Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Supply , installation, testing and commissioning including transportation at site , transformer step down out door type copper wound complete with standard fitting , LT 433 volt 3 phase 4 wire 50c/s outgoing and HT 11 kV 3 phase, incoming oil immersed naturally oil cooled 315 KVA capacity complete with first filling of adequate transformer oil with tap changing arrangement on HT side to varry secondary voltage +/- 2.5%,+/-5% and +/-7.5% complete with off load circuit taping switch drain valve diagram plate jointing material, connection etc along with fittings complete with Energy efficient level -3 as per IS-1180 part-1:2014 with amendment No 4 and BEE certified including 10% extra oil and Rail section, channel embeddedin foundation of suitable size in and including PCC (1:3:6) type C- 1 plateform of size not less than 2.0 X 2.0 X 1.2 M and necessary earth work and excavation as direct or as per manufacturer recommendation complete all as specified & as directed. |
| 2 | Excavation intrenches in soft/loose soil not exceeding 1.5 mtrdeep and not exceeding 1.5 mtrwide for fdn, laying of cable and erection of poles etc all as specified and directed at site. |
| 3 | Excavation intrenches in soft/loose soilexceeding 1.5 mtrdeepbut not exceeding 3 mtr for erection of polesall as specified and directed at site. |
| 4 | Removing excavated material n.exceeding50 m and depositing at a level n.exc 1.5 mabove the starting point all as specified & directed by Engineer-in - Charge. |
| 5 | Returning, filling in including spreading, leveling, watering and well ramming excavated soft/loose soilin layers , all as specified and directed at site |
| 6 | M&L for sand cushioning to under ground cable using locally available fine clean dry river sand over,under ground UG cable laid in treches and gently punning to cushioning to cable complete all as directed by Engineer-in-Charge. Note : For the purpose of payment only punned thickness will be measured. |
| 7 | M&L for HV cover to HTunderground cables class HV, Type 1, flat, size 300mm x l80mm x 40 mm laid dry and flat abutting each other with gaps not exceeding 10mm complete all as specified and directed. |
| 8 | M&L for brick protection cover of size 230x115x75 mm to LT underground cables with sub class \"B\" over burnt brick, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10mm complete all as specified and directed. |
| 9 | M&L Plain cement concrete 1:2:4, type B-1( using 20mm graded crushed stone aggregate ) as in lintels upto 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, coping, bed plates and the like including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified. |
| 10 | M & L for plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation of pole / strut etc including necessary form work all as specified and directed by Engineer-in-Charge. |
| 11 | Boring/Drilling (horizontally) manually under min 0.5 to 2 m deep in soilbelow existing road suitable for passing GI tubing of 40 to 80 mm bore complete all as specified. |
| 12 | Supply and fixing of GI tubing light grade 80mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor /wallcomplete all as specified and directed . |
| 13 | Supply, transportation, fixing and erection of steel tubular sewaged pole 11 mtr long complete with MS base plate ,finial taper plug nut bolts,screws as specified type 410 SP-55 as per relevant IS specification including two coats of aluminium paint over a coat of red oxide primerand including making alternate red and black strips 30 cm height (Total 5 Nos ) complete all as specified and directed.(Excavation and PCC will be measured and paid seprately.) |
| 14 | Supply and fixing of Switch air break, gang operated triple pole mechanically operated mounted on with 9 insulator and steel frame with operating mechanism working from ground level current rating upto 400A, 11000 V grade having nine insulators, vertical type complete all as specified and as directed. |
| 15 | Supply and fixing of expulsion drop out fuse carrier assembly outdoor & channel type 400 Amps capacityand insulators suitable for HT 11 KV complete all as specified and as directed. |
| 16 | Supply and fix of lightening arrester station type rated frequency 50 Hz nominal discharge current 65 kA and suitable for 11 KV complete all as specified and as directed. |
