| 1 | Material and labour for excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in softloose soil for laying / taking up/ taking down of cablesand getting out and leveling of bottom surface to required level complete all as specified and directed by Engineer- in- Charge. |
| 2 | Material and labour for returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thickcomplete all as specified and directed by Engineer- in- Charge. |
| 3 | Material and labour for removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting pointcomplete all as specified and directed by Engineer- in- Charge. |
| 4 | Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc,complete all as specified and directed by Engineer- in- Charge. |
| 5 | S&F sub class B bricks of size 230mmx115mmx70mm having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protectionetccomplete all as specified and directed by Engineer- in- Charge. |
| 6 | All as per srl item No 5 here-in-before but using old bricks obtained under srl item No01 here in beforecomplete all as specified and directed by Engineer- in- Charge. |
| 7 | Material and labour for demolition of road, path, drain and concrete in ground floors, RCC/Brick wall (below or above ground level)complete all as specified and directed by Engineer- in- Charge. |
| 8 | Material and labour for providing cement concrete 1:2:4 type B-2 (using 40 mm grade crushed stone aggregate) 50 mm Thickcomplete all as specified and directed by Engineer- in- Charge. |
| 9 | Supplying, laying, jointing testing and connecting in replacementXLPE insulated, screened, PVCbedded, galvanized steel strip or wire armored,electric power cable (heavy duty) with multistranded aluminum conductors,IS 7098marked, suitable for LT 1100 Voltsystem, laid in trenchesfixed to pole, including jointing & testingcomplete all as specified and directed by Engineer- in- Charge of following sizes:-Read : Note : (i)Excavation, earth work, cable protection, sand fillings shall be measured and paid separately under respective items of schedule. (ii) Cable lugs, thimble and glands ofsuitable size of cable deemed to be included inquoted rate. |
| 10 | 16 Sqmm 4 core |
| 11 | 25 Sqmm 4 core |
| 12 | 35 Sq mm 3.5 core. |
| 13 | 50 Sq mm 3.5 core. |
| 14 | 70 Sqmm 3.5 core |
| 15 | 95 Sqmm 3.5 core |
| 16 | 120 Sqmm 3.5 core |
| 17 | 150 Sqmm 3.5 core |
| 18 | 185 Sqmm 3.5 core |
| 19 | 240 Sqmm 3.5 core |
| 20 | 300 Sqmm 3.5 core |
| 21 | 10 Sqmm 2 core |
| 22 | Material and labour for boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 80 to 100 mm bore and making good both endscomplete all as specified and directed by Engineer- in- Charge. |
| 23 | S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallahcomplete all as specified and directed by Engineer- in- Charge.of following bore sizes |
| 24 | 40 mm |
| 25 | 50 mm |
| 26 | 80 mm |
| 27 | 100 mm . |
| 28 | Taking outfaulty underground1100 Volt LT cable of differentsizes by excavation and removingbricksof any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using newbricks as requiredcomplete all as specified and directed by Engineer- in- Charge.Note: (a) 1100Volt LTcable & joints shall be measured and paid for separately under respective items of schedule. (b) Retrieved old serviceable brickswill be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs.(c) Excavation and earth work will be measured and paid for separately under respective items of schedule. |
| 29 | Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminum conductor 1100 Volts gradecomplete all as specified and directed by Engineer- in- Charge for the following sizes :- |
| 30 | 25-50 Sqmm x 3.5 core/ 4 core |
| 31 | 70-185 Sqmm x 3.5 core |
| 32 | 240-400 Sqmm x 3.5 core |
| 33 | Material and labour for disconnecting faulty /burnt end or portion of cable byremoving the cable from loop including necessary excavation & earth work , suitable size of thimble LT tap , relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 16 Sqmm 3.5 core to 300 Sqmm3.5 core of LT cable toLT Panel/pole/main switchcomplete all as specified and directed by Engineer- in- Charge. |
| 34 | Supplying and fixing in replacement MCB DP, 63Amps, 50 Hz, 10 KA, 240 Voltscomplete all as specified and directed by Engineer- in- Charge. |
