| 1 | Note: (i) Please refer Schedule \"A\" Notes of tender documents.(ii) Unless otherwise specified, earth work and excavation shall be measured and paid separately.(iii)The Schedule \"A\" Part - IX to XIII are not estimatedby MES and the estimated rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only.(iv) In case rate of any item is not quoted by the bidder, the rate for the same item will be considered as zero and no claim in this regard at later date will be entertained. |
| 2 | LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS |
| 3 | Lump sum price worked out by the contractor for BUILDING WORKS carried forward from Pre-Priced Schedule \"A\" Part-I. |
| 4 | Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule \"A\" Part-II. |
| 5 | Lump sum price worked out by the contractor for LIGHTENING PROTECTION WORKS carried forward from Pre-Priced Schedule \"A\" Part-III. |
| 6 | Lump sum price worked out by the contractor for ROAD,PATH AND CULVERTWORKS carried forward from Pre-Priced Schedule \"A\" Part-IV. |
| 7 | Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS carried forward from Pre-Priced Schedule \"A\" Part-V. |
| 8 | Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule \"A\" Part-VI. |
| 9 | Lump sum price worked out by the contractor for AREA DRAINAGE WORKS carried forward from Pre-Priced Schedule \"A\" Part-VII. |
| 10 | Lump sum price worked out by the contractor for SITE CLEARANCE & EARTHWORKS carried forward from Pre-Priced Schedule \"A\" Part-VIII. |
| 11 | INTERNAL ELECTRIFICATION WORKS (SCHEDULE \"A\" PART-IX) |
| 12 | S & F in replacement sheet metal enclosures distribution boards, double door three phase 415 volts 4 ways vertical TPN DB for comprisingthree phase four wire copper strip bus bar of appropriate capacitycomplete all as specified and directed and comprising of the following:-(a) MCCB 3 POLE 125 AMPS AC415 VOLTS16 KA=01 Noas incoming and 02 nos. MCB TPN 63 Amps 10kA, Isolator TPN 40 Amp, MCB SPN 40 to 63 Amp 240V 10 kA. Note :-(i) The DB shall be VTPN. The DB shall be flush fixed ,and making good the disturbed surface matching with existing specifications shall be part of job at no extra cost.(ii) Connection of the MCCBs/ MCBs with cableshall be made through appropriate size pin /bottle type thimble -properly crimped.(iii)All the vacant holes of the DB shall be provided with blank plates of appropriate size. (iv) Double continuous earth wire shall be provided for each three phase DB from earthing mains dolly (v) MCCB\"s andMCB\"s should have a same make as of DB. |
| 13 | S & Fhighbay luminaire of LED light 70 watt, at any height in hangers/work shop closed version with energy saving environment friendly and aluminium alloy pressure die cast housing with epoxy powder coated LED IP 65 luminaire with high power LED as light source complete and with in built surge voltage protection of 10 KV and with covered tempered protective toughened glass including taking down old light fitting complete all as specified and directed. Make:- Cat Part No Iliosbayplushbp70Wled857Sp90Dtopc of Havells or equivalent of Makes as specified in tender documents. |
| 14 | EOT CRANE WORKS (SCHEDULE \"A\" PART-X) |
| 15 | Supply, installation and testing of Double Grider (EOT) crane, box type having lift 6.0 Mtr & Span 16 mtr conforming to IS 807/3177 ,II Indoor type and comprising of the following complete all as specified and directed.(a) Main host safe working load 02 Tons (2000 Kgs)(b) Span 16 Mtr and longitudinal travel-25 mtr(c)Height of lift -6.0 Mtr(d) Operation:-Floor operation from pendant push button control station(e) Main hosting speed with AC drive (3 to 3.5 Mtr/Minute)(f) Cross travel speen (10 Mtr/Minute) (g) Long travel speed (10 Mtr/Minute)(h) main host motor rating:03HP or higher as recommended by manufacturer (j) Cross travel motor rating: 0.5 to 1 HP or higheras recommended by manufacturer(k) Long travel motor rating:twin drive 0.5 to 1 HP (2 Nos) each with gear box Note for (j) & (k) : Make of Crane motor:Kirloskar/Crompton and Greaves or equivalent |
| 16 | (i) Main hoist wire rope dia:12mm(m) Main hoist Nos of fallas : Two (n) Wire rope construction : (6X36)8mmx 4 falls ( Make Usha Martin) ISI marked(o) Main Grider-02 Nos (Box type) of size as per design of manufacturer (p) Over load capacity:25%(q) Rail size: 40mm SA BAR(r) Wheel: MS with bronze coating on tread Note:-(i) The double girder crance shall be suitable for working on 415 volts,3PH,50HZ AC supply and shall be complete with following of crane of capacity 02 ton as specified above(a) Main frame(b) Bridge/Box Grider(c) End carriages (d) Trolly with frame(e) CRAB |