| 17 | Supplyfabricate , fixing structural mild steel RS joist , channelangle iron, flat iron and brackets etc for fabrication of cross arms, bracing supports clamps including D clamps, eye hook and back plate etc fabricated from structural steel section includingnuts , bolts, washers, welding (cold and hot ) drilling holes for bolts, bend to any shape or size as indicated and directed , inclusive of one primer coat and two coats of aluminium paint after preparation of surfaces complete all as specified and directed . |
| 18 | Supply and fixing of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and as directed. |
| 19 | Supply and fixing of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20 cm size complete all as specified and as directed. |
| 20 | M&L for anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered (clamps measured separately) complete all specified and as directed. |
| 21 | M&L for Earthing complete with galvanized steel earth plate electrode 60cm x 60cmx 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the earth plate not less than 1.5 meter below normal ground level connected to galvanized iron strip 32 x 6mm as earthing lead by means of bolt and nut, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 5 of MES Schedule part I with and including excavation & earth work in any type of soil, providing charcoal dust and common salt upto 15 cm above top edge of earth plate, construction of PCC pit in cement concrete 1:3:6 type C-1 with 40 mm thick RCC 1:2:4 type B-1 reinforced with 8 mm dia MS deformed bars @ 100mm center to center both ways watering arrangement with funnel and wire mesh and watering pipe of 20mm dia GI medium grade and 40mm dia medium grade pipe for earth lead protection and testing on completion complete all as specified and directed. |
| 22 | M&L for Earthing complete with copper earth plate electrode 60cm x 60cmx 3.15 mm thick electrode buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the earth plate not less than 1.5 meter below normal ground level connected to copper strip 20 x 3 mm as earthing lead by means of bolt and nut, check nuts and washers of brass material all as shown in electrical plate No 3 of MES Schedule part I with and including excavation & earth work in any type of soil, providing charcoal dust and common salt upto 15 cm above top edge of earth plate, construction of PCC pit in cement concrete 1:3:6 type C-1 with 40 mm thick RCC 1:2:4 type B-1 reinforced with 8 mm dia MS deformed bars @ 100mm center to center both ways watering arrangement with funnel and wire mesh and watering pipe of 20mm dia GI light grade and 40mm dia medium grade pipe for earth lead protection and testing on completion complete all as specified and directed. |
| 23 | Supply, laying & testingcable XLPE insulated, screened, PVC bedded, galvanizedsteel strip or wire armoured, electric power cables(heavy duty) with stranded aluminium conductor,11000 volts grade, of size 3 core95 sq mm. |
| 24 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size following size :- |
| 25 | 300 sq mm 3.5 core |
| 26 | 240 sqmm 3. core |
| 27 | 150 sq mm 3.5 core |
| 28 | 95 sq mm 3.5 core |
| 29 | Supply, installaing, testing & commissioning of factory made (CPRI Approved) LT indoor Panel ,AC, 415 volt, 50 Hz,3 Phase,4 wire of size not less than 1500mmx1200mmx400mm designed following form 4b separator panel rules for protection from interior live components,totally enclosed self supporting structure/cubical openable at the front & back,with bottom cable entry and exit; structure made out of 2 mm thick CRCA steel sheet with U channel Iron base of ISA-75x40x5 mm.The components doors should be provided with the name plates giving feeder description for permanent identification.All doors must be provided with Tri functional (Functional as a sealant,elastic in nature and non water absorbent) gasket to make the panel dust and vermin proof.All doors must be welded at the joints and should have smooth corner bends.Fan filters/outlet filters with hood must be provided at the ventilation.Cable alley should be provided for all outgoing connections accessories prewired with suitable size FRLSH PVC insulated multistranded copper conductor of 10 sqmm.Wiring should be complete with sockets and ferrule marking for every cnnection.Brass glands should be provided at the inlet and outlet cable points.Danger board on front and rear sides of the panel should be provided.Structure painted with textured powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system.All MCCB panels must have exhaust fans of diameter 6 inches on both sides for proper ventilation.Test certifaicate of every switchgears must be provided and internal wiring of suitable size to be used for incoming & outgoing connection of all switches/MCCB\"s and bus bar.The aluminium bus bars of capacity 600 Amps shall be insulated with color coded heat shrinkable incl necessary preparation of surface externally & internally and providing PCC (1:3:6) type C-2 as in foundation all as specified & as directed complete all specifeid & as directed with comprising of the following:- |