| 35 | Supplying and fixing in replacement MCB SP, 6 to 32 Amps, 50 Hz, 10 KA, 240 Voltscomplete all as specified and directed by Engineer- in- Charge. |
| 36 | Material and labour for earthing in replacement complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.10 m below normal ground level) with top edge of earth plate not less than 1.5mbelow normal ground level, connected to galvanized iron strip 25X4 mmby means of bolts, nuts, check nuts and washers of galvanized iron or steel as shown in electricalplate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanized ironsides complete all as specified, including testing and commissioningcomplete all as specified and directed by Engineer- in- Charge.Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc.(b)The quoted rates shall also deemed to include the cost of earth test point and earth strip/GIlead wire and protection pipe upto 7.5 meter beyond the earth plates electrode. |
| 37 | Supply and fixing in replacement of outdoor type wall mountedBusbar chamberhaving 04 pole busbar of rating 200 amps fittedwith MCCB 100 Amp, 4 pole , 25 KA, 50 Hzas incomer including suitable hole in bus bar for outgoing cableconnection including suitable size nut bolt and fasynercomplete all as specified and directed by Engineer- in- Charge. |
| 38 | Supply, installation, testing and commissioning in replacement of factory made and testedBus bar chamberoutdoor type with canopy made out of3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work,powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement of sizenot less than 400mm x 400mm x 300mm with 4 Nos400 Amps aluminum bus bar and with 250 Amp MCCB,4 pole, 25 KA, 415 Volt 50 Hz including excavation,earth workand platform for the Bus bar chamberwith PCC 1:4:8 type D-2 with 40 mm gradedstone aggregate, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm gradedstone aggregate on top and grouting bolts etc for Bus bar chamber.The platform shall be such that it is of a height 45 cm above the nearest road levelcomplete all as specified and directed by Engineer- in- Charge. |
| 39 | Supply in replacement and Installation ofLT CT operated Trivector Meter with the following specifications:-(a) Meter Type:LT 3 Phase 4 Wire Electronic Tri vector Meter(b) Standard: IS 13779:1999 / CBIP 88 (c) Accuracy: Class 0.5(d) Voltage and Current rating:-(i) Reference Voltage - 3x240 V (ii) Basic Current (Ib)- 5 A(iii) Maximum continuous current (Imax) - 10 A(e) Rated Frequency (variation) - 50Hz (±5%)(f) Power consumption:-(i) Voltage circuit: Less than 1.5 W and 10 VA per Phase at reference voltage, reference temperature and reference frequency(ii) Current circuit: Less than 1 VA per phase at basic current, reference frequency and reference temperature(g) Display type: 8 digit 7 segment backlit LCD display, not less than10 mm character height(h) Display in the event of Power Failure: Internal battery back-up for LCD display(j)Communication port:(i) Galvanically isolated Optical Communication port for data transfer through either CMRI or remote device or both is provided (ii) RS 485 for DLMS protocol(iii) Energy recording - Unidirectional |
| 40 | Supply drawing, connecting and testing of3 core, 1.5 Sqmm PVC insulated and PVC round sheathed copper conductor (flexible ) industrial cable, 1100 Volts conforming to IS 694 in steel tubular poles from KIOSK box to street light fitting including providing suitable copper lugscomplete all as specified and directed by Engineer- in- Charge. |
| 41 | Material and labour for carrying out balance distribution of load on LT Lines by checking the existing load on the feeder (3 phase,4wire system) and accordingly shifting & connecting service cables to another phase conductor in accordance with balancing of Electric load. submit feeder wise report for before load balancingand after load balancing as per format given including maintenance of LT panel i.e. tinting of all nuts, bolts, washers, cleaning of LT panel dust etc complete all as specified and directed by Engr-in-Charge. |
| 42 | Supply drawing, connecting and testing of3 core, 2.5 Sqmm PVC insulated and PVC round sheathed copper conductor (flexible ) industrial cable, 1100 Volts conforming to IS 694 in steel tubular poles from KIOSK box to street light fitting including providing suitable copper lugscomplete all as specified and directed by Engineer- in- Charge. |
