| 1 | Taking down existing old unserviceable LT Panel board with all accessories and Supply, installing, erecting, commissioning and testing newfactory made LT panel board, 415 Volts, 3 Phase & 4wire system, cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable alley protected with bakelite sheet between bus bar & cable alley with front side shutters with locking arrangement, including TPN Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating not less then 1.5 times the rated capacity of the incomer ACB/MCCB and bus barchamber covered both side using bakelite sheet partition and wire mesh to the back side of cable alley for the protection purpose . All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IEC: 61439/2011Part-1 andpart -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job. The TPN bus bar shall be mounted on F class insulators with intervals not more then 500 mm.All control wiring shall be with FRLS PVC insulated 2.5 sqmm multi-stranded copper conductor and shall be properly bunched. The panel board shall have bottom channel of size 75 x 40 mm properly welded with 45 CM long 04 legs of angle iron 50x50x6 mm using 3 mm thick CRCA sheet corners to all legs and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of Aluminum lugs and suitable size of chrome plated brass double compression glands provided for incoming and out-going cables comprising the following :- Make of ACB/ MCCB/MCB/Change over switch: L&T/ABB/LEGRAND/SCHNIEDER/SIEMENS |
| 2 | INCOMING MCCBa) 250 Amp 4 pole MCCB 36 KA breaking capacity with adjustable thermal magnetic setting with earth fault protection and rotary handleIcs= 100% Icu-01 Nos. OUTGOING MCCBa) 100 Amp 4 pole MCCB 25 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 02 Nos. b) 63 Amp 4 pole MCCB 16 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 03 Nos. c) Space for spare MCCB- 01 No.Metering:a) AC digital voltmeter 0-500 volts Size 4\"X4\"with 3 Ph selector switch-01 Nosb) 0-500 digital Amp meter with suitable Size 4\"X4\" with 3 Ph selector switch- 01 No..c) LED Indicating lamps RYB set of three -01 SetsNote: (a) Cable entry should be incoming/ out going from separate cable gallery.(b) All incoming/outgoing MCCBs shall be provided with suitable size of copper connection plates.(c) All incoming/outgoing MCCBs shall be provided with suitable spreader links – 04 Nos.(d) Provision of gland hole, brass glands and heat shrinkable end joints of all incoming and out going cables all as directed.(e) All incoming/outgoing MCCBs should be marking label/end plate/end clams/ suitable size of terminal block stud/screw less type etc.(f) Main bus bar/ link bus bar should be full covered including back side |
| 3 | Taking down existing old unserviceable LT Panel board with all accessories and Supply, installing, erecting, commissioning and testing newfactory made LT panel board, 415 Volts, 3 Phase & 4wire system, cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable alley protected with bakelite sheet between bus bar & cable alley with front side shutters with locking arrangement, including TPN Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating not less then 1.5 times the rated capacity of the incomer ACB/MCCB and bus barchamber covered both side using bakelite sheet partition and wire mesh to the back side of cable alley for the protection purpose . All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IEC: 61439/2011Part-1 andpart -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job. The TPN bus bar shall be mounted on F class insulators with intervals not more then 500 mm.All control wiring shall be with FRLS PVC insulated 2.5 sqmm multi-stranded copper conductor and shall be properly bunched. The panel board shall have bottom channel of size 75 x 40 mm properly welded with 45 CM long 04 legs of angle iron 50x50x6 mm using 3 mm thick CRCA sheet corners to all legs and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of Aluminum lugs and suitable size of chrome plated brass double compression glands provided for incoming and out-going cables comprising the following :- Make of ACB/ MCCB/MCB/Change over switch: L&T/ABB/LEGRAND/SCHNIEDER/SIEMENS |
| 4 | INCOMING MCCBa) 400 Amp 4 pole MCCB 50 KA breaking capacity with adjustable thermal magnetic setting with earth fault protection and rotary handleIcs= 100% Icu-01 Nos. OUTGOING MCCBa) 250 Amp 4 pole MCCB 25 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 01 Nos. b) 160 Amp 4 pole MCCB 25 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 02 Nos. c)100 Amp 4 pole MCCB 16 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 02Nosd) 63 Amp 4 pole MCCB 16 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 1 Nos.e) Space for spare MCCB- 01 No.Metering:a) AC digital voltmeter 0-500 volts Size 4\"X4\"with 3 Ph selector switch-01 Nosb) 0-500 digital Amp meter with suitable Size 4\"X4\" with 3 Ph selector switch- 01 No..c) LED Indicating lamps RYB set of three -01 SetsNote: (a) Cable entry should be incoming/ out going from separate cable gallery.(b) All incoming/outgoing MCCBs shall be provided with suitable size of copper connection plates.(c) All incoming/outgoing MCCBs shall be provided with suitable spreader links – 04 Nos.(d) Provision of gland hole, brass glands and heat shrinkable end joints of all incoming and out going cables all as directed.(e) All incoming/outgoing MCCBs should be marking label/end plate/end clams/ suitable size of terminal block stud/screw less type etc.(f) Main bus bar/ link bus bar should be full covered including back side |