| 30 | Aluminium busbar 600 Amps rated capacity-04 Nos. |
| 31 | 400A 4P 50 KA MCCB with O/L, S/C adjustable Thermal & adjustable Magnetic Release-03 Nos |
| 32 | MCCB Extended Rotary Handle-03 Nos |
| 33 | Spreader Link-06 Sets |
| 34 | MCCB Aux+Trip Unit-03 Nos |
| 35 | R,Y,B,On,Off,Tripindicator lamps LED-03 (Set of 3) |
| 36 | LED multifunction meter with CT\"s -03 Nos |
| 37 | Fuse/ MCB 6A SPfor meter Protection-06 Nos |
| 38 | Fine wiring with single core copper conductor cable for indicating lamps-01 Job |
| 39 | Manual Changeover Switches,I-O-IIoperation supplied with bridging bars,extended shaft and IP-65 protection with pistol type handle of rating 400 Amps 4 pole fixed in open execution .Make : ABB Cat No OT200E04CP/Havells/Legrand - - 03 Nos |
| 40 | Supply , installation, commissioning and testing of Factory assembled DG Set with( CPCB-4+ Version ) engine Silent type built in within an acoustic enclosure Diesel Enginedriven Generating set water cooled including AMF panel for standby power supply 415 volts, 3 Phase, 4 wire, 50 cycles / sec,0.8 power factor, 320 KVA (256 KW) or next higher standard size available KVA,1500 RPM. Self exicited self regulated brushless AC generator installed. The alternator directly coupled to diesel engine and engine developing 390 BHP at 1500 RPM, mounted on common base frame & complete with self starter 24 volt. Acoustic enclosure suitable for ambient condition at Siliguri area and confirming to condition under IS 10002, 13364 Part I 1992, BS 5514/5000to meet exhaust emission test as per revised MoEF norms/as per CPCB. Fuel tank capacity not less than 08 hours fuel requirement & battery as reccommended by OEMwith battery leads, sound proof canopy etc. with features for automatic shutdown in the event ofa circuit failure condition arising from low oil pressure, high coolant temperature, over speed etc. & microprocessor based gen-set controller governor with the following under-mentioned features & all as specified & as directed :-Note :- The capacity of Generator set shall be net after all due derating factors as per relevant IS/BS Standards design.(A)Alternator :-Standard design alternator rated at 320 KVA nearest higher available capacityat 0.8 (lag) power factor AC,3 - phase 4 - wire, 415 volts, 50 Hz, 1500 RPM, self exicited self regulated screen protected drip proofbrushless design with winding in pole faces, insulating class \"H\" and voltage regulation of+ 1% at rated voltage from no load to full load. The alternator shall be confirming to BS 5000, IS: 13364 Part I (1992) and shall be in position to generate supply with frequecy regulation with in + 1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS - 2613/5000/ IS - 4722.(i) Insualation class - \"H\"(ii) Temparature rise Class - \"H\"(iii) Excitation : Self Excited(iv) Regulation performance: The voltage is kept constant with + 1%.(v) Frequency regulation + 1% |
| 41 | (B) Diesel Engine: - Adequate capacity of Diesel enginewater cooled to drive independently above alternator and after considering de-rating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylindermulti stroke direct injection,cold starting 1500 RPM, as per relevant IS/BS complete, with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under:- (i) Fly wheel with housing(ii)Cooling system :- Closed circuit engine cooling with water pump , pusher fan and radiator with fan & belts.(iii) Cooling Water pump : - Centrifugal type belt driven. (iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe medium grade. MS Exhaust pipe with bends/flanges and all accessories to be supplied and erected as per OEM recommendation. The Exhaust Pipe shall be insulated with low resin bounded wool of min 75 mm thickness min 144 Kg/m density. The dia/thickness and Stack height of the Exhaust pipe shall be as per OEM recommendation and CPCB norms. The minimum height of Stack to be provided with each gererator set shall be worked outas per CPCB norms.