| 1 | Dismantling/Taking out ACSR conductor/GI wire complete. |
| 2 | Dismantling/Taking out XLPE cable of any size and type complete. |
| 3 | M&Lfor tube light gread GI laid under road/culvert/drain fixed to pole wall with help of flat iron clamps etc for cable protection for the following sizes :- |
| 4 | 40 mm nominal bore complete all as specified and directed. |
| 5 | 50 mm nominal bore complete all as specified and directed. |
| 6 | Supply and laying cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area, electric power cable grade with stranded aluminium conductor of size10 Sqmm, 4 core including lux/thimbles. Note : Unserviceable cable shall be deposit in MES Yard. MAKE: HAVELLS/POLYCAB/SCI/Finolex |
| 7 | - do- all as per item No 04 above but 16 sqmm, 4 core complete all as specified and directed. |
| 8 | - ditto - all as per item No.04 above but 50 Sqmm 3.5 core complete all as specified and directed. |
| 9 | - ditto - all as per item No.04 above but 95 Sqmm 3.5 core complete all as specified and directed. |
| 10 | - ditto - all as per item No.04 above but 120 Sqmm 3.5 core complete all as specified and directed. |
| 11 | -ditto - all as per item No.04 above but 150 Sqmm 3.5 core complete all as specified and directed. |
| 12 | -ditto - all as per item No.04 above but 185 Sqmm 3.5 core complete all as specified and directed. |
| 13 | Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for foundation of poles/ stays/ laying of cables etc and gettingout including trimming of sides of trenches complete all as specifiedand directed. |
| 14 | Returning, filling the soft / loose soil including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer complete all as specified and directed. |
| 15 | Removing of surplus excavated soilto a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point completeall as specified and directed. |
| 16 | Material and labour for sand cushioning to under ground cable with a layer of sand 8 cm thick before laying of cable and 15 cm thick after laying of cable complete all as specified and directed. |
| 17 | Material and labour for brick protection using old size sub class ‘B’bricks, laid flat, dry adjacent to each otherlaid length wiseperpendicular to theaxis of cable complete all as specified and directed. |
| 18 | M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected using galvanised iron strip 32x6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. |
| 19 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class \"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of following :- |
| 20 | (Sub Main LT Panel) . Make of MCCB : Legrand/Havells/Schneider/L&TINCOMING : MCCB 4 Pole, 250 Amps ,415 Volt of breaking capacity 36 KAwith Adjustable Thermal Magnetic- 01 Nos. BUSBAR: TPN 400 A- 01 Sets.OUTGOING : MCCB 4 pole 415 V160 Amps 35 KA, TM release - 01 nosMCCB 4 pole 415 V 63 Amps 25 KA, TM release - 04 nosMCB SPN, 240 V, 6-32 Amps -02 NosVoltmeter (0-500) V digital type with selector switch.-01 No, Astro timer switch 32A with auto ON/Off to street lights including TPN MCB 32AAmpere Meter (0-500) Amperes, 96mm square, digital type, CT connected with suitable CTs and selector switch-)1 No, RYB Phase indicator, LED type each Set |
| 21 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI type tested) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class \"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of following :- |
| 22 | (Sub Main LT Panel) . Make of MCCB : Legrand/Havells/Schneider/L&TINCOMING : MCCB 4 Pole, 160 Amps ,415 Volt of breaking capacity 36 KAwith Adjustable Thermal Magnetic- 01 Nos. BUSBAR: TPN 250 A- 01 Sets.OUTGOING : MCCB 4 pole 415 V 25-100 Amps 36 KA, TM release - 04 nosMCCB 4 pole 415 V 63 Amps 25 KA, TM release - 04 nosMCB SPN, 240 V, 6-32 Amps -02 NosVoltmeter (0-500) V digital type with selector switch.-01 No, Astro timer switch 32A with auto ON/Off to street lights including TPN MCB 32AAmpere Meter (0-500) Amperes, 96mm square, digital type, CT connected with suitable CTs and selector switch-)1 No, RYB Phase indicator, LED type each Set |
| 23 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class \"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of following :- |
| 24 | (Sub Main LT Panel) . Make of MCCB : Legrand/Havells/Schneider/L&TINCOMING : MCCB 4 Pole, 100 Amps ,415 Volt of breaking capacity 66 KAwith Adjustable Thermal Magnetic- 01 Nos. BUSBAR: TPN 150 A- 01 Sets.OUTGOING : MCCB 4 pole 415 V 25-100 Amps 36 KA, TM release - 04 nosMCB SPN, 240 V, 6-32 Amps -03 NosVoltmeter (0-500) V digital type with selector switch.-01 No, Astro timer switch 32A with auto ON/Off to street lights including TPN MCB 32AAmpere Meter (0-500) Amperes, 96mm square, digital type, CT connected with suitable CTs and selector switch-)1 No, RYB Phase indicator, LED type each Set |
| 25 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class \"B\") work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of following :-(Bus Bar Panel). Make of MCCB : Legrand/Havells/Schneider/L&TOUTGOING : MCCB 4 Pole, 25-100 Amps ,415 Volt of breaking capacity 16 KAwith Adjustable Thermal Magnetic- 01 Nos.Digital Multi function meter connected with suitable CTs and selector switch-1 No, Phase indicator RYB LED type - 1 Set |
| 26 | Supply and installhi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity 1.5 TR . Note : Split A/Cs rate include the cost of extra copper pipe with puf insulation, drain pipe, iron stands etc. complete all as specified and directed. |
| 27 | Supply and fix voltage stablizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V t0 250 V with output voltage stablized at 230 volt with accuracy +2.5 % and capacity 4KVA |
| 28 | Supply and fixing sheet metal enlosure single pole and neutral with two pin socket and earth plug complete with one MCB SP 240 volts 20 amps complete all as specified and directed by EIC. |
| 29 | M&L for sub main wiring with two runs of single core PVC insulated(FRLSH), unsheathed copper condutor, multi stranded cable of size 4.00 Sqmm 1100 volts grade drawn PVC concealed conduit of size19/20 mm (ISI marked) including PVC accessories complete with one run of 4.00 Sqmm single core copper conductormulti-stranded PVC insulated(FRLSH), unsheathed cable as earth wire continuity conductor including cutting, chasing and making good to disturbed surface etc. complete all as specified and directed by Engineer-in-Charge. Note : Three run of 4.00 Sqmm cableand one run of PVC Conduit shall be measured & paid as one unit.) |