lift room (i) Mirror of 6mm thickness of suitable size on one wall inside the car |
| 153 | (k)Battery operated emergency light (LED ceiling fitting), alarm (speaker for emergency alarm system to be fixed on all the floors) and stop button in car with rechargeable arrangement for battery(l) Aluminium chequered plate (3mm thick) as flooring (m) Car size shall be conformily with IS-3534-1976 and body to be stainless steel of 16 gauge mirror finish with stainless steel hand rail (n)Front door, operations with a minimum time of 10 seconds and upto a maximum timeof 30 seconds. (o) Hand rail (o) Specification plate (p) Belt drive of adequate size as per relevant IS and as per manufacturer specification(q) Suitable earthing pit earthing of lift as per IS and as required technically (r) One sleek circular PVC heavy duty fan in false ceiling.(s)Fire man switch(t)Automatic rescue device during power failure with capacity of battery designed for 45 minutes including manual operation provision (u) Other standard fixtures and fittings like guide rails, sheaves, counter weight with guard, buffers, gears, brakes, control panel, motor, locks, governor,car operational panel, power control and trailing cables complete. Note :-The rate quoted shall beIncluding the rate for comperhensive maintenanceperiod for two year after completion of the work. |
| 154 | Design, Supply, Install, Testing and Commisioning of Passenger Lift, with capacity of 13 Nos. passangers, Speed 1.5 metre/sec, Lift with single speed motor 415 Volts, 3 Phase, AC 50Hz supply conforming to IS-14665, suitable to serve G + 12 upper floors with AC Variable Voltage and Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (Electric motor driven mechanism), sliding stainless steel doors, Automatic Rescue Device(ARD) System (with+/-5mm with suitable dry maintenance free battery, automatic power operated Centre Opening & Sliding stainless door of 16 gauge with 3D infrared sensor in full height of door and built-in announcing system without hand set (03 Nos, One each in car, machine room and Near Ground floor landing door) complete all as specifiedinclnecessary joists for mouting machine in machine room and all civil works required with erecion of lift incl auto fan, LED lights, emergency lights all as specified .The lift shall be provided with and including the following:- (a)alarm speaker for alarm system to be fixed),stop button in car with rechargeable arrangement for battery, (b) four sleek circular LED lights fitting in false ceiling, (c) overload warning indicator both audio and visual type with tripping system having relay etc. (d) set of three nos limit switches at the bottom and top most position of lift.(e) display indicating panel, power control cables (f) testing of govt approved lift inspector including registration of lift with local body (h) Marking on lift\"s pit and lift room (i) Mirror of 6mm thickness of suitable size on one wall inside the car |
| 155 | (k)Battery operated emergency light (LED ceiling fitting), alarm (speaker for emergency alarm system to be fixed on all the floors) and stop button in car with rechargeable arrangement for battery(l) Aluminium chequered plate (3mm thick) as flooring (m) Car size shall be conformily with IS-3534-1976 and body to be stainless steel of 16 gauge mirror finish with stainless steel hand rail (n)Front door, operations with a minimum time of 10 seconds and upto a maximum timeof 30 seconds. (o) Hand rail (o) Specification plate (p) Belt drive of adequate size as per relevant IS and as per manufacturer specification(q) Suitable earthing pit earthing of lift as per IS and as required technically (r) One sleek circular PVC heavy duty fan in false ceiling.(s)Fire man switch(t)Automatic rescue device during power failure with capacity of battery designed for 45 minutes including manual operation provision (u) Other standard fixtures and fittings like guide rails, sheaves, counter weight with guard, buffers, gears, brakes, control panel, motor, locks, governor,car operational panel, power control and trailing cables complete. Note :-The rate quoted shall beIncluding the rate for comperhensive maintenanceperiod for two year after completion of the work. |
| 156 | Note (i) Comprehensive maintenance consists of preventive and breakdown services including replacment of minor consumables like topping of gear oils/ grease/ door rollers/ relays/ door belts/ gate lock contacts and any hardware like bolts and nuts including load testing of lift for satisfactory performance once in a year complete and rate quoted by the tenderer includes the above(ii)Preventive maintaince consists of carrying out routine check by skilled personnel as specified in Particular specifications and as recommended by Engineer-in-Charge and lubricating to all moving parts,topping up of oils as per Lubrication chart. (iii) Breakdown maintenance consists of attending to the faults that may occur and carrying out necessary repairs to electrical and control circuits and mechanical components of the lift that may occur during the operation. (iv) Fortnightly,quarterly maintaince registeres shall be maintained and signed by site engineer and contractor.(v)Load testing shall be arranged by the contractor in presence of state lift inspecter every yearas and when directed by Engr-in-charge. |