(a)Turbo charger type(b)Exhaust manifold(c ) Silencer : Residential type(v) Fuel System :- Diesel Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governer electronic operated/ (as recommended by OEM) for 1% speed /frequency regulation. Comprising with Fuel Filters and Fuel Hoses.(vi) Lub oil System :-Comprising of Lubricating oil filter, Lubricating oil pump etc.(vii) Air Intake System :- Air intake Manifold, Air cleaner dry type etc(viii) Governer: Electronic type(ix) Starting System :- Electric Self starter with and including battery charging alternator 24 Volts DC. |
| 42 | (x) Batteries :- Batteries of maintenance free of capacity 12 V, 180 AH- 02 Nos complete with copper conductor multistranded leads of suitable length fromself starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified.(a) Start and stop push button(b)Ignition key / Switch(c )Radiator with blower fan & first fill of coolant oil(d)Corrosion inhibitor coolant(xi) Generator Monitoring Panel : - Comprising of all standard items as per standard manufacturing, iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant temperature indicator, Battery volt display in digital mode. (xii) Safety Controls : - Engine low lube oil pressure, high water temperature and over speeding of engine. (xiii) Coupling arrangement : - Flexible coupling(xiv) Accessories :- AVM Pads built- in or separetely mounted to manufactrer base frames.(xv) Base Frame : - Made out of ISMC of sturdy design made of MS channel with necessary reinforcement and predetermined holes as per manufacturer.(xvi) Fuel Tank :- Daily service fuel tank made complete on a common base inside the acoustic enclosure as per manufacturer guidelines for min 8 hrs continuous operation.(xvii) MS/Steel flexible pipe line to and from the fuel tank to the DG Set.(xviii) Battery Charger shall be provided as per manufacturer guidelines.(xix)The DG Set shall comply to the emission limits requirement as per Govt of India,The DG Set shall be complied with all test requirements as stipulated in the gazette notification. All relevant test results from NABL accredited lab shall be produced. |
| 43 | (C) AMF Panel :- Factory madecontrol cubical made out of 2mm thick CRCA sheet dust and vermin proof totally encosed with front and rear opening of 415 volts 3 -phase4 - wire AC 50 Hz, including powder coated painted, copper bus bar of one and half times the rated load of 320 KVA alternator complete with internal wiring with PVC insulated single core copper condutor multistranded wire of 1100 volts grade of suitable capacity, fuses, name plates consisting of 4 pole ACB/MCCBs and Contactors. The size / rating of all the connected accessories viz. Contactors, relays, timers, bus-bars, connecting cables etc. of the AMF Panel shall be in conformity with the I/C and O/G ACBs/MCCBs and as recommended by the manufacturer. Detachable cable gland plates, all controls, indicators and standard fitting shall be as per OEM recommendation. (i) Multifunction meter 4410 LED meter Cl 1 with RS485 Make : L&T catpart No WL441011OOOO or equvalent cat part No. of Make Havells India Ltd./ HPL India Ltd. / AE/ Schneider/ BCH/ techno commercially equivalent.(ii)Controls and Records:-(a) Load on Indication(b) Load off indication(c) Engine start push button(d) Engine stop push button(e) Fault accept / reset push button(f) Battery Charger shall be provided as per manufacturer guidelines(g) Suitable to provide a record of most recent fault conditions & fault history.(h) Complete alternator data viz, voltage ph - ph, ph - neutral, KVA , frequency etc.(j)Complete engine data viz, starting battery voltage, engine temp, engine runnning hours, engine oil pressure etc.(k)Control incl provn of service adjustment & calibration of DG control functions. |