| 5 | Taking down existing old unserviceable LT Panel board with all accessories and Supply, installing, erecting, commissioning and testing newfactory made LT panel board, 415 Volts, 3 Phase & 4wire system, cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable alley protected with bakelite sheet between bus bar & cable alley with front side shutters with locking arrangement, including TPN Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating not less then 1.5 times the rated capacity of the incomer ACB/MCCB and bus barchamber covered both side using bakelite sheet partition and wire mesh to the back side of cable alley for the protection purpose . All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IEC: 61439/2011Part-1 andpart -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job. The TPN bus bar shall be mounted on F class insulators with intervals not more then 500 mm.All control wiring shall be with FRLS PVC insulated 2.5 sqmm multi-stranded copper conductor and shall be properly bunched. The panel board shall have bottom channel of size 75 x 40 mm properly welded with 45 CM long 04 legs of angle iron 50x50x6 mm using 3 mm thick CRCA sheet corners to all legs and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of Aluminum lugs and suitable size of chrome plated brass double compression glands provided for incoming and out-going cables comprising the following :- Make of ACB/ MCCB/MCB/Change over switch: L&T/ABB/LEGRAND/SCHNIEDER/SIEMENS |
| 6 | INCOMING MCCBa) 800 Amp 4 pole ACB 50 KA breaking capacity with adjustable thermal magnetic setting with earth fault protection and rotary handleIcs= 100% Icu-01 Nos. OUTGOING MCCBa) 400 Amp 4 pole MCCB 50KA KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 01 Nos. b) 250 Amp 4 pole MCCB 36 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 03 Nos. c) 200 Amp 4 pole MCCB 25 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 02 Nosd) 100 Amp 4 pole MCCB 25 KA breaking capacity with adjustable thermal magnetic setting with rotary handle Ics= 100% Icu - 01 Nose) Space for spare MCCB- 01 No.Metering:a) AC digital voltmeter 0-500 volts Size 4\"X4\"with 3 Ph selector switch-01 Nosb) 0-500 digital Amp meter with suitable Size 4\"X4\" with 3 Ph selector switch- 01 No..c) LED Indicating lamps RYB set of three -01 SetsNote: (a) Cable entry should be incoming/ out going from separate cable gallery.(b) All incoming/outgoing MCCBs shall be provided with suitable size of copper connection plates.(c) All incoming/outgoing MCCBs shall be provided with suitable spreader links – 04 Nos.(d) Provision of gland hole, brass glands and heat shrinkable end joints of all incoming and out going cables all as directed.(e) All incoming/outgoing MCCBs should be marking label/end plate/end clams/ suitable size of terminal block stud/screw less type etc.(f) Main bus bar/ link bus bar should be full covered including back side |
| 7 | Supplying & fixing in replacement of energy-efficient 60-watt LED street light fitting with pressure die-cast aluminum housing, IP65/IP66 protection, and suitable for operation on 120V– 270V AC, 50Hz. The luminaire should include high-power LEDs with suitable optics for road illumination, inbuilt electronic driver, and surge protection (minimum 10kV). The fitting shall be mounted on existing 9 mtr pole arms using standard clamps, nuts, bolts, and wiring connections, including all materials, labour, T&P, complete all as specified and directed.MAKE -Philips, Bajaj,Havells, Crompton. |
| 8 | Supplying & fixing in replacement of energy-efficient 70watt LED street light fitting with pressure die-cast aluminum housing, IP65/IP66 protection, and suitable for operation on 120V– 270V AC, 50Hz. The luminaire should include high-power LEDs with suitable optics for road illumination, inbuilt electronic driver, and surge protection (minimum 10kV). The fitting shall be mounted on existing 9 mtr pole arms using standard clamps, nuts, bolts, and wiring connections, including all materials, labour, T&P, and all as specified and directed.MAKE -Philips, Bajaj,Havells, Crompton. |
| 9 | Supply and fixing in reolacement of post top lantern LED type 60 watt 230 watt volts AC outdoor type with Decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 10 | M & L for preparation of steel surface of electric pole upto 11 Mtr longextension portion, apply one coat of aluminum paint over full length and marking of pole number and five strips as per approved colour by the departmetnusing synthetic enamel paint all as per existing complete all as specified and directed. |
| 11 | S&F street light brackets suitable for mounting on existing or new poles, made from 40 mm galvanized mild steel pipe/conforming to IS standards. The bracket shall be of single arm design, 1.0 to 1.5 meter in length, with appropriate bend (typically 105° to 120°), including necessary clamps, bolts, nuts, and washers for secure installation on the pole. The bracket shall be duly painted (if not galvanized) with corrosion-resistant paintcomplete all as specified and directed. |
| 12 | Supply, installing, erecting, commissioning and testing newfactory made Bus Bar panel board cubical out door type of size 1.00 MtrX 0.750mtrX0.600mtrfor housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 60 cm legs &bottom channel of size 75 x 40 mmfor 433 volts, 3 phase, 4 wire systemincluding TPN Aluminium bus bar of rating400A, 4PoleThe TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators complete all as specified and directed. Note : Bus bar should be fixed on PCC and its rate included in quoted rate. |
| 13 | Supply, installing, erecting, commissioning and testing newfactory made Bus Bar panel board cubical out door type of size 0.750 MtrX 0.600mtrX0.500mtr for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 60 cm legs &bottom channel of size 75 x 40 mmfor 433 volts, 3 phase, 4 wire systemincluding TPN Aluminium bus bar of rating250A, 4PoleThe TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators complete all as specified and directed.Note : Bus bar should be fixed on PCC and its rate included in quoted rate. |
| 14 | Supplying & fixing in replacement of high-performance 120-watt LED flood light fitting, suitable for outdoor installation on poles or high masts. The luminaire shall be constructed from pressure die-cast aluminum housing with efficient heat dissipation fins, equipped with high-power LEDs and precision optics/lens for wide and uniform light distribution. The unit shall have IP66 ingress protection, inbuilt high-efficiency electronic driver, and minimum 10kV surge protection. It shall operate on 140–270V AC, 50Hz supply. The fitting shall be mounted securely on pole brackets or high mast arms using appropriate clamps, bolts, nuts, and wiring. all civil, electrical, and mechanical works required for the complete installation shall be included in the item rate complete all as specified and directed. |
| 15 | Supply and fixing in replacement of nature switch complete with timer (swadeep) contactor, relays and suitable rating MCBs for incoming and out goingin buil in suitable IP 66 enclosure of three phase integrated models of capacity 8 KW to 10 KW complete all as specified and directed. (Make- Swadeep Cat Part no-Sugam 66-8kW3P/abb/Siemens0 |
| 16 | Supply and fixing in replacement of nature switch complete with timer (swadeep) contactor, relays and suitable rating MCBs for incoming and out goingin buil in suitable IP 66 enclosure of single phase integrated models of capacity 8 KW to 10 KW complete all as specified and directed (Make- Swadeep Cat Part no-Sugam 66-8kW3P/abb/Siemens. |
| 17 | S & fixing in replacement 1100 volts grade heavy duty PVC insulated aluminium conductor, bedded unarmoured cable of size 4 Sqmm 2 core fixed on wall/floor/poles including 15mm PVCpipe with clamps complete all as specified and directed . |
| 18 | S & fixing in replacement 1100 volts grade heavy duty PVC insulated aluminium conductor, bedded unarmoured cable of size 10 Sqmm 2 core fixed on wall/floor/poles complete all as specified and directed. |
| 19 | Excavation in trenches in soft/loose soil n.exc 1.5m wide and n. exc 1.5m depth for laying of cable, errection of poles, stay andpipe line,and getting out complete all as specified and directed |
| 20 | Returning & filling including spreading, leveling watering and well ramming in layers not exc 25 cm thick in any type of soil complete all as specified and directed. |
| 21 | Removal of excavated soil to a distance not exc 50 m above the starting point complete all as specified and directed. |
| 22 | Supply & laying double walled corrugated (DWC) HDPEfull rounded pipe in 6 m lenght conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 75 mm outer dia and 63 mm inner dia complete all as specified and directed. |
| 23 | Supply & laying double walled corrugated (DWC) HDPEfull rounded pipe in 6 m lenght conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 63 mm outer dia and 50 mm inner dia complete all as specified and directed. |
| 24 | S&L XLPE LT UG cable PVC insulated, beddedarmoured heavy duty electric cable 1100 volts grade with aluminum conductor of of cable 16 Sqmm 4 Core, including taking down the unserviceable UG cablecomplete all as specified and directed. |
| 25 | S&L XLPE LT UG cable PVC insulated, beddedarmoured heavy duty electric cable 1100 volts grade with aluminum conductor of of cable 25 Sqmm 4 Core, including taking down the unserviceable UG cable complete all as specified and directed. |
| 26 | S&L XLPE LT UG cable PVC insulated, beddedarmoured heavy duty electric cable 1100 volts grade with aluminum conductor of of cable 95 Sqmm 3.5 Core, including taking down the unserviceable UG cablecomplete all as specified and directed. |