| 157 | (vi) One qualified diploma Engineer shall be employed full time along with one lift mechanic and one helper having sound knowledge and well experience in maintenance of lift. All the staff employed for maintenance will be reported to AGE E/Moffice dailly and will give day to day progress duly entered in the registers.(vii)The quoted rate shall be deemed to be included the above aspects and for consumebles such as timely topping up/replacement of gear oils,acrylic covers,fuses,copper cables,hardware like bolts, nuts, emery papers, grease, waste cotton, stationary and other miscellaneous items etc |
| 158 | M & L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x 4 mm dia GI strip,, complete all as specified and as directed by the Engineer-in-Charge |
| 159 | M & L for 25mm bore `light grade` galvanised tubes with all fitting, laid in trenches for protection of GI Strip complete all as specified and as directed |
| 160 | Supply and lay double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 75 mm, complete all as specified |
| 161 | Supply and lay double walled corrugated HDPE pipe inner plain 750 N with RR & NPF nominal dia 40 mm, complete all as specified |
| 162 | Supply, testing and laying ofLT under ground cable 1100 volts grade Cross linked Polyethylene (XLPE) insulated PVC Sheathed Cables: armoured multistranded heavy duty electric cable with aluminium conductor laid in trenches/ duct / walls includingend termination on both ends usingcable gland and lugs, connecting to switchgears,complete allas specified & as directed for 3.5 Core70 Sqmm of size. |
| 163 | Supply, testing and laying ofLT under ground cable 1100 volts grade Cross linked Polyethylene (XLPE) insulated PVC Sheathed Cables: armoured multistranded heavy duty electric cable with aluminium conductor laid in trenches/ duct / walls includingend termination on both ends usingcable gland and lugs, connecting to switchgears,complete allas specified & as directed for 4 core 25 Sq mm of size. |
| 164 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 3.5 Core70 Sqmm (33-37 mm dia) complete all as specified and as directed . |
| 165 | Supply and fix brass double compression cable gland with bright nickel plated finish , weather proof , with sealing ring made of Neoprene/Nitrile/Natural Rubber, IP 67 , size of the glade suitable for cable size 4 Core25 Sqmm (20-23 mm dia) complete all as specified and as directed . |
| 166 | Supply , installation, testing and commissioningof indoor panelCPRI Approved, IP 42made out of CRCA sheet 2 mm thick vermin proof factory madewith 40 x 40 x6 mm MS angle/channelduly painted with two coats of synthetic enamel powder coated paint over a coat of metal primer with bus bar chamber comrising of high conductivity copper bus bar of capacity 250 Amps three phase and half the capacity for neutralincluding PCC foundation suitable to accommodate the following as specified and as directed.:INCOMING(a) MCCB 415 V,125 A, 4 pole with electronicreleaseElectronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 16 KA- 01 Nos.(b)Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard pratice ---1 JobOUT GOING (a) MCCB 63 A, 415V , 3 pole withElectronic Earth leakage module ,over load short circuit protection, breaking capacity 16 KA electronic release- 04 Nos (b) MCCB 40 A, 415V , 3 pole withElectronic Earth leakage module ,over load short circuit protection, breaking capacity 16 KA electronic release - 04 No Note :-(i) All MCCBs / instruments / MCBs /Bus Bar shall be housed in a separate housing with on- off latches in the housing and Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp for each outgoing complete and all as per standard pratice. |
| 167 | DG SET |
| 168 | Supply , installation,testing and commisioning of silent Diesel Engine driven generating set of capacity 125 kVA , CPCB IV+ Emission Compliant , 415 volts at 1500 RPM ,0.8 lagging power factor at 415 V suitable for 50 Hz,3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with foundation (as per OEM design), standard control panel with necessary meter and sound proof canopy and for 0.85 Load Factor and consisting of the followings: Diesel Engine: Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable forabove output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fittedcomplete with all the required accessories. Engine mounted Instrument Panel fitted withand having digital display for following: (i) Start-stop switch with key, ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication (vi) RPM indication(vii) Over speed indication (viii) Low lub. Oil trip indication (ix) Engine Hours indication Alternator :Synchronous alternator rated at 125 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class- F/H insulation. |
