| 1 | BOQ (UPGRADATION OF ELECTRICAL INFRASTRUCTURE IN NCS (E) QTRS AND PROVN OF EARTHING AND MCB DISTRIBUTION BOX WITH ALLIED WORK AT ANIONICS LAB AT AF STN SOG) |
| 2 | Supply and laying LT UG XLPE insulated 1100 volt grade heavy duty cable, multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel strip wire or tape and connecting up to the electrical system with suitable size of aluminium lugs cable of size 35 sq mm 3.5 core as per IS:7098 (Part-I) including taking out of old cable complete all as specified and as directed. |
| 3 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth for laying of cables and getting out complete all as specified and directed by Engineer-in-charge. |
| 4 | Returning, filling in, including spreading leveling, watering and well ramming in layer not exc. 25 cm in soft/ loose soil, complete all as specified and directed. |
| 5 | Removing excavated material to a distance not exc 50m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified. |
| 6 | M&L Brick of common burnt clay, sub class \"B\" old size laid flat and dry on cables as in cable protection in trenches over cables perpendicular to direction of cables abutting each other complete all as specified and directed. |
| 7 | M & L for river bed fine sand laid in trenches15 cm below cable and 8 cm above the cable for cushioning/protection to cable including spreding, levelling and18cm after hand punning complete all as specified and directed at site.Note : For payment purpose pinned thickness shall be measured. |
| 8 | S&FGalvanised iron steel tubes, ISI marked light grade of 50mm bore for cable protection on the wall/ under road /under drains complete all as specified. |
| 9 | Material and labour for cutting of road, cutting chases pining in making good to facing where required to edges of landing road, hard standing, etc. and cutting chases for concealed water tubing making good exc. 20 cm but not exc. 60 cm width and digging of excavation 45 cm but not exc. 1 m depth in bituminous road / concrete surface and making good as existing surface by using 0.63 mm hard core as required including premixed high performance cold mix patching material ideal for instant as require high quality repairs to bituminous as well as concrete surface all as specified and as directed by Engr-in-Charge. |
| 10 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials or for taking credit and making good disturbed surfaces of walls, floors, etc. |
| 11 | Taking down unserviceable main switches, DBs, bus bars chambers any capacity including all fittings and fixtures such as MCBs, isolator, etc and removing from site complete all as specified anddirected. |
| 12 | Dismantling and taking down fluorescent tube light single/double of any wattage orsize fittingfor repair or replacementof burnt/worn outaccessories and removing from site. complete all as specified and as directed. |
| 13 | M&LforpointwiringwithsinglecorePVCinsulatedunsheathed 1100 volts grade FRLScablecopper conductor multi stranded of size 1.5 sqmm (Nominal size) drawn through and including non metallic rigidPVCconduitmediumgrade,ISImarked notless then 20 mm dia with all accessories like tee, straight joint, L bend etcconcealedin wall,ceiling,flooretc,pressedMS Sunkenboxes in wall of required size and colour for switches and sockets, 1.5sqmm (Nominalsize) PVC insulated (green insulation)copperconductorFRLSearthcontinuitycabledrawn withwiringandconnectedtocommonearthdolly allasspecified foronelightpoint, ceiling fan/exhaustfancontrolledbyoneSPswitchincludingmaking good distrubed surface, complete all as specified and directed.Note:- CostofMS Sunken Boxes, Hylum sheets are cutting,chieselingand cutting the wall/Ceiling for conduit fixing demand to be included in the quoted rate. The disturbed surfaces of wall for concealing the wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces.The rate for point wiring shall be deemed to include the cost of making good. |
| 14 | AllasperSrlitemNo 12here-in-beforebutforonebellpoint controlled by one bell push, complete all as specified and directed. |
| 15 | All as per item No. 12 above but for One light Point controlled by 2- Way Switch all asspecified and directed |