| 17 | (f) Buffers (g) Gear with Gear boxes (h) Shafts(j) Rope Drum(k) Rope sheaves (l) Wire ropes (m) Wheelsn) Lifting hook(o) Brakes Motors, Limit Switches,control panels, pendant push button station, Micro speed arrangements wiring etc all as per standard specification of manufacturer (p) 02 Nos of service platforms all as per standard specification of manufacturer (q) Make of contactors : L&T/siemens or equivalent as specified in tender. |
| 18 | Notes (ii)(a) Line diagram for the crane shall got approved from AO before installation (b) Any minor modifications required for sucesful operation of crane shall be carried out by contractor within over all cost quoted.(c)Trial run of crane shall be carried out for a period of one month.Only on sucessful completion of trail completion shall be issued by GE (d) Make of crane (i) M/S Hecules Ltd, (ii) M/S Mukund Iron & steel (iii) M/S TIB Udhyog (iv) M/S Rock well Hoisto Cranes Pvt Ltd (v) M/S NRS TIIB & Co (e) For Long travel:- Main grider with bracket and 12mm thick plate and 50mm sqbar rail shallin scope of supply of crane manufacturer (f) Copper coductor cable of size 4 sqmm 4 core or as recommended by the manufacturer from outdoor type feeder pillar box installed outside the sheeds to control panel of individual crane shall be supplied with in overall cost qoted (g) Testing of Crane shall be out in pesence of Rep of Accepting Officer as per IS standards, necessay load is to be arranged by contractor at site. (h) Pre dispatch testing/inspection shall be carried out in premises of manufacturers site in presence of the Rep of Accepting Officer. |
| 19 | Note (iii) MAKE OF STANDARD BOUGHT OUT ITEMS AS UNDER:- a) MOTORS: CROMPTION/KIRLOSKAR/BBL/SIMENS/LHP b) BRAKES: SPEED-O-CONTROL/PETHE/BCH/JAISON\"S c) LIMIT SWITCH : SPEED-O-CONTROL/PETHE/BCH/JAISON\"S d) PENDENT CONTROL: SPEED-O-CONTROL/JAISON\"S/SCHNYDERe) CONTACTORS: L&T/BCH/SCHNYDER/T.C.FRANCE/L.Sf) OVER LOAD RELLAY l L&T/BCH/SCHNYDER/T.C/L.S. g) HRC FUSES: L&T/BCH/EE/GE/ESSEN/SCIh)CABLE:PLAZA/FINOLEX/POLYCAB/ALCON/SWADESHI. J)WIRE ROPE:USHA MARTIN/FORT WILLIAM/MAHADEV k) WIRE ROPE DRUM: JAISON\"S l) VF DRIVE: ABB/SIEMENS/L&T/BCH/DELTA/BOSCHm) WHEELS: JAISON\"S(n) GEAR BOX : JAISON\"So) COUPLING:JAISON\"S/ARISTOFLEX/CRYSTAL p) BEARINGS: SKF/TATA TIMKEN/FAG/ROMANIA/F.K/N.T.N (q) HOIST:JAISO |
| 20 | EXTERNAL WATER SUPPLYWORKS (SCHEDULE \"A\" PART-XI) |
| 21 | M&L for Construction of RR masonary staging for over head tank 2.4mtr from ground level PCC 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete and brick work with sub class \"B\" bricks straight or curved on plan exc 6m mean radius in CM 1:4 with plastering and rendering 15 mm thick on fair faces of brick work or concrete surface in CM 1:4 including applying three coat of white wash includingpreparation of new surface of wall complete all as specified and directed. |
| 22 | EXTERNAL ELECTRIFICATION WORKS (SCHEDULE \"A\" PART-XII) |
| 23 | Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified),LT Panel, LT Panel Outdoor type, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of200 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring not less then 4 Sqmm with PVC insulated,strandedcopper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:- |
| 24 | (a) Incoming(i) MCCB 4 pole 415 volts100 Amps with 25kA-01No (ii)Voltmeter 0-500 volts,square,144 mm,digital type, - 01 No(iii) Ammeter size 144 mm,square dial, digital type, - 01 No(iv) LED Indicating lamps : 01 set of three(v) Current & Potential Transformer as per manufacturer design : 01 Nos(b) Outgoing(i) MCCB 4 pole 415 volts100 Amps with 16 kA-01Nos(ii) MCCB 4 pole 415 volts63 Amps with 16 kA-01NosNote:- Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level. |
| 25 | Supply and fixing ofstreet light control box made of Engineering plastic one piece moulding control box with locking arrangmentmade out ofHDPE and FI clamp 25 x 3mm complete ofdimensions in mm+/-10%(333x233x120) including MCB SP upto 6 Amp 240 Volts complete with 02 Nos aluminium busbar or terminal two nos (Phase and Neutral with colour coding) of rating 63 amps for single phaseand neutral on porcelain based insulators complete all as specified and directed.. |
| 26 | DG SET WORKS (SCHEDULE \"A\" PART-XIII) |
| 27 | Supply, installation, commissioning and testing of 82.5 KVA Liquid (Water) Cooled silent DG Set as per latest CPCB norms,comprising of Liquid Cooled Diesel Engine Modeldeveloping minimum 102 BHP @1500 RPM82.5 KVA Alternator rated at Three Phase, 415 Volts, 50 Hz, 0.8 PF @ 1500 RPM both mounted and aligned on a common MS Base frame complete with MS fuel Tank, Manual Control Panel, Residential exhaust silencer, AVM pads fitted on baseframe, 12 Volts Battery , battery leads, 1st fill of Lube oil all housed in sound proof acoustic enclosure protected with asbestos rope independently supported from engine to outside power house upto 1 mtr, AVM pads foundations as per manufacure design battery start with suitable size of cable for connecting upto panel board . DG Set should be capableof operating in temperture range (-25° C to + 35°C) fitted with Cold starting kit with and including the following . |
| 28 | (A) Prime moverVertical diesel engine of suitable capacity water cooled closed circuitas per BS-649 or IS-10002 direct injection type turbo charged electric starting system having rated speed 1500 RPM. The DG Set shall be capable of running 24hrs continuously with 10% over loading for one hrs continuously in every 12 hrs as per BS -649. Engine shall be eqippedwith all standrd fitting and mounted on common base frame with following fittings.(a) RPM cum hour meter(b) Barttery charging Ammeter( c) ignition key and starting with push button switch(d)Lubricating Oil pressure gauge (e) Electronicgovernor controlling Oil temo gauge (g) 12/24 Volts starting equipment comprising of the following fittings (i)12/24 V Battery (ii)Battery charging alternator (iii) Self starting of suitable capacity (iv) Battery leads of copper cable with brass thimbles and terminals. (v)starting gear engine. |
| 29 | (B) AlternatorAlternator rating 82.5 KVA,3 phase,4wire,415 Volts 50C/s supplyDeratedat site condition i.e 1800 mtr above MSL 0.8 Pfrunning @ 1500 RPM self excited ,self regulated, mounted on strong fabricated steel frame,suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be confirming to BS-2613 or IS -4722.(C) Control panel Alternatorcontrol panelto be canopy mounted with internal copper wiring with copper conductor cable of suitable size for 82.5 KVA alternator 415V,3 phase,4 wire 50Hz fabricated out 1.5mm thick MSsheet painted externally with two coats of synthetic enamel paint over acoat of primer including following accessories (a) Digital Amp, volt, Frequency, KW, KWH, Meters in the Engine controller with Scrollable selector switch(b) CTs of suitable range -01 set (c)MCCB -01 No ( For incoming )as recommended by manufacture (d) Set of Aluminum bus bar suitable capacity (e) Set indicating lamps (f) Set of instumental fuses. |
| 30 | (D) Other fittings (i)Battery charger having electric circuitconsisting of triodes , capacitor and resistances etc. The battery charger should be able to charge the battery at all times whenever the electric supply given to battery charger through control panel or electric power point.(ii) In built Fuel tank of suitable capacity as per manufacturers instructions capable for12 hrs running of DG Set inside the canopy basewith all connecting pipes upto fuel pump and including oil level indicating gauge drain air vent plug etc.(Note : The rates of this items including foundation as per manufacturer design the commissioning & testing complete (POL for DG Set testing will be issued by MES) |
| 31 | Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified),LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars ofAmps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with aprons for cable entry,with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys,internal wiring 2.5 Sqmm with PVC insulated,solid copper conductor, FRLS cables, IS-694marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:- |
| 32 | (a) Incoming(i) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 25KA rupturing capacity complete with microprocessor based OL protection - 01 No (ii)Voltmeter 0-500 volts,square,144 mm,digital type, - 01 No(iii) Ammeter size 144 mm,square dial, digital type, - 01 No(iv) LED Indicating lamps : 01 set of three(v) Change over 100A 4 Pole : 01 Nos(vi) Current & Potential Transformer as per manufacturer design : 01 Nos(b) Outgoing(i) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 25KA rupturing capacity complete with microprocessor based OL protection - 01 Nos.(c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B\", old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cmabove the nearest road level. |