| 169 | Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.Fuel Tank: Daily service fuel tank of 230 liters capacity fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories all as specified and directed.Exhaust System: 1) Dry exhaust mainfold with hospital exhaust silencer and catalytic convertor. 2)Exhaust gas piping of suitable dia. welded black MS, B Class pipeconforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool, 50 mm thick wiremesh & aluminum cladding etc., as required as directed by Engineer in Charge . Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteriesas required as perspecifications. Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere all as specified and directed. |
| 170 | Fabricating, Installing, Testing & Commissioning of Outdoor Type Automatic mains failure control Panal including auto by-pass panel, suitable for 125 KVA silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF panel to diesel engine and elsewhere if required, all complete and interlocking. The AMF panel shall have two incomer( one main power + one DG supply) and one outgoing supply. TheAMF shall consist of : Power Section: 1. 250A 4P Contactor for EB- 1 No., 2. 250A 4P Contactor for DG - 1 No. 3. 200A 3P MCCB For DG Incoming - 1 No.,4. 200A 3P MCCB For EB Incoming -1 No. 5. 300A Aluminum Bus bar - 1 No.CONTROL Section :1. Single phase Preventer - 1 No., 2. Control Contactor - 1 No., 3. Timer - 2 No., 4. Volt Amp Freq Meter - 1 No., 5. Auto Manual switch - 1 No. 6. Source Selector Switch -1 No. , 7. DC On Off switch - 1 No., 8. Battery On Off Switch - 1 No.,9. Auto Cut of Battery Charger - 1 No. , 10. Control MCB - 7 No.,11. Start Push Button - 1 No. , 12. Stop Push Button - 1 No.,13. EB Lamp RYB - 3 No.14. DG Lamp RYB - 3 No.,15. DC On lamp - 1 No.,16. EB DG ATS Closing Push Button - 1 No., 17. EB Close Lamp - 1 No. , 18. DG Close Lamp - 1 No., 19. Terminal block 4 Way - 1 No. , 20. CT Coil - 3 No. 21. Battery charger, complete with transformer/ rectifi er, D.C. voltmeter and ammeter, selectorwitch for trickle, off and boost and current adjustment. 22. Auto/Manual/Test/Off selector switch23.) 2 Nos. over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay. 24) Main supply failure monitor 25) Supply failure timer |
| 171 | Supply and installation LT Electric control panel, cubical type, for out door use floor mounted made out of CRCA outer sheet of 3 mm thick and inner sheet of 2 mm thick and angle iron legs of size 50mmx50mmx5mm having front and rear open hinged doors with front openable shutters for each MCCB with spreader with fully enclosed bus bar chamber, having insulated bas bar made but of aluminium strips of rating 400 amps for 3 phase, 415 volts, 50 C/S 4 wire system, with cable entry provision, with suitable lugs gland, voltmeter , Ammeter,CTs and phase indicator complete, duly painted with two coats of stove enameled powder coated paint over as coat of red oxide primer complete and nut,bolt,washers for connection of cable, including necessary PCC work of height 45 cm from ground level and white washing to the platform all as specified and equipped with the following items :- (Loc : Near AMF). INCOMER:I.MCCB, 4pole,160 Amps , rupturing capacity 25 KAmagnetic thermal release - 01 Nos. II. Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No (L&T)III. Digital Volt Meter 0-500 Volts with selector switch - 01 No (L&T)OUTGOING:I. MCCB, 3 pole,125 Amps , rupturing capacity 16 KAmagnetic thermal release - 02 Nos. II.MCCB, 3 pole,63 Amps , rupturing capacity 16 KA magnetic thermal release- 02 Nos. |
| 172 | ARBORICULTURE |
| 173 | M & L for Poeta soil (garden soil) mixed with requisite quantity of pesticides and fertilizers while filling (stack measurements shall be considered for payment) complete all as specified and as directed. |
| 174 | M&L for dry gober manure mixed with requisite quantity of pesticides and filled along with the garden soil in alternate layers (stack measurements shall be considered for payment)complete all as specified and as directed. |
| 175 | Supply and planting dry American/ Korean grass in mud patches and watering all as specified and as directed. |
| 176 | Supply and Planting of hedges like Aakalita Aspar/Duranta varigated by digging in trenches of size 300mm wide and 300mm deep and filling soil obtained from same location upto 200mm height and balance 100mm depth filled with garden soil and manure mixed in the required proportion and planting hedges of height 300mm above GL and removal of soil, debris, weeds to a distance exc 250m and n.exc 500m and watering etc complete incl 3 years maintenance complete all as specified and as directed |
| 177 | Supply and Planting Semi studded plants like Golden Tum/Mananta varieties as per argus/mery aglonima draft varieties by digging in trenches of size 300mm wide and 300mm deep and filling garden soil and manure mixed in the required proportionand watering etc incl 3 month maintenance complete all as specified and as directed |
| 178 | Supply and planting healthy for smallplants /shrubs ( Exsovia,Plumnbingo neerium , olundar, hisbiscus and mvssnder ayain goubichoa height 1.5 feet and digging pits size 0.6X0.6X0.6 and filling with good earth and manure 3:1 and planting shrubs directed |
| 179 | PILE FOUNDATION |
| 180 | Boring for bored cast-in-situ piles 900mm dia. in any type of soil/clay/ mud using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed |
| 181 | Boring for bored cast–in–situ piles 900mm diainhard rock/ weathered / fractured rock using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed |
| 182 | Carrying out initial compressive load test on 900mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed. |
| 183 | Carrying out initial lateral load test on 900mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed. |
| 184 | Carrying out low strain integrity test on bored cast in situ piles of 900mm diaincluding analysing the result as per ASTM D 5882 and as directed. |
| 185 | Carrying out routine compressive load test on 900mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed. |
| 186 | Carrying out routine lateral load test on 900mm dia. pile as specified in IS, complete all as specified and as directed. |
| 187 | SCHEDULE \"A\" PART-XIX: Outsourcing Services for Operation of Lifts for the First Year of the two year Defect Liability Period: |
| 188 | Outsourcing of services for operaion of passenger lifts (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) any type and make to serve S+12 floors, during First Year of the two year Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts). |
| 189 | SCHEDULE \"A\" PART-XX: Outsourcing Services for Operation of Lifts for the Second Year of the two year Defect Liability Period: |
| 190 | Outsourcing of services for operaion of passenger lifts (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) any type and make to serve S+12 floors, during Second Year of the two year Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts). |
| 191 | SCHEDULE \"A\" PART-XXI: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the First Year after Defect Liability Period: |
| 192 | Outsourcing of services for operaion of passenger lifts (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) any type and make to serve S+12 floors, during First Year after expiry of Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts). |
| 193 | Comprehensive mainenance of passenger lift, with capacity of (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) to serve S+12 floors complete including ARD and all connected components of lift during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 194 | SCHEDULE \"A\" PART-XXII: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the Second Year after Defect Liability Period: |
| 195 | Outsourcing of services for operaion of passenger lifts (4 Nos. i.e. 8 passengers & 13 passengers 02 each) any type and make to serve S+12 floors, during Second Year after expiry of Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts). |
| 196 | Comprehensive mainenance of passenger lift, with capacity of (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) to serve S+12 floors complete including ARD and all connected components of lift during Second Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 197 | SCHEDULE \"A\" PART-XXIII: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the Third Year after Defect Liability Period: |
| 198 | Outsourcing of services for operaion of passenger lifts (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) any type and make to serve S+12 floors, during Third Year after expiry of Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts). |
| 199 | Comprehensive mainenance of passenger lift, with capacity of (4 Nos. i.e. 8 Nos passenger 02 Nos, 13 passengers 02 each) to serve S+12 floors complete including ARD and all connected components of lift during Third Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge. |
| 200 | Notes for Outsourcing Services Items:(i) The lift shall be operated daily in two shifts as directed by the Engineer-in-Charge.(ii) The timings for two shifts of 8 hours each daily i.e. First shift shall be from 0630 hours to 1430 Hours and Second Shift shall be from 1430 Hours to 2230 Hours.(iii) In case of non-function of passenger lift, the Goods Lift installed in the same building shall be operated as directed.(iv) The work shall be supervised by adequately qualified supervisor with relevant experience of minimum 5 years items under BoQ shall be deemed to be including the same.(v) The unit rate is deemed to include for maintaining log books, record of repair/replacement of perished/unserviceable, minor adjustments, minor repairs of all accessories, cleaning/up keeping of lift and surrounding area as directed by the Engineer-in-Charge.(vi) One emergency light and necessary tools shall be available in a tool box with the operator in the shift for smooth functioning of lifts.(vii) Conveyance and communication system like mobile phone etc. shall be provided by the Bidders/Service providers to all Lift Attendants/Supervisors.(viii) The Bidders shall ensure house keeping, environmental cleanliness of area all round the lift and the area shall be kept absolutely neat and clean. The lift attendant shall clean the Lift car cabin, all landing floors and tiles all round lift doors with necessary cleaning material such as cotton cloth and cleaning solution etc. |
