| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in PVC casing caping with modular switch modular plates suitable size modular surface box of specified Category and earthing the point with 1.5 sq.mm FR PVC insulated copper conductor single core cable etc. as required.;(a) Group A -- with Cat A Modular Accessories |
| 2 | Wiring for 5A /15A plug with 2 x 4 sq.mm FR PVC insulated copper conductor single core cable in PVC casing capping alongwith 1 No 4 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor single core cable in the independent PVC casing capping of appropriate size as required.;(a) 2 x 1.5 sq.mm + 1 x 1.5 sq.mm earthwire (20mm casing ) |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor single core cable in the independent PVC casing capping of appropriate size as required.;(b) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earthwire (20mm casing ) |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor single core cable in the independent PVC casing capping of appropriate size as required.;(j) 4 x 6 sq.mm + 2 x 6 sq.mm earthwire (32mm casing ) |
| 6 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required;(a) Cat A |
| 7 | Supplying and fixing brass batten/ angle holder including connections etc as required. |
| 8 | Supplying and fixing following size modular PVC box alongwith modular base and cover plate for modulator switches in recess etc. as required;(a) 1 or 2 Module Cat A |
| 9 | Supplying and fixing suitable size modular PVC box with modular plate and cover in front on surface or in recess including providing and fixing 1 no 6 pin 15/16 A modular socket outlet and 1 nos 15/ 16 A modular switch connection painting etc. as required. ( For workstations);(a) Cat A |
| 10 | Supplying and fixing suitable size modular PVC box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 A modular socket outlet and 5/ 6 A modular switch connection painting etc. as required. |
| 11 | Supplying and fixing suitable size modular PVC box with modular plate and cover in front on surface or in recess including providing and fixing 4 nos 3 pin 5/6 A modular socket outlet and 4 nos 5/ 6 A modular switch connection painting etc. as required. The scope of work includes alternate arrangement if required as per site conditions to provide switches and sockets seperately above and below the table respectively. (For workstations);(a) Cat A |
| 12 | Supplying and fixing 3 pin 5/6 A modular socket outlet and 5/ 6 A modular switch on board the modular surface/recessed PVC/GI modular box by suitably increasing its modular capacity modular plate and cover including connection painting etc. as required.;(a) Cat A |
| 13 | Installation earthing testing and commissioning of pre-wired fluorescent fitting/ compact fluorescent fittings of all types complete with all accessories and tube etc. directly on ceiling / wall including connections with 1.5 sq .mm FRLS PVC insulated copper conductor single core cable and earthing etc. as required. |
| 14 | Installationearthing testing and commissioning of ceiling fan including wiring the down rod of standard length ( upto 30 cm) with 1.5 sq .mm FRFRLS PVC insulated copper conductor single core cable etc. as required. |
| 15 | Installation earthing testing and commissioning of exhaust fan upto 450 mm sweep in the existing opening including making the hole to suit the size of the above fan making good the damage connections testing commissioning etc as required |
| 16 | Supplying and fixing following way TPN sheet steel double door Verticle type MCB distribution board 415 V on surface/ recess complete with tinned copper busbar neutral busbar earth bar dinnbar detachable gland plate interconnections phosphotized and powder painted including earthing etc. as required ( but without MCB/RCCB/Isolator)interconnection between incomer MCB and busbars of following ways (but without MCBs as required);(a) 4 way (8+12) double door Vertical type Cat A |
| 17 | Supplying and fixing following way TPN sheet steel double door Verticle type MCB distribution board 415 V on surface/ recess complete with tinned copper busbar neutral busbar earth bar dinnbar detachable gland plate interconnections phosphotized and powder painted including earthing etc. as required ( but without MCB/RCCB/Isolator)interconnection between incomer MCB and busbars of following ways (but without MCBs as required);(b) 8 way (8+24) double door Vertical type Cat A |
| 18 | Supplying and fixing 50 A C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required.;(e) TPN Cat A |
| 19 | Supplying and fixing 63 A C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required.;(d) TP Cat A |
| 20 | Supplying and fixing 6 A to 32 A C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required.;(a) SP Cat A |
| 21 | Supply and erecting meter box suitable for three phase energy meter and incoming SP/DP MCB fabricated out of 16 SWG sheet steel powder coated complete as required and conforming to the requirements of Goa Electricity Department. |
| 22 | Supply installation testing and commissioning of electronic type three phase energy meter (KWh) 4 wire ISI marked in polycarbonate or sgheet steel body ( base mounting type) with counter display/LCD display with ELT in Class 1.0 50 Hz 240 V. AC duly tested by MRT along with Test Certificates complete as required of following capacity of make L & T only.;(b) 10 to 40 A |
| 23 | Earthing with GI earth pipe 2 mts long 40 mm dia medium class with ISI markof approved brands including accessories and providing masonry enclosure with CI/RCC cover having locking /lifting arrangement and watering pipe etc. with charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 2.0 mtrs(min) and disposal of excavated soil. b) Class B GI pipe 40mm diameter as per specifications. c) Charcoal/salt as per specs ( paid seperately). d) Refilling the pit of size 1.0x1.0x 2.0 mtrs(min) with soft black soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe. g)watering arrangement(plumbing will be paid seperately).;(b) In rocky strata |
| 24 | Extra for using salt and charcoal for pipe earth electrode as required( 65 Kgs of Charcoal and 5 Kgs of Salt). |
| 25 | Providing and fixing 4 mm dia copper wire on surface or in recess for loop arthing . as required |
| 26 | Providing and laying earth connection from earth lectrode with4 mm dia copper wire in 15 mm dia GI pipe from earth electrode as required |
| 27 | Supply of 4 core unarmoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) IS:7098(Part I) with latest amendments of following size.;4 Core 10 sq.mm |
| 28 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm on surface etc. complete as required |
| 29 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Inchargesand cushioning with screened sand bed of 20mm thick protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(a) In soily strata |
| 30 | Supply and erecting of 48 inch (1200mm sweep) ceiling fan double ball bearing type complete with all accessories.;(a) Cat A |
| 31 | (c) For 6 inches rafter size |
| 32 | Supply and erecting of 9 inch (225 mm sweep) exhaust fan with double ball bearings 1400 rpm complete with all accessories.;(a) Cat A |
| 33 | Supplying and fixing call bell/ buzzer suitable for single phase 230 V complete as required.;(a) Ding Dong Bell |
| 34 | Supply of 4 feet 20 W single box/batten industrial type LED luminaire with CRCA body pre coated in white and pre wired for LED type complet with all accessories of make Crompton , model no IGP 131LT8-16 or Havells bearing Cat No. LHFYBYPNIA1W022/ Bajaj Bearing Cat No.BLRB-DB 118/Wipro bearing Cat No WIO 921208 or any approved brand including 1 No of of 4 feet 20 W LED tube of make crompton bearing Cat No. LTT8-20/Bajaj bearing Cat No.BLRB 18W CWc /Havells bearing Cat No.LHLDCLXUL8X020 or Wipro bearing Cat No. LL13-181-650 as required.( Equivalent to be approved by Engineer in charge). The LED tube should have a warranty of two years from the date of commissioning. |
| 35 | Supply and fixing of 15 Watts B22 base LED Lamp of approved make having two years warranty. |
| 36 | Dismantling of light point, fan points, submain wiring and all electrical accessories including M.S. main board, D B, main switch board, light points, PVC pipes etc and making good the surface,plastering and painting the patch work to maintain the shade etc, complete as required and as directed by Engineer in Charge. |
| 37 | Supplying and fixing 20 A 240 V SPN industrial type socket outlet with 2 pole and earth metal enclosed plug top alon with 20 A C series SP MCB in sheet steel enclosure in surface or in recess with chained metal cover for the socket outlet and complete with connections testing and commissioning etc. as required\";(a) Cat A\" |
| 38 | Supply and fixing of Wall mounted fan of 400 mm sweep with speed of minimum 1350 rpm of make Crompton model SDX Black Gold or equivalent in Havells, Orient as approved by Engineer in Charge. |
| 39 | S.I.T.C of LED Flood light Fixtures 50W or above with its accessories and fitment/mounting the same as per required site conditions with proper finishing etc, of make hovels model JETALEGANZAFLS 50WLEDD730P60DTOTG, HSN code 9405/ Crompton Model CFS-504-50-57-60D-SL-GL-NSG/Bajaj Model Glatt MT 60L WH PO PC SD or Equivalent in recognized / ISO certified brands only & to be approved by Engineer in charge Please Enable Macros to View BoQ information |