| 1 | S/I/T/C of solar water heating system of 1000 LPD capacity in FPC (Presser modal) with hot water storage tank made of ss 304L grade sheet, thickness 2.5mm with stand of C channel and piping GI duly insulated with rock wool 50mmand cladding as per MNRE guidelines and ISO Certified (SITC of Flat plate Solar collector panels of size 2000mm x 1000mm x 100mm (or as per manufacturer`s standard) with extruded Aluminum frame, glazing 3.2 mm thick toughened and textured glass back sheet of luminum 25mm rockwool insulation at sides and 50mm rockwool/ pufinulation at bottom of 48 kg/cum density and K value between 0.028 to 0.033 W/mK Absorber will be of Cu copper) tubes type, of 2sqm area, Havin glaze /ultrasonic welded tube and fins arrangement, with Copper Tube Headers of dia 25.4 mm approx.) and 127 mm dia for riser tube with nos of riser tubes and absorber coating suitably selected Coating Absorptivity should be )90% and Coating Emissivity should be (20% with with brass flanges and EPDM rubber gaskets. The Collectors shall be placed with stands of size 32x 32 x 3mm thick Angles duly coated with included Civil work with all labour and material required to the complete in all respect up to entire satisfaction of the Engineer-in-Charge of the works) Make: /Solcrome / BHEL/ Alfa Solar |
| 2 | Supply and erection of cold water stoarge tank of 1000 LPD in four layer with stand of MS in height 7.8 ft. with (civil work for cold water storage tanke and hot water pipe line and for plant) complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make Sintex/ Ashirwad/ Sheetal |
| 3 | Supply and erection of 6 Sq. mm 4 core armoured aluminium cable on surface/ cable tray complete with necessary connections complete in all respect upto the entire satisfaction of Engineer in charge of the work (As per HSR 24.14.12). Make Polycab/ Havells/ RR Kabel |
| 4 | Supply and erection of 32 mm GI pipe B class for cold water complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Jindal/ Tata/Ravindra |
| 5 | Supply and erection of 25 mm GI pipe B class for hot water with 100mm Rockwood insulation complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Jindal/ Tata /Ravindra |
| 6 | Supply and erection of 20 mm GI pipe B class for hot water with 100mm Rockwood insulation complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Jindal/ Tata/Ravindra |
| 7 | Supply and erection of 15 mm GI pipe B class for hot water with 100mm Rockwood insulation complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Jindal/ Tata/Ravindra |
| 8 | Supply and erection of Gate valve in 32mm complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Zoloto/Sant/Jindal |
| 9 | Supply and erection of Gate valve in 25mm complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Zoloto/Sant/Jindal |
| 10 | Supply and erection of NRB 32mm complete in all respect upto the entire satisfaction of the Engineer-in-charge.Make Zoloto/Sant/Jindal |
| 11 | Supply and erection of Ball valve in 15mm complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Zoloto/Sant/Jindal |
| 12 | Supply and erection of temprature meter ISI approved for solar water heater complete in all respect upto the entire satisfaction of the Engineer-in-charge. |
| 13 | Supply and erection of electric Heater with thermostat 5 KW complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make Bajaj/ L&T/ Surya |
| 14 | Supply and erection of booster motor 1 HP complete in all respect upto the entire satisfaction of the Engineer-in-charge. Make CRI/Crompton/ Kirloskar |
| 15 | Supply and erection of CPVC pipe 25 mm dia complete with all labour and material required to complete job in all respect upto the entire satisfaction of the Engineer-in-charge. Make Ashirwad/Prince/ Supereme |
| 16 | Supply and erection of Hot water recirculation pump 0.5 HP for instant hot water in bathroom/ kitchen complete with all labour and material required to complete job in all respect upto the entire satisfaction of the Engineer-in-charge. Make CRI/Crompton/ Kirloskar |
| 17 | Supply and erection of Brass Tab for hot water complete with all labour and material required to complete job in all respect upto the entire satisfaction of the Engineer-in-charge. Make Roco/ Laxmi/Delta/ Liva |
| 18 | Supply and erection of Hot water re-circulation control panel and heating controlling with sensor features complete with all labour and material required to complete job in all respect upto the entire satisfaction of the Engineer-in-charge. Make Green Energy/ L&T/ Inter Solar |
| 19 | Supply and erection of PVC unsheathed copper conductor cable single core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe complete in all respect upto the entire satisfaction of Engineer in charge of the work 4.0 sq.mm |
| 20 | Supply and erection of miniature circuit Breaker/isolator 240/415 V in the existing distribution board including making necessary connections:-6 amp. to 32 amp Single Pole (As per HSR 23.22.5.1) |
| 21 | Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 125 to 160 amp, 25 KA (As per HSR 23.22.1.10) |
| 22 | Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to to the entire satisfaction of the Engineer-in-Charge of the work. Vertical TPN DB Double Door 4 way ( 8 incoming and 3phase*4 outgoing) (As per HSR 23.22.4.9) Please Enable Macros to View BoQ information |