| 43 | Supply and fixing in replacement of galvanized iron strip 32 X 6 mm for additional earthing lead beyond 7.5 metercomplete all as specified and directed by Engineer- in- Charge. |
| 44 | Material and labour for cutting and removing grass, vegetation bushes etc from surrounding of installation/LT Panel and removing all rubbish to a distance not exceeding 50 mcomplete all as specified and directed by Engineer- in- Charge. |
| 45 | S&F of stranded aluminium conductor cable PVC sheathed unarmoured, 1100 Volts, flat twin corecomplete all as specified and directed by Engineer- in- Charge. of following sizes:- |
| 46 | 4 Sqmm |
| 47 | 6 Sqmm |
| 48 | 10 Sqmm |
| 49 | 16 Sqmm |
| 50 | Material and labour in replacement of Retro Reflective installation sign boards of size 12 feet x 4 feet fabricated out of 16 gauge MS sheet frame duly welded/riveted with MS square pipe of size 25mm x25mm at height 9.00 meter above ground level on stainless steel heavy dutypipe of size 80mmbore embaded 75 CM in PCC 1:2:4 type B 1 block of size 45cmx45cmx75cm including necessary excavation and earth work.The steel portion of the board shall be painted in stove enameled paint and the front & back of the frame shall be overall sheathed with blue colour base painter adhesive tape.The wiriting matter will be in English language on both sides with reflective adhesive painter tapes complete all as specified and directed by Engineer- in- Charge. |
| 51 | Material and labour for re-painting of LT Steel tubular poles of any sizes with apply of 2 coats of aluminum paint including rubbing with wire brush/emery paper & writing pole Nos in appropriate size of letters including making yellow and black strips upto height of 1.5 mtr above from ground levelcomplete all as specified and directed by Engineer- in- Charge. |
| 52 | Supply, installation, testingand commissioning in replacement of factory made testedLT Panel compartmentalized cubicaloutdoor type Floor mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminum bus bar of rating 1200 Amp installed on porcelain / SMC insulator. The panel should be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and 50X50X6 mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on out side surface and painted in side with two coat of red oxide primer and rear opening type with apron for cable entry, closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size and comprising of the following including necessary PCC platform of suitable size (Location - NEW NPG LINE)INCOMING:- (i)ACB drawn-out type with adjustablemicroprocessor release confirm to IS/IEC:60947-2, 4 pole , LT 415 Volts, 50 Hz ACgradeof 800 Amps rating50KArupturingcapacitysuitable foradjustable over loadcurrent and short circuit and earth fault protection - 01 No.(ii)Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii)Digital Ammeter 96mm x 96 mm,flush pattern with 3way selector switch- 01 No.(iv) 3 Nos of CTs ofratio800/5 Amp copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase :01 set of three OUTGOING (i)MCCB4 pole , LT 415 Volts, 50 Hz ACgradeof 315 AmpIcu=Ics=100%,36KArupturingcapacitywith adjustable Thermal and Magnetic setting releases, - 01 Nos. (ii)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 250 Amp Icu=Ics=100%,36KArupturingcapacitywith adjustable Thermal and Magnetic setting releases, complete - 02 Nos.(iii)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 200 AmpIcu=Ics=100%,36KA rupturingcapacitywith adjustable Thermal and Magnetic setting releases, complete - 02 Nos.(iv)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 100 AmpIcu=Ics=100%,36KArupturingcapacitywith adjustable Thermal and Magnetic setting releases, complete - 02 Nos.NOTE:-(i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimbles. (ii) All MCCB Should have spreader link with barrier. |
| 53 | Supply, installation, testingand commissioning in replacement of factory made testedLT Panel compartmentalized cubicalOutdoor type canopy headed Floor mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminum bus bar of rating 500 Amp installed on porcelain / SMC insulator. The panel should be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and 50X50X6 mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on out side surface and painted in side with two coat of red oxide primer and rear opening type with apron for cable entry, closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size and comprising of the following including necessary foundation platform of suitable size LOCATION-(512 LT AD,sanyath line)NOTE:-(i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) All MCCB Should have spreader link with barrier. (I) Incoming :- (i) MCCB 4P, 315 A, 36 KA, rupturingcapacitywith adjustable Thermal andMagnetic setting releases = 01 Nos.(ii)Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii)Digital Ammeter 96mm x 96 mm,flush pattern with 3way selector switch- 01 No.(iv) 3 Nos of CTs ofratio315/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase :01 set of three(II) Outgoing :-(i) MCCB 4P, 100 A, 16 KA,rupturingcapacitywith adjustable Thermal andMagnetic setting releases= 02 Nos.(ii) MCCB 4P, 63 A, 16 KA,rupturingcapacitywith adjustable Thermal andMagnetic setting releases= 04Nos. |
| 54 | All as per item No 30 here-in-before but bus bar of rating 1000 Amp-set of four. (Loc :- AFMSD )INCOMING:- (i)MCCB4 pole , LT 415 Volts, 50 Hz ACgradeof 630 Amp Amps rating50 KArupturingcapacitywith adjustable Thermal and Magnetic setting releases, - 01 Nos. .(ii)Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No Make: SECURE / L&T (iii)Digital Ammeter 96mm x 96 mm,flush pattern with 3way selector switch- 01 No. Make: SECURE / L&T (iv) 3 Nos of CTs ofratio630/5 Amp copper wound, Class 1.0, 10 VA – 1 Set(v)Indicating Lamp LED type 240 V 50 HZ AC supplyset of three colour (RYB)-01 set (Make BCH/SIEMENS/L&T) OUTGOING (ii)MCCB4 pole , LT 415 Volts, 50 Hz ACgradeof 200Amps rating 25KAIcu=Ics=100%,rupturingcapacitywith adjustable Thermal and Magnetic setting releases, - 04 Nos.(ii)MCCB4 pole , LT 415 Volts, 50 Hz ACgradeof 100Amps rating16KAIcu=Ics=100%,rupturingcapacitywith adjustable Thermal and Magnetic setting releases, - 02 Nos. |
| 55 | Supply, installation, testingand commissioning in replacement of factory made testedLT Panel compartmentalized cubicalINDOOR type Floor mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminum bus bar of rating 1200 Amp installed on porcelain / SMC insulator. The panel should be dust and vermin proof IP -65 class protection and made of 2.00 mm CRCA MS sheet and 50X50X6 mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on out side surface and painted in side with two coat of red oxide primer and rear opening type with apron for cable entry, closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size and comprising of the following including necessary PCC platform of suitable size (Location - AFTC MAIN PANEL)INCOMING:- (i)ACB drawn-out type with adjustablemicroprocessor release confirm to IS/IEC:60947-2, 4 pole , LT 415 Volts, 50 Hz ACgradeof 800 Amps rating50KArupturingcapacitysuitable foradjustable over loadcurrent and short circuit and earth fault protection - 01 No.(ii)Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii)Digital Ammeter 96mm x 96 mm,flush pattern with 3way selector switch- 01 No.(iv) 3 Nos of CTs ofratio800/5 Amp copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase :01 set of three OUTGOING (i)MCCB4 pole , LT 415 Volts, 50 Hz ACgradeof 315 Amp Amps rating36KAIcu=Ics=100%,rupturingcapacitywith adjustable Thermal and Magnetic setting releases, - 01 Nos. (ii)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 250 Amp Amps rating36 KAIcu=Ics=100% rupturingcapacitywith adjustable Thermal and Magnetic setting releases, complete - 02 Nos.(iii)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 200 Amp Amps rating25 KAIcu=Ics=100% rupturingcapacitywith adjustable Thermal and Magnetic setting releases, complete - 02 Nos.(iv)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 100 Amp Amps rating16 KAIcu=Ics=100%rupturingcapacitywith adjustable Thermal and Magnetic setting releases, complete - 02 Nos.NOTE:-(i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimbles. (ii) All MCCB Should have spreader link with barrier. |
| 56 | Note :Contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work orderand shall be verified by the Engr-in-charge. |