| 201 | (ix) The Bidders shall abide by the latest Labour rules and minimum wages Act.Wages paid by the bidders to the persons employed shall not be less than the minimum wages fixed by the state/central government from time to time whichever is higher. The Bidders shall also insure the workmen employed on the job.(x) The Bidders is responsible for insurance, EPF, ESI, Bonus, Labour welfare cess et., as applicable and shall be paid to the workmen as per existing Labour rules/ Acts/ regulations and rate quoted shall be deemed to be included for the same.(xi) Dress Code: The bidders shall provide the workmen with Dark Blue Colour uniform {formal pant & T-shirt} with labels showing/ printed i.e. “Name of the firm and designation” on front and on the back of the T-shirt along with protective clothing/gear. The bidders shall also provide shoes to the workers and the persons shall not be allowed to enter the work site without wearing shoes.(xii) INSURANCE: The Bidders shall be responsible for all Accidents/Injuries happening to the workmen. Any accident causing minor/fatal injury, partial disability due to any untoward incident or non-adherence to safety and IE regulations or fault in maintaining of internal electric supply system or on account of any mishandling/ wrong operation/ lack of knowledge of safety precautions or on account of any circumstances beyond his/ their control, the bidders shall be solely responsible for settling all claims of compensation to the deceased, falling which department will have a right to recover any sum indicated/ claimed by Labour commissioner/court authorities. No claim whatsoever will be entertained in this regard. No compensation is payable by the department on this account. Bidders shall provide first aid boxes to meet any emergency situations.(xiii) The rate quoted by the bidders shall be deemed to be including Basic rate (Minimum Wages as notified by Government of India/ State Government/ Local body, whichever is higher), employers contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards Bonus. Overhead and profit and labour welfare cess (LWC) as applicable depending upon the manpower requirement. This will create onus on the Bidders to applicable depending upon the man power requirement. This will create onus on the bidders to ascertain the relevant rates and quote accordingly. The rates quoted shall be inclusive of all taxes, cess, levies are applicable including GST. Note: The Manpower deployed shall be changed for every 11 months period. The rate quoted deemed to be inclusive for the same. |
| 202 | (xiii) The rate quoted by the bidders shall be deemed to be including Basic rate (Minimum Wages as notified by Government of India/State Government/Local body, whichever is higher), employers contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards Bonus. Overhead and profit and labour welfare cess (LWC) as applicable depending upon the manpower requirement. This will create onus on the Bidders to applicable depending upon the man power requirement. This will create onus on the bidders to ascertain the relevant rates and quote accordingly. The rates quoted shall be inclusive of all taxes, cess, levies are applicable including GST. Note: The Manpower deployed shall be changed for every 11 months period. The rate quoted deemed to be inclusive for the same. |
| 203 | Notes for Comprehensive Maintenance Items:(i) Comprehensive maintenance consists of preventive and breakdown services including replacement of material and labour for major/minor spare parts and consumables like topping of Oils/grease/door rollers/ relays/door belts/gate lock contacts and hardware like bolts and nuts including load testing of lift for satisfactory performance once in a year complete and rate quoted by the tenderer includes for the above Lifts.(ii)Preventive maintenance consists of carrying out routine check by skilled personnel as specified in Particular specifications and as directed by Engineer-in-Charge and lubricating to all moving parts, topping parts, topping up of oils as per Lubrication Chart including Material and labour for all consumable and major/minor spare parts.(iii)Breakdown maintenance consists of attending to the faults that may occur and carrying out necessary repairs to electrical, control circuits and mechanical components including materials & labour for all minor & major spare parts and consumables of the lift that may occur during the operation.(iv) Fortnightly, quarterly maintenance registers shall be maintained and signed by the site engineer and contractor.(v) Load testing shall be arranged by the contractor to the Lift for which repairs were carried out as and when directed by Engineer-in-Charge.(vi) All maintenance works shall be carried out by well qualified tradesmen and supervisor of OEM.(vii) The quoted rate shall be deemed to be included the above aspect and for consumables such as timely toping up oils, acrylic covers, fuses, grease, waste cotton, stationery and other miscellaneous items and all minor & major spare parts. |
| 204 | (viii) The tenderer shall submit MoU from the original manufacturer of the lift for comprehensive maintenance to undertake comprehensive maintenance during and after Defects Liability Period directly or through their nearest authorized/accredited agencies service personnel.The MoU shall be submitted at least 06 months prior to issue of completion certificate of main contract as per Work Order No I. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail