| 1 | Taking down carefully aluminum/copper point wiring (light, fan, socket or power) complete along with fittings such as switches, ceiling roses, pendants, regulators sockets etc, and removing from site and making good disturbed surfaces of walls, floors etc., all as directed. |
| 2 | Taking down existing unserviceable MCB DB along with MCBs completeby disconnecting all as directed. |
| 3 | Taking down existing unserviceable T/Light fitting . |
| 4 | Taking down existing unserviceable sub main wiringaluminum/copper cable along with all conduits and fittings all as directed. |
| 5 | M&L for point wiring using approved colour coding as per IS (For phase and neutral), with stranded copper conductor 1.5 Sqmm (nominal area), single core, multistranded, FRLS, PVC insulated and unsheathed cable 1100 volts grade, ISI 694 marked drawn in existing conduits (surface/recessed), terminated in junction box incl 1.5 Sqmm (Nominal area) single core, multistranded, FRLS, PVC insulated and unsheathed cable as earth continuity conductor to common earth and connected to earth dolly complete all as specified for the following :-Note :- 1. Colour code of wiring should be(for phase-Red,neutral-black and earth wire-green) 2. Modular switch sockets fan regulator shall be measured and paid separately under respective items. 3. Cost of Modular MS Box, Modular cover plate an frameof any modules as required at site and as directed by ENgr-in-charge is deemed to be included in the quoted rates. |
| 6 | One light point / fan point controlled by one, one way 5 Amps switch |
| 7 | One 3 pin socket outlet 5 Amps on independent board |
| 8 | One 3 pin socket outlet 5 Amps on same board |
| 9 | M&L for point wiring using approved colour coding as per IS (For phase and neutral), with stranded copper conductor 1.5 Sqmm (nominal area), single core, multistranded, FRLS, PVC insulated and unsheathed cable 1100 volts grade, ISI 694 marked drawn in and including stove enamelled metallic conduit with fittings ISI marked, terminated in junction box incl 1.5 Sqmm (Nominal area) single core, multistranded, FRLS, PVC insulated and unsheathed cable as earth continuity conductor to common earth and connected to earth dolly complete all as specified for the following :-Note :- 1. Colour code of wiring should be(for phase-Red,neutral-black and earth wire-green) 2. Modular switch sockets fan regulator shall be measured and paid separately under respective items. 3. Cost of Modular MS Box, Modular cover plate an frameof any modules as required at site and as directed by ENgr-in-charge is deemed to be included in the quoted rates. |
| 10 | One light point / fan point controlled by one, one way 5 Amps switch |
| 11 | One 3 pin socket outlet 5 Amps on independent board |
| 12 | One 3 pin socket outlet 5 Amps on same board |
| 13 | M&L for point wiring using approved colour coding as per IS (For phase and neutral), with stranded copper conductor 2.5 Sqmm (nominal area), single core, multistranded, FRLS, PVC insulated and unsheathed cable 1100 volts grade, ISI 694 marked drawn in existing conduits (surface/recessed), terminated in junction box incl 2.5 Sqmm (Nominal area) single core cable as earth continuity conductor to common earth and connected to earth dolly complete for one power point 15 Amps all as specified. Make of cable : Plaza/Finolex/HavellsNote :- 1. Colour code of wiring should be(for phase-Red,neutral-black and earth wire-green) 2. Modular switch sockets fan regulator shall be measured and paid separately under respective items. 3. Cost of Modular MS Box, Modular cover plate an frame of of any modules as required at site and as directed by ENgr-in-charge is deemed to be included in the quoted rates. |
| 14 | M&L for point wiring using approved colour coding as per IS (For phase and neutral), with stranded copper conductor 2.5 Sqmm (nominal area), single core, multistranded, FRLS, PVC insulated and unsheathed cable 1100 volts grade, ISI 694 marked drawn in and including stove enamelled metallic conduit with fittings ISI marked, terminated in junction box incl 2.5 Sqmm (Nominal area) single core cable as earth continuity conductor to common earth and connected to earth dolly complete for one power point 15 Amps all as specified. Make of cable : Plaza/Finolex/HavellsNote :- 1. Colour code of wiring should be(for phase-Red,neutral-black and earth wire-green) 2. Modular switch sockets fan regulator shall be measured and paid separately under respective items. 3. Cost of Modular MS Box, Modular cover plate an frame of of any modules as required at site and as directed by ENgr-in-charge is deemed to be included in the quoted rates. |
| 15 | M&L for Sub main wiring/power wiring PVC insulated, armoured, heavy duty electric cable with copper conductor, 1100 Volts grade, cross sectional area 16 sqmm 4 core all as specified and directed by Engr in charge |