| 44 | (D) Civil Works :-All civil works including PCC plat form and related foundations including for panel and equipments including making good of distrubed area during installation and commissioning of genset. The depth and size of the foundation and PCC as recommended by the manufacturer.(Note: The Contractor shall arrange for artifial resistive load for testng DG Set at site and the cost is deemed to be included in the above offer). (E) Acoustic Enclosure:- Manufactured by OEM suitable for 320 KVA DG Set. (i) Tested by NABL approved lab as per CPCB, (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating setbattery should be inside the enclosure.(iv) Fuel tank should be inside the enclosure, however, the fuel storage shall be enough for 8 hrs continuous operation.(v) Construction Details/specification are as follows : -(a)Outer body :- CRCA Sheet ofand thickness as per OEM recommendation.(b) Doors :- CRCA Sheet ofand thickness as per OEM recommendation.(c) Sound Insulation :- 100 mm thick rock wool (minimum density 64kg/Cum)/ fire resistance foam/puff as per OEM/ as per standard manufacturing to achieve desired decibel level(vi) The acoustic should be composite in construction and fully assembled integral unit.(vii) The DG Set should be provided with external Emergency stop push button.(viii) The enclosure should be suitably internally illuminated by LED Lamp fittings.(ix) The noise level should be 75 dB at 1m under free field conditions.(x) The acoustic enclosure parts shall be of powder coated after pre treatment process.The base frame should be painted with epoxy based black shade.Make :(i) Engine : Cummins/Kirloskar/Ashok Leyland/Greaves/Mahindra and Mahindra. (ii)Alternator : Stamford/ Kirloskar/Ashok Leyland/Crompton)(iii) MCCB: Legrand/ L&T/Siemens/Schneider/ GE/C&S |
| 45 | (iv) Battery:Exide/Amco/Nicco/ Amaron/ techno commercially equivalent.(v) Battery Charger:Escorp/Su-Kam/Microtek / techno commercially equivalent.(vi) Single Phase Preventor / Contactors /Relay: ABB/ BCH/ L&T/ Siemens /C&S Electric Ltd / Schneider (vii) Indicator Lamp / Selector Switch:L&T /Siemens/ GE/ RR Micro/ BCH /Schneider. (viii) Voltmeter / Ammeter:Havells India Ltd./ HPL India Ltd./ L&T/ AE/ Schneider/ BCH Display digital preferred.Note :- (i)The complete DG shall be procured form authorised OEM/Dealer/ Supplyer . Design/ Drawing of the AMF Panel and DG Set showing the dimensions is to be obtained from OEM/ Auth supplier and shall be got approved from the Dept before placing final order to the manufacturer. Desired inside temparature s of acoustic enclosure, if required shalll be provided as per OEM/ recommendation.(ii) The quoted rate shall be deemed to be inclusive of 12 hours test run at site as specified in PS and IS requirements in presence of IEM of HQ Zone, all testing arrangements/ equipments shall be made available by the contractor for tests.(iii) The quoted rate shll be deemed to be inclusive of first fill of lubricant oil. DHPP for 12 hours testing and final successful acceptance test.(iv) Necessary PCC foundation/ plinth shall be as per the recommendations of OEM and cost of the same is deeemed to be included in the quoted rates.(v) Anything missed out above but technically required for efficient working of DG Set is deemed to be included in quoted rates |
| 46 | Supply and fixing GI strip 32x6 mm buried ground with necessary nut and bolt etc for connection with existing Earting pit and electrical equipment complete all specified and directed by Engr-in-Charge. |
| 47 | Supply and fixing of GI pipe light garde of size 40 mm dia complete for protection of earth lead strip complete all as specified and as dircted. |
| 48 | Supply, installation, testing and commissioningof Panel board not less than 1.8m x 1.5 m x0.60 m ,outdoor cubical type factory made (CPRI approved) ,double door , front& back both side openable type fixed with Butt Hinges and locking arrangement with Aldrop latches , fabricated of CRCA sheet , inner sheet 2.0 mm thick hinged type door for individual MCCBs and outer door 3.15 mm thick,rubberised gasket, supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 600 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar /PVC insulated copper cable control wiring duly mounted on PCC foundation with suitable size of bolts, nuts & wahsers and connecting all I/C & O/G existing cables. Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and lugs to accommodate and includingthe following :- |
| 49 | INCOMING :-(a) Aluminium busbar 600 Amps rated capacity-04 Nos.(b) 400A 4P 50 KA MCCB with O/L, S/C adjustable Thermal & adjustable Magnetic Release-02 Nos(c) Spreader Link -02 Sets(d) Manual Changeover Switches,I-O-IIoperation supplied with bridging bars,extended shaft and IP-65 protection with pistol type handle of rating 400 Amps 4 pole fixed in open execution .Make : ABB Cat No OT200E04CP/Havells/Legrand - - 01 No |
