| 1 | Supply, installation, testing and commissioning of diesel engine/ driven generating set of capactity 125 KVA/ 100KW, 0.8 power factor at 3200 Mtr altitude and having consider 12 percent dearating factor,mounted on common base frame alongwith sound proof enclosure (acoustic enclosure) 1500 RPM, with silencer pipe independently supported from engine to outside upto 1 Mtr, AVM padded foundation as per manfacture\"s design, cold starting kit, battery start with suitable size cable for connection from DG Set to panel board (DG Set shall be capable of operating in temperature range of (-35) degree centrigade to (+20) degree centrigade) complete with and incl the following:-(a) PRIME MOVER:- Vertical diesel engine of suitable capactiy water cooled (Radiator mounted) closed circuit as per BS 649 or IS-10002 direct injection type turbo charged electric starting system having rated speed 1500 RPM. The DG Set shal be capable of running 24 hours continuosly with 10% over loading for one hour in every 12 hours as per BS 5514/- BS 649. Engiene shall be equipped wth all standard fittings as per manfacturer recommendation and mounted on common base frame with following accessories as per manufacturer design:-(i) RPM cum Hrs meter.(ii)Battery charging ammeter.(iii) Ignition key/ starting with push button switch.(iv) Lubricating oil pressure gauge.(v) governor controlling.(vi) temperature gauge.(vii) AMF Pannel. |
| 2 | (aa)Two nos 24V 180AH maintenance free batteries. Make Exide/ Standard.(ab)Battery charging alternator with inbuilt regulator.(ac)Starter motor of suitable capacity.(ad)Battery leads (copper cable) of suitable size with brass thmbles and terminal.(B) ALTERNATOR:-Alternator rating 125KVA/ 100KW 03 Phase 50 cycles, 415 Volts 04 wires supply at NTP 0.8 power factor @ 1500 RPM, self-excited, self-regulated mounted on a strong fabricated steel frame suitable for mounting on permanent foundation to be coupled with the above engine. The alternator shall be confirming to BS-2613 or IS-4722.(C) ACCOUSTIC ENCLOSURE:-Set shall be fitted with accoustic enclosure suitable for 125 KVA as per manfacturer instruction and confirming to CP CB norms accoustic enclosure shall comply with revised noise limit for DG Set vide GSR-371 (E) dt 17 May 2002 and its amendments under environment (protection) act 1996 issued by Min of Environment and forest.(D) CONTROL PANEL:- Alternator control panel alongwith self regulated AVR system inbuilt, cubical type with internal copper wiring for 125 KVA alternator 415 V3 phases, 04 wire, 50 Hz fabricated out of 2 mm thick CRCA sheet painted internally and externally with 02 coats of synthetic enamel paint over 01 coat of primer including following accessories as per manfacturer design:-(i) Digital Voltmeter 0-500 amp of size 96 mm x 96 mm AC with flush type selector switch, Make:-AE/ Legrand.(ii)DIgital ammeter 0-500 Amp of size 96 mm x 96 mm (3 phase/ 1 phase) AX with flush type selector switch. |
| 3 | (iv)MCCB 400 Amps, 4 pole 36KA-01 (for incoming) as recommended by manfacturer.(v) Set of copper bus bar for suitable capacity.(vi)Set of indicator lamps LED type (Red, Yellow & Blue).(vii) Set of instrument fuses.(viii) Digital energy meter having facility to show KWH, KW, KVA, power factor reading etc.(ix)Running hour meter. (E) OTHER FITTINGS:-(i) Battery charger having electric circuit consisting of triodes, rectifier, capacitor and resistor etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to the battery charger through control panel are electric power point.(F) FUEL TANK:- Of suitable capactity as per manfacturer instructions capable to store 12 hrs running of DG Set, as per manfacturer design, with all pipes connecting upto fuel pumps including oil level indicating gauge in ltrs, drain and air vent plug etc.(i)The Contractor shell supply 2 yrs maint spare of the above Genr set:-(aa) Fuel filter - 12 Nos(ab) Lub Oil Filter - 12 Nos(ac) Eliment air Cleaner outer - 06 Nos(ad) Eliment air cleaner ineer - 06 Nos(ae) Coolant & engine Oil. |
| 4 | M & L for Earthing complete with galvanised steel earth plate electrode of size (600 x 600 x 6.3) mm thick buried directly into ground vertically to depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, surrounded on all sides by alternate layers of 150 mm thick charcoal and common salt,connected to MS galvanized earh stripof size 32 x 6 mm by means of lugs, bolts, nuts, washer, check nuts of galvanised iron or steel all as shown in Electrical plate No. 3, wire protected by dia 15 mm bore light grade GI Pipe laid in floor and fixed to wall with proper size of clamps and watering pipe of bore 20 mm dia GI light grade including wire mesh funnel, PCC, earth chamber pit with PCC 1:2:4 type B-1 using 20 mm grade stone aggreate including form work cement mortar including CI Pit cover with frame necessary excavation and earth work in any type of soil including testing on completion for desired result all as specified. ( For DG Set) |
| 5 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3½ core. |
| 6 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3½core. |
| 7 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for taking out pipe line etc for repairs / laying cables etc and getting out in soft / loose soil complete all as specified and as directed by the Engineer - in - Charge. |
| 8 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in hard/dense soil |
| 9 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed by the Engineer - in - Charge. |
| 10 | Removal of excavated material [soil] to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed by the Engineer - in - Charge. |
| 11 | Material and labour for un reinforced pre cast concrete cable cover class LV type I, flat size 250 mm x 150 mm x 40 mm. |
| 12 | Sand cushioning to under ground cable complete all as specified in clause 19.75 of SSR Part - I. |
| 13 | M&L for Busbar chambers with 4 aluminium busbar strip of rating 400 Amp 6 way fixed on angle iron of size 40mm x40mm x5mm complete all as specified and directed by Engineer in Charge. |
| 14 | Supply install, test and commission cubicle type CPRI approved LT feeder piller box mounted on pedestal factory made, totally enclosed, dust & vermin proof (protection class IP 54), (front opening) with propper locking arrangement made of MS angle iron frame size of 50mmx50mmx6mm and CRCA sheet of 3.15 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide primer.The panel shall be suitable for 415 volts, 50 Hz 3 phase 4 wire system and shall be complete withinternal wiring, thimbles glands and shall be complete allas specified as directed with the undermentionedaccessories.The cost of the PCC pedestal is deemed to be included in the quoted rate of above item.The panel will comprise of the following :-(a) On Load Changeover 200 Amp 4 Pole.(b) Supply and fix 4 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 50 KA(c) S&F 4 Pole MCCB 63Amp, 50 Hz, 415 V with rupturing capacity 25 KA.(d) Digital Voltmeter 0-500 Volts with VSS - 01 Set(e) Digital Ammetre with CTs & ASS -01 Set(f) LED Phase indicating lamp ( R.Y.B ) - 01 Set (g) Copper Bur bar TPN 630 Amp Rating - 01 Set |
| 15 | M & L for Earthing complete with galvanised steel earth plate electrode of size (600 x 600 x 6.3) mm thick buried directly into ground vertically to depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, surrounded on all sides by alternate layers of 150 mm thick charcoal and common salt,connected to MS galvanized earh stripof size 32 x 6 mm by means of lugs, bolts, nuts, washer, check nuts of galvanised iron or steel all as shown in Electrical plate No. 3, wire protected by dia 15 mm bore light grade GI Pipe laid in floor and fixed to wall with proper size of clamps and watering pipe of bore 20 mm dia GI light grade including wire mesh funnel, PCC, earth chamber pit with PCC 1:2:4 type B-1 using 20 mm grade stone aggreate including form work cement mortar including CI Pit cover with frame necessary excavation and earth work in any type of soil including testing on completion for desired result all as specified. |
| 16 | M&L for Cement concrete 1:5:10 type E2 (40mm graded aggregate) in foundations,filling and mass concrete. |
| 17 | M&L for Pre-cast cement concrete block Using (PCC 1:3:6 type C1) masonry with solid blocks, exc. 10 cm in width and setting in CM (1:4), complete all as specified |
| 18 | M&L for rendering 15mm thick in CM(1:6) on fair faces of brick work or concrete surfaces finished even and smooth (without using extra lime or cement) |
| 19 | M&L for Cement concrete 1:3:6 type C2 in foundations, filling and mass concrete. |
| 20 | Sand filling under floors or in foundations including watering and consolidation |
| 21 | M&L for Cement concrete type B- 2,100 mm thick 1:2:4 (40mm graded aggregate) in sub base of flooring. |
| 22 | S&F for Pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering /cladding to wall, fixed with self tapping screws as specified. |
| 23 | S&F for Rolled mild steelin Roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat section) including distance pieces, cleats etc. conforming to FE-410W (Gde-E250) quality -B. |
| 24 | S&F for Rolled mild steel in joist, channel, angle, or tee sections, fixed independently, without conncecting plates, etc. (cut to ordinary length ie. Within 20mm of the length indicated) conformingFE-410W (Gde-E250) quality -B. |
| 25 | M&L for preparation of new steel surfaces of any description over 10cm in width or girthand applying two coats of synthetic enamel paint (1st quality) over one coat of red oxide primer complete all as specified and directed. |
| 26 | Providing and laying 80mm thick factory made chamfered edge cement concrete paver block of M-30 grade with approved colour, design & pattern as in footpath,parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of coarse sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with fine sand and cutting of paver block as per required size and pattern, finishing and sweeping extra sand; complete. |
| 27 | M&L for Providing, cement concrete 1:3:6 type C1 (using 20mm graded agg) in roof kerbs or mud stops, rounded or chamfered on edges. |