| 16 | All as per Srl item No 12 here-in-before but for one 5 pin socket outlet,6Ampsonsameboardwiththecable1.5Sqmmsize, complete all as specified and directed. |
| 17 | All as per Srl item No12 here-in-before but for one 5 pin socket outlet,6AmpsonIndependentboardwiththecable1.5Sqmm size, complete all as specified and directed. |
| 18 | All as per Srl item No 12here-in-before but for one power point 6 pin15Ampssocketoutlet with2.5Sqmm strandedcopper conductorFRLScablePVCinsulatedincludingearthwire2.5Sq mm copper conductor FRLS cable connected to earth dolly complete, all as specified and directed. |
| 19 | S & F switch piano flush button single pole one way 6 amp 240 volts, all as specified and as directed. |
| 20 | S & F switch piano flush type single pole two way 6 amps 240 volts, all as specified and as directed. |
| 21 | S & F bell push switch, single pole, flush type, 6 Amps, 240 volts all as specified and as directed. |
| 22 | S & F Socket outlet, flush type3 pin, 6 amps, 240 volts all as specified and as directed . Make : Anchor/Plaza/Crabtree |
| 23 | S & F Socket outlet 2 in 1, 3 pin,6/16 amps, flush type, 240 volts all as specified and as directed. |
| 24 | S & F switch piano flush button single pole one way 15 amp 240 volts, all as specified and as directed. |
| 25 | S&FFan regulator step type deluxe, 100W 230 volts, 50 HZ,complete all as specified and as directed . |
| 26 | S&F ceilingrose,surfacetype, 3 plate complete all as specified and as directed by Engr-in-Charge. |
| 27 | S&F ofBuzzer, Ding Dong AC. 230 volts,single pole, complete, all as specified and as directed. |
| 28 | S&Flamp holder, with metal ring insulated body with back plate of batten fitting complete all as specified and as directed by Engr-in-Charge. |
| 29 | Supply and fixing LED lights fitting 1x 20 W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. |
| 30 | Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete |
| 31 | S & F in replacement of LED Bulb, 10 Watts Lumen ≥ 900, Luminous afficacy ≥ 100 Lum/Watt, CCT:WW/NW/CW, CRI > 80 Ra,IP 20 rated, overmoulded plastic housing, polycarbonate diffuser, 4KV surge Protection with over voltage protection withstand upto 440 V (for 10 Minute) with open and short circuit protections as per IS: 16102 with all accessories and connecting up with twin core twisted copper conductor cable of suitable size including lamp complete all as specifiedand directed. |
| 32 | S&F in replacement of LED bulkhead luminaire 10 watt, wall/surface mounted complete with LED lamp 10 watt, all accessories, pre-wired includingprovidingflexiblecopperwire, twincore cablePVC insulated sheathed, complete all as specified and directed . |
| 33 | S&F ofLED building security light 30 watt, 230V with lens and toughen glass top.The luminarie should have a color temperature of 6500K, IP 65 complete PF > 0.95 with all accessories and including connecting up to ceiling rose with 0.5 sqmm three core copper flexible conductor cable, One GI medium grade 20/25 mm dia bracket of total length 50 cm and fixed to wall with 2 Nos MS Clamp and fastenerall as specified and directed. |
| 34 | Supply and fix exhaust fan, steel body AC single Phase. 230V copper winding of 300mm sweep 900 RPM, 50 watt ISI marked with, blades, and frame and louvers complete all as specified and as directed |
| 35 | Supply and fix exhaust fan, resin body and blades AC single Phase. 230Vof250mm sweep 1270 RPM with, blades, and frame and louvers complete all as specified and as directed |
| 36 | M&Lforcuttingopenningthroughbrickwall230mmthickbuiltin cementmotarsuitableforexhaustfan250&300mmseepincluding makinggooddismantledportionincementmortar1:3orcement concrete1:2:4typeB-1asrequired,completeallspecifiedand directed. |
| 37 | M&Lforsubmainwiring withtwosinglecore 6.0sqmm PVC insulated FRLS multistranded copper conductor cable drawing into and including rigid non metallic PVC conduit of size not less than 25mmdia,mediumgrade ISImarkedwithallconduitfittings& fixingaccessoriesandonesinglecore6.0Sqmm multistranded copperconductorcableascontinuousearthwirecompleteallas sepcified and as directed.Note-(a)Thetworunsofsinglecorecableandspecifiedearth continuity conductor and PVC conduit with fitting acessories will be measured as one run.(b) Cost of cutting, chasing and make good to existing surfaces i.e the disturbed surfaces of wall for concealing the wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces are deemed to be including in the quoted rate by the contractor. |
| 38 | Takingdownceilingfansofanysweepincluding cable connectionsand disconnecting of fan bladesand removing thefanwithblades and deposit tostoreyard forfurtherhanginginitsoriginalposition oranyother position including as per direction of Engineer-in-Charge including it\"s fitting and fixtures after carrying markingofMESnumberwith blackpaintafterpreparationofsurfacereassemblingthefanetc including testing complete serviceable all as specified and as directed by Engr- in-charge.Note:-Anydamagehastobemadegoodbythecontractorto make the item functional after testing. |
| 39 | Takingdownexhaustfansofanysweepincluding cableconnections andremovingtheexhaustfanwithblades depositto store yardfor further fixing initsoriginalpositionoranyotherpositionasperdirectionof Engineer-in-Charge including it\"sfittingand fixturesafter carrying outservicereassembling the fan etc including testing complete all as specified and as directed . |
| 40 | Supply and fix metal AC box Single pole and neutral enclosure withtwo pin and earth plug and socket complete with one single pole MCB 20 A 240 V complete all as specified and directed by Engr-in-charge |
| 41 | Supply and Fixing Sheet metal TPN double door DB 4 Way, 415 Volt, TPN with 200 Amps rated bus bar and with neutral, earthing bar complete all as specified and as directed by Engr-in-Charg |
| 42 | S&F as in replacement MCB distribution board, IP 43 protection, Double door,SPN, 230 Volts, 8 way with 200 Amps rated bus bar and with neutral, earthing bar complete all as specified and directed. |
| 43 | S & F as in replacement MCB TPN63 Amps, breaking capacity 10 KA \"C\" curve confirming to IS-8828, 415 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc. completeallasspecifiedandas directed . |
| 44 | Supply and fixing 240V, 10 KA \"C\" curve miniature circuit breaker (MCB)single pole and Netural current carrying capacity 40 to 63 AMP,Completeallas sepcified and as directed. |
| 45 | Supply and fixing 240V, 10 KA \"C\" curve miniature circuit breaker (MCB) single pole, current carrying capacity 6 to 32 AMP,Complete allas sepcified and as directed.. |
| 46 | Taking down existingstorage type water heater of any capacity of any type and size by disconnecting from Power socket, carring out necessary repairincluding cleaning and inner water tank, removing of hard water deposites and connected back and refixing in original position including testingcompleteall as specified and as directed. |
| 47 | M & L as in relacement PVC Connections of 15 mm size 450mm incluidng with PTMT nuts of length 450 mm complete as directed. |
| 48 | M&L for earthing complete with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earthpitnotlessthan2.25metersbelow groundlevel)withtop edgeofearthplatenotlessthan1.5metersbelowgroundlevel connected to galvanized earth wire 4.00 mm diaby means of nuts, bolts, thimbles, check nuts, washers of GI or steel,PCC (concrete chamber of size 300 mmx 300 mm x 300 mminside dimension) shallbePCC1:3:6typeC-1 (using20mmgradedcrushedstone aggregate)withfairfinish, internalsurfaceofconcretechamber shallbegiven15mmthickplasterinCM1:4,funnelwithwire gaugeof22gauge,8meshperlinerinch,80mmthickPCCpit cover320mmx320mmofRCC1:2:4typeB-1(using20mm graded crushedstoneaggregate)reinforcedwith XPMJALLIand charcoal dust and common salt all as shown in electrical plate No 3 ofMESSSRPart-I(2009)andspecifiedincluding provisionof earthwireprotectedby15mmdiamediumgradeGIpipeand watering GI pipe shall be 20mm bore medium grade etc complete, allexcavationand earthwork&connectingtheearthingtoan earthingtestpointmainswitchboard asspecifiedandtestingon completion complete all as specified & directed. |
| 49 | M & L for surface submain wiringwith two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 2.5 sqmm (Nominal area) drawn through in and including steel conduitsize with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 2.5 sqmm as earth lead and connected to earth dollyall as specified and directed. NOTE: (a) Two run of cable with one run of earth wire and one run of steel conduit will be measured as one length. |
| 50 | M & L for surface submain wiringwith two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 4.0 sqmm (Nominal area) drawn through in and including steel conduitsize with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 4.0 sqmm as earth lead and connected to earth dollyall as specified and directed. NOTE: (a) Two run of cable with one run of earth wire and one run of steel conduit will be measured as one length. |
| 51 | M & L for surface submain wiringwith two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 6.0 sqmm (Nominal area) drawn through in and including steel conduitsize with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 6.0 sqmm as earth lead and connected to earth dollyall as specified and directed. NOTE: (a) Two run of cable with one run of earth wire and one run of steel conduit will be measured as one length. |
| 52 | M & L for surface submain wiringwith four single core PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 10 sqmm (Nominal area) drawn through in and including steel conduitsize with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 10 sqmm as earth lead and connected to earth dolly all as specified and directed. NOTE: (a) Four run of cable with one run of earth wire and one run of steel conduit will be measured as one length. |
| 53 | M & L for surface earth wirewith one single core green PVC insulated unsheathed 1100 volt grade multi stranded FRLS Copper conductor cable of size 4 sqmm (Nominal area) drawn through in and including PVC casing/caping size with all fittings and accessoriesas earth lead and connected to earth dolly and making good to disturbed surfaces all as specified and directed. NOTE: (a) one run of cable with one of PVC casing/caping will be measured as one length. |
| 54 | Supply & fix modular switch 1 way, 16 Amps, 1 module (ISI marked) complete all as specified and as directed by Engineer-in-Charge. |
| 55 | Supply & fix modular socket, 6/16 Amps 2 moduler, multi pin (ISI marked).complete all as specified and directed by Engr-in-Charge. |
| 56 | Supply & fix modular white cover plate with frame 6 module complete all as specified and directed by Engr-in-Charge. |
| 57 | Supply & fix modular PVC flush box 6 module complete all as specified and directed by Engr-in-Charge. |
| 58 | S&F MCB, Double Pole, 6 to 32 amps, 415 volts, 10 kA breaking capacity, \"C\" curveall as specified and as directed. |
| 59 | S&F earth continuity conductor or main earthing lead of size 20x3 mm copper strip fixed to wallto ples or any other indicated situation for loop earthing etc directed. |
| 60 | M&L for commissioning , installation and testingof maintenance free UL approved copper bonded earth rod of 10 feet length50 mm dia made of high tensile low carbon steelrod, molecularly bonded with 99.9% electrolytic grade copper on outer surface (minium copper bonding thickness 250 microns) with exothermally jointed copper bus bar of 200x 50x 6mm for connection ,The rod and exothermic joint together successfully tested at 25 KA fualt current by CPRI with 75 Kg eco friendly earth enhancing compund with each earth rod, The earth pit should be 125 mm dia.The compund should comply to IEC 62561-7 havingpassed leaching, corrosion, sulphur and resisitivity tes as per IEC62651-7 by NABL accredit Lab with FRP earth pit cover oftop size lockable Lid.It includes GI Protection pipe light grade of size 40 dia with copper strip of size 32x6 mm upto test point , strip should be run on PCC block of suitable size upto wall to avoid thouching to ground including connecting of strip between two earthing earth pit cover complete all as specified and directed by Engr in - Charge. |
| 61 | Contract Amount shall be derived after deducting the amount of Schedule of Credit in General Summary of tender documents. |