| 50 | OUTGOING :-(a) MCCB 320 Amps, 4 pole,415 volt 50 kAwith O/L, S/C adjustable Thermal & adjustable Magnetic Release-01Nos(b) MCCB 250 Amps, 4 pole,415 volt 36 kAwith O/L, S/C adjustable Thermal & adjustable Magnetic Release-01 Nos(c) MCCB 160 Amps, 4 pole,415 volt 25 kAwith O/L, S/C adjustable Thermal & adjustable Magnetic Release-02 Nos(d) Spreader Link -04 Sets(e) LED multifunction meter with CT\"s -01 No(f) MCB 6 Amps, 415 Volt, \"B\" curve -03 Nos(g) MCB TPN 63 Amps, 415 Volt, \"B\" curve -03 Nos(h) Indication lamp Neon/ LED type (set of three) - 01 Set(j) Danger Notice plate - 01 No.(k) Panel control wiring with 16 sqmm s/c copper wire complete- 01 Job. |
| 51 | S&F Prepainted galvalume aluminium zink coating GI based corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering /cladding to wall fixed with self tapping screws as specified and directed. |
| 52 | S&F Prepainted galvalume aluminium zink coating GI basedplain steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering /cladding to wall fixed with self tapping screws as specified. |
| 53 | S&F Roof truss (framed) trussed, purlins,crane gantires of steel work in tubular trussesincluding special shaped washer etc. complete using ERW or induction butt welded tubesconfirming to IS 1161-1998 grade St-240 including one shop coat of zink chromate primer paint includingpreparation of surface all as directed by Engr in Charge. |
| 54 | M&L preparing new steel surfaces of any description, not otherwise describe over 10cm width or girth and applyingtwo coats of synthetic enamel paint over red oxide all as specified. |
| 55 | Supply, laying and testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable(heavy duty) with stranded alum conductor 11000 volts grade of size 3 core 95 Sqmm incl taking down old unsv complete all as specified & as directed. |
| 56 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core incl taking down old unsv complete all as specified & as directed. |
| 57 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core incl taking down old unsv complete all as specified & as directed. |
| 58 | Supply and fixing of cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95sqmm complete all as specified and as directed. |
| 59 | Dismantling of steel poles/struts any size embedded in concrete including demolition of concrete, etc and removing unserviceable materials from site of work complete all as directed by Engr-in-charge. |
| 60 | Supply, transportation, fixing and erection of steel tubular sewaged pole 9 mtr long complete with MS base plate ,finial taper plug nut bolts,screws as specified type 410 SP-31 as per relevant IS specification including two coats of aluminium paint over a coat of red oxide primerand including making alternate red and black strips 30 cm height (Total 5 Nos ) and removing the old U/S one complete all as specified and directed.Note :- (Excavation and PCC will be measured and paid seprately.) |
| 61 | S&F for 32 mm dia GI tubing light grade bracket over all 1.2 mtr length bent to shape 120 degree with cutting as required and bend to shape with flat iron clamp of size 32x6 mm, 2 Nos, suitable size of nut bolts and washers completefor fixing street light fittings on electric poles/bldgs for security complete incl taking down old unsv complete all as specified and directed. |
| 62 | M&L of aluminium conductor steel reinforced (ACSR) on HT/LT poles ,stringing properly on insulators and binding with aluminium binding wire , jumpers etc complete for any size ( Mink , Dog ,Ferret ,Weasel ,Squirel of conductor.Note : - Measurement & Payment shall be made by measuring horizontaldistance between centre of two adjaacentpole and adding 3% extra for sag , joints and jumper etc . |
| 63 | Supply, transportation, fixing and erection of steel tubular sewaged pole 11 mtr long complete with MS base plate ,finial taper plug nut bolts,screws as specified type 410 SP-55 as per relevant IS specification including two coats of aluminium paint over a coat of red oxide primerand including making alternate red and black strips 30 cm height (Total 5 Nos ) and removing the old U/S one complete all as specified and directed.(Excavation and PCC will be measured and paid seprately.) |