| 16 | M&L for Sub main wiring/power wiring complete with four runs of16.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through existing conduits (surface/recessed) , with one run of PVC insulated, 16.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. NOTE :- Fourruns of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length. |
| 17 | M&L for Sub main wiring/power wiring complete with four runs of16.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and including stove enamelled steel conduit with all fittings as required , with one run of PVC insulated, 16.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. NOTE :- Fourruns of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length. |
| 18 | M&L for Sub main wiring/power wiring PVC insulated, armoured, heavy duty electric cable with copper conductor, 1100 Volts grade, cross sectional area 10 sqmm 3 core all as specified and directed by Engr in charge |
| 19 | M&L for Sub main wiring/power wiring complete with two runs of 6.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through existing conduits (surface/recess) , with one run of PVC insulated, 6.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. NOTE :- Tworuns of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length. |
| 20 | M&L for Sub main wiring/power wiring complete with two runs of 6.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and includingconcealed stove enamelled steel conduit with all fittings as required , with one run of PVC insulated, 6.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. NOTE :- Tworuns of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length. |
| 21 | M&L for Sub main wiring/power wiring complete with two runs of 4.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through existing conduits (surface/recess) , with one run of PVC insulated, 4.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. NOTE :- Tworuns of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length. |
| 22 | Supply and Fixing Ceiling rose 3 terminal 5 Amps 230 volts PVC/Polycarbonate, insulated body. |
| 23 | Supply & Fixing 6 Amps 1 way one module switch complete. |
| 24 | Supply & Fixing 6 Amps 3 pin socket two module complete. |
| 25 | Supply & Fixing 16 Amps one way one module switch complete. |
| 26 | Supply & Fixing modular multi socket outlet 6A/16 Amps 3/3 Pin socket 2 module complete. |
| 27 | S&F MCB DB SPN 4 way with 200 Amps ratedbus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed. |
| 28 | S&F MCB DB SPN 6 way with 200 Amps ratedbus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed. |
| 29 | S&F MCB DB SPN 8 way with 200 Amps ratedbus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed. |
| 30 | S & F Vertical Distribution Board iron clad, double door with IP-43 1K-09 protection suitablefor MCCB as incommer and MCB SP as outgoing 415 Volts 3 phase 50 C/S 4 way, complete with appropriate size copper bus bar and neutral link confirming to cat pt No 607790 of Legrand or equivalent of make Hager / Merlin Gerin multi-9 complete with one MCCB 3 pole 415 Volts 100 Amps rating with rupturing cap 16 KA of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge. |
| 31 | S & F Vertical Distribution Board iron clad, double door with IP-43 1K-09 protection suitablefor MCCB as incommer and MCB SP as outgoing 415 Volts 3 phase 50 C/S 8 way, complete with appropriate size copper bus bar and neutral link confirming to cat pt No 607790 of Legrand or equivalent of make Hager / Merlin Gerin multi-9 complete with one MCCB 3 pole 415 Volts 125 Amps rating with rupturing cap 16 KA of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge. |
| 32 | S&F MCB SP 6-32 Amps 230 volts 6 KA , B curve ISIall as directed |
| 33 | S&F MCB SP 6-32 Amps 230 volts 6 KA , C curve ISIall as directed |
| 34 | S&FMCBSPN 32 Amps 230 volts , C curve ISI marked all as directed |
| 35 | S&FMCBSPN 25 Amps 230 volts , B curve ISI marked all as directed |
| 36 | S&F MCB TP 63 Amp 415 V 10 KA C curve ISI marked all as directed |
| 37 | S&F MCB TPN 63 Amp 415 V 10 KAC curve ISI marked all as directed |
| 38 | S&F LED Batten industrial type 40 W , 230 Volt, waterproof with IP-65, IK08 protection, robust and durable body made of ABS or Polycarbonate with a frosted or milky polycarbonate diffuser cover, high efficiency SMD LED chipsfor enhanced brightness, integrated high quality driver offering protection against surge voltage, open circuits, short circuits and having high power factor (PF>0.95) and low THD<20% |
| 39 | S&F LED tube light with batten 1X18/20 watts LED, 230Volt energy efficient, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with three core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed. |