| 64 | Supplyfabricate , fixing structural mild steel RS joist , channelangle iron, flat iron and brackets etc for fabrication of cross arms, bracing supports clamps including D clamps, eye hook and back plate etc fabricated from structural steel section includingnuts , bolts, washers, welding (cold and hot ) drilling holes for bolts, bend to any shape or size as indicated and directed , inclusive of one primer coat and two coats of aluminium paint after preparation of surfaces complete all as specified and directed . |
| 65 | Supply and fixingmild steel galvanised stay assembly set complete comprising of 20 mm dia, 400mm long stay bow, 2150mm long stay rod 20mm dia,300mm x 300mm x 6mm stay plate, thimble, all as shown in electrical plate No.1 of MES Schedule part-I 2010 complete all as directed. |
| 66 | S&F galvanised stay strand 7/3.15 mm for stay of poles complete . |
| 67 | M&L for loop porcelain ,vitreous white , brown or greeninsulator with over all dimension of 90 mm x 140 mm ,clearence of whole 25.5 mm complete all as specifeid and as directed. . |
| 68 | M& Lfor two-in-series\" assembly for tension with tension clamps for conductors Disc type insulator, porcelain, vitreous, white, brown or green insulator ( Single disc assembly )of size145 mm height, 255 mm dia ball socket type forworking pressure 11 kvvolts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nutcomplete all as specified. |
| 69 | Supply and fix in cable route indicator for HT UG cable made out of CI plate of size 200mm dia x 6mm thick marked \"HT UG CABLE MES\" connected with MS angle Iron of size 1200mm length 50X6MM with GI nut, bolt and washer MS angle grouted in PCC block 1:3:6 type C1 using 20mm graded stone aggrgeate of size 500 x600x400 mm including excavation and earth workand painting to steel surfaces with two coats synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed. |
| 70 | Supply and fixing in repair of cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95sqmm incl taking down old unsv complete all as specified and as directed. |
| 71 | Supply and fixing in repair of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm incl taking down old unsv complete all as specified and as directed. |
| 72 | Supply and fix HT joint box 400 A of size 1500(h) x 1500(w) x 800 (d) mm sheet thickness 3.15 mm, having stand of MS angle of size 50x50x6mm and length 600mm, 400 Amp HT bus bar and insulator, poeder coated paint after 8 tank treatment process complete all as specified and directed. |
| 73 | M&L for Earthing complete with galvanized steel earth plate electrode 60cm x 60cmx 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the earth plate not less than 1.5 meter below normal ground level connected to galvanized iron strip 32 x 6mm as earthing lead by means of bolt and nut, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 5 of MES Schedule part I with and including excavation & earth work in any type of soil, providing charcoal dust and common salt upto 15 cm above top edge of earth plate, construction of PCC pit in cement concrete 1:3:6 type C-1 with 40 mm thick RCC 1:2:4 type B-1 reinforced with 8 mm dia MS deformed bars @ 100mm center to center both ways watering arrangement with funnel and wire mesh and watering pipe of 20mm dia GI light grade and 40mm dia light grade pipe for earth lead protection and testing on completion incl taking down old unsv complete all as specified and directed. |
| 74 | M & L for plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation of pole / strut etc including necessary form work all as specified and directed by Engineer-in-Charge. |
| 75 | M&L Plain cement concrete 1:2:4, type B-1( using 20mm graded crushed stone aggregate ) as in lintels upto 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, coping, bed plates and the like including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified. |
| 76 | Supply and fixing in repair of GI tubing light grade 100mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor /wallincl taking down old unsv complete all as specified and directed . |
| 77 | Supply and fixing in repair of GI tubing light grade 40mm dia for protection of cable on pole , under road crossing or across drain , along electric pole or floor /wallcomplete all as specified and directed . |
| 78 | M & L for Horizontal boring under the road for passing DI pipe below n.exc.1.5 m depth from the road surface and dia of hole not exc. 200 mm, without damaging the existing road, getting out and disposal of soil to a distance not exceeding 50 m complete all as specified and directed. |
| 79 | PCC work for reinforcement support to pipe laid, cement concrete in foundation, feeling and mast conccrete with type C2 1:3:6 with 20mm aggregate including use and waste of form works.. |
| 80 | M&L for Centrifugally Cast (Spun) Ductile Iron pressure pipe, class K-7 of 150 mm bore(as per IS 9523/2000, PN 10) of any length with Socket & Spigot confirming to IS: 8329/2000 (Latest amendment) ISI marked, in standard length with cement mortar lining inside the pipes with outside Zinc coating with finished layer of black bitumen/ blue epoxy synthetic resin laid in trenches and testing complete includingtitan joint gasket suitable for 200mm bore DI pipe all as specified and as directed by the Engr-in-Charge.Note:- For DI pipe fitting and accessaries will be measuredand paid saparately under revent items. |
| 81 | M&L for Centrifugally Cast (Spun) Ductile Iron pressure pipe, class K-7 of 200 mm bore(as per IS 9523/2000, PN 10) of any length with Socket & Spigot confirming to IS: 8329/2000 (Latest amendment) ISI marked, in standard length with cement mortar lining inside the pipes with outside Zinc coating with finished layer of black bitumen/ blue epoxy synthetic resin laid in trenches and testing complete includingtitan joint gasket suitable for 200mm bore DI pipe all as specified and as directed by the Engr-in-Charge.Note:- For DI pipe fitting and accessaries will be measuredand paid saparately under revent items. |
| 82 | S&F in repair 200 mm bore and 3 mtr long DI pipe both ends flangedand includiing all jointing material such as nut,bolts,washers,rubbers gaskets etc complete all as specified and directed |
| 83 | Cast iron air release valve with double orifice 200 mm bore suitable for installation in 200 mm dia CI/DI pipe line including nuts, bolts and gasket joint all as required complete, conforming to IS 14845/2000 complete all as specified and as directed. |
| 84 | M & L for Cutting of CI/DI pipe in position, including jointing socket etc. completewith necessary tools and plants of size 200/300mm bore all as specifeid and as directed. |
| 85 | S & F Sluice valve 150 mm bore with both end flanged with iron wheel handle for clockwise closing brass spindle heavy duty PN-1.6 class. Conforming to IS-14846/2000 including gasket joint nut, bolts & washers all as requirement of site with neccessary nut bolts washers etc complete all as specified and as directed by the Engr-in-Charge.Make : kriloskar/leader/zoloto/venus/upadhaya. |
| 86 | S & F Sluice valve 200 mm bore with both end flanged with iron wheel handle for clockwise closing brass spindle heavy duty PN-1.6 class. Conforming to IS-14846/2000 including gasket joint nut, bolts & washers all as requirement of site with neccessary nut bolts washers etc complete all as specified and as directed by the Engr-in-Charge.Make : kriloskar/leader/zoloto/venus/upadhaya. |
| 87 | M&L for CI/DI fitting any size for spigot and socketed pipes, such as bends tappings any type, Tee pieces single branch, T junction,double branches, Cross, Collars,caps & plugs etc. complete all as specifiedand directed. |
| 88 | M & L for construction of brick masonry valve pit of size 1200 X 1200 X 1200mm (internal dimension) one brick thick wall built in CM (1:4) on 100mm thick PCC (1:4:8) type D2 (using 40mm graded stone aggregate) as in foundation, and 15mm thick rendering in cement mortar (1:4)both externally andinternally, external plaster shall be up to 15cm below GL, providing valve pit cover made of 3.15mm thick MS sheet/plate, including provision of hinges, handle and locking arrangement including40 X 40 X 5mm angle iron frame fixed on top of valve pit by means of MS hold fast 40x5mm and 150mm long, embedded in PCC (1:2:4) type B-1 (using 20mm graded stone aggregate) including two coats of anti-corrosive paint over a coat of red oxide primer and necessary earth work in soft/loose soil complete all as specified & directed. |
| 89 | S&F Angle iron frame work with suitable size to hold the pipe during crossing of iron over bridge,with neccssary cutting and welding etc.and all as directed by Engr-in-charge. |
| 90 | Note 1:- (Applicable for all parts/items) : The bidders/contractors are advised to read tender document, all drawings & all corrigendum / amendments and general condition of contracts before entry / quoting the rates.Note 2:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail