| 1 | Supply and fixingsteel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-55 ( 11 meter long) complete, Including disconnectingand taking outold damage any type pole all as directed . Make - National Tubing co/ Indian tube co ltd / Bharat Conduit & steel works kanpur .Note- Earth work and PCC shall be measured and paid separately as these respectively. |
| 2 | Supply and fixingmild steel galvanised stay assembly set complete comprising of 14mm dia, 400mm long stay bow, 2150mm long stay rod 20mm dia,300mm x 300mm x 6mm stay plate, thimble, loop insulator large size all as shown in electrical plate No.1 of MES Schedule part-I 2010 complete including dismantling and taking out old damaged stay complete all as directed. Note :- PCC , earth work and Insulators etc shall be measured and paid separately. |
| 3 | Supply and fix gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level Vertical type for rating upto 400 Amps, 11000 volts complete with GI operating pipe of heavy duty including taking down U/S one . Make - BHEL / JAIPURIA / RASHTRIYA / MEI . |
| 4 | Supply and fixing drop out fuse assembly complete set with Insulator-02 Nos and connected accessories for 11000 Voltsgrade of 400 Amps capacityincluding taking down U/S DO fuse assmbly .Make - BHEL / JAIPURIA / RASHTRIYA / MEI . |
| 5 | Supply and fix gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level horizontal type /Vertical type in double stack type for rating upto 400 Amps, 33000 volts complete with GI operating pipe of heavy duty including taking down unserviceable one complete all as specified and as directed. |
| 6 | Taking down and repairing/overhauling ofair break gang operated switch with DO fuse unit 11 KV/ 33 KV rating 200 Amp/400 Amp capacity triple pole mechanically operated mounted on insulators and steel frame installed vertically / horizontally , replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing ofelectric contacts with providingconductingjelly of contactsrefixed the same after repair including proper allienmentcomplete all as specified and as directed. (Note:- Worn out component/ insulators / ASCR shall be measured and paid separately under respective items of this schedule.) |
| 7 | Supply only Female contact or fixed contact heavy duty and high conductivemetal complete capacity 200A/400 Amp, 11 KV rated. Make - BHEL / Jaipuria/ Rashtriya/ MEI |
| 8 | Supply only Male contact or Moving contact heavy duty and high conductive metal complete capacity 200A/400Amp 11 KVMake Rastriya/Jaipuria.Make - BHEL / Jaipuria/ Rashtriya/ MEI. |
| 9 | Supply only Tinned copper flexible jumper of capacity 200A/400A suitable for 11KV rated GOD.Make - BHEL / Jaipuria/ Rashtriya/ MEI |
| 10 | Supply only Fixed top contact & Fixed bottom contact 11 KV 400 Amp for DO fuse unit.Make - BHEL / Jaipuria/ Rashtriya/ MEI |
| 11 | Supply only Fiber glass tube with metalic fittings both ends suitable for DO fuse 11KV. Make - BHEL / Jaipuria/ Rashtriya/ MEI. |
| 12 | Supply only mild steel jumper carrier suitable for 11 KV GOD as per sample. |
| 13 | Supply only back connector plate suitable for 11 KV GOD as per sample. |
| 14 | Supply only post insulator suitable for 11 KV GOD as per sample. |
| 15 | Supply only Female contact or fixed contact heavy duty and high conductivemetal complete capacity 400 Amp suitbale for 33 KV rated horizontal GOD. Make - BHEL / Jaipuria/ Rashtriya/ MEI |
| 16 | Supply only Male contact or Moving contact heavy duty and high conductive metal complete capacity 400 Amp suitbale for 33 KV rated horizontal GOD. Make - BHEL / Jaipuria/ Rashtriya/ MEI. |
| 17 | Supply only post insulator suitable for 33 KV GOD as per sample. |
| 18 | Supply only Tinned copper flexible jumper of capacity 200A/400A suitable for 33 KV |
| 19 | Supply only Fixed top contact & Fixed bottom contact 33KV 400 Amp for DO fuse unit.Make Rastriya/Jaipuria |
| 20 | Supply only Fiber glass tube with metalic fittings both ends suitable for DO fuse 33 KVMake Rastriya/Jaipuria |
| 21 | Supply only mild steel jumper carrier suitable for 33 KV GOD as per sample. |
| 22 | Supply only back connector plate for 33 KV GOD as per sample. |
| 23 | Supply & fix lightening arrestor linear resistance type distribution class discharge capacity 65 kilo ampsuitable for 11 KV system pole mounting type conforming to IS - 3070 Part-I including taking down existing unserviceable one complete all as specified and as directed. |
| 24 | Supply and fixing Danger notice plateof 1.6mm thick mild steel sheet vitreous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp for HT size 25 X 20 Cm and taking out of us one complete all as specified. |
| 25 | M& LPin type, porcelain, vitreous, white, brown or green insulator, 150 mm height, 150 mm dia for 11000 volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut andand taking out of unsv onecomplete all as specified.Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL . |
| 26 | M& Lfor Disc type insulator, porcelain, vitreous, white, brown or green insulator ( Single disc assembly )of size145 mm height, 255 mm dia ball socket type forworking pressure 11 kvvolts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut andtaking out of U/S onecomplete all as specified.Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL . |
| 27 | M& L loop type, porcelain, vitreous, white, brown or green insulator large type 140 mm , clearence of hole 25.5 mm for 11000 volts grade includingout of U/S onecomplete all as specified. Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL . |
| 28 | M & L for restraining ofHT /LT over head linesingle ACSR conductorcomprising of any size of conductor aluminium/copper/GI after opening binding wire from insulators and replace binding wire and achieved permissible sag limit of over head line conductor complete all as directed and specified. |
| 29 | S & F sealed lead acid battery for constant voltage charge of capacity 12V , 7Ah including taking out the unserviceable battery complete all as speciifed and as directed. |
| 30 | S & Flithium battery for RMUER 14250 ,3.6V ,1/2AA ,1200mAh including taking out unserviceable battery complete. |
| 31 | Repair / Servicing / maintenance of transformer 11 / .433 KV indoor / outdoor type , plinth / pole mounted type including the following work services :-(a) Disconnecting transformer from electric system and providing electric power to user from alternative arrangement including taking out from existing position . (b) Decanning oftransformer oil , opening top cover , disconnecting of all internal connections , lifting and taking out ofcore assemble , LT / HT bushes, Tapchanger etc ,cleaning and inspection of core and winding , segrigetion ofserviceable and unserviceable items , removing of sludge and cleaning tank and cooling pipes / fins /tankswith pressure water and drying the tank complete.(c)Replacinig unserviceableLT / HT bushing by replacing rubber / cork oil seals and damage terminal rod &replacement of Transformercover gasket of rubber cork sheet. (d) Re installation of TFR including reassembling of core / winding assebly complete including replacement of unsv parts , repair the defective parts and tighting of all loose / sparks wire / nut bolts etc and refixing theto the existing position , connecting with HT/LT cables and earthing strip and testing complete including necessary Transportation ( If required ) to the work shop and backand including Dehyderation and refilling of existing ornew transformer oil of required quantity .NOTE :- (i) Dehydration of oil and new Transformeroil shall be measured seperately . (ii) Transportation of TFR measuredand paid seperately . (iii) HT & LT Busing, Tap Changer will bemeasured & Paid separataly. (iv) In case HV / LV Windingfound damages then Contactor shall be made serviceable with new winding and the same will be measured and paid seperately. (v) The rate ofcork sheet & Packing Material for following cap of TFR are included in coated rate of transformer capacity 100 to 160KVA . |
| 32 | ……..Ditto…as per item no 31 But capacity 200 to 300 KVA . |
| 33 | ……..Ditto...as per item no 31But capacity 400 to 500 KVA . |
| 34 | Supply onlyfor incorporated to the repair of transformer HT bushingporcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for outdoor type Transformer of capacity 100 to 160KVA . |
| 35 | ……..Ditto…as per item no 34 But capacity 200 to 300 KVA . |
| 36 | ……..Ditto..as per item no 34 But capacity 400 to 500 KVA . |
| 37 | Supply onlyfor incorporated to the repair of transformer LT bushingporcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for indoor/outdoor type Transformer of capacity 100 to 160KVA . |
| 38 | ……..Ditto…as per item no 37 But capacity 200 to 300 KVA . |
| 39 | ……..Ditto…as per item no 37 But capacity 400 to 500 KVA . |
| 40 | Supply onlyfor incorporated to the repair of transformer Off load Tapchanger switch of existing model / type of Transformer of capacity 100 to 160 KVA . |
| 41 | Supply onlyfor incorporated to the repair of transformer Off load Tap changer switch of existing model / type of Transformer of capacity 200 to 300 KVA . |
| 42 | Supply onlyfor incorporated to the repair of transformer Off load changer switch of existing model / type of Transformer of capacity 400 to 500 KVA . |
| 43 | M&L for Dehydration of transformers oil minimum three cycles to achieve dielectric strength up to 50 KV in 2.5 mm gap electrode including toping up of Transformer oil if required at site .Note: (i) Dehydration of transformer oil shall be carried out at site and contractor shall be taken the testing result before and after dehydration of oil and shown to the EIC at site and maintain necessary documentsfor record .(ii) Dehydration Machine with all T&P & Transformeroiltesting machinefor dehydration of Transformer oil and necessary transportation for the machines is arrange by contractor. (iii) Oil required for topping up the transformer will be measured & paid separatly. |
| 44 | Supply and topup of transformer oil EHV as per IS 335 of 1993 Part II with dielectric strength up to 50 KV in 2.5 mm gap electrode complete and including necessary transportation complete all as specified and as directed. |
| 45 | Supply and replace of silica gel cristal complete all as specified and as directed. |
| 46 | Supply and fixing in repalcement of heavy duty breather assembly with Silica jel cristal complete for Transformer upto 300 KVA complete all as specified and as directed. |
| 47 | S & F in replacement Winding tempreture gauge for Transformer 0 - 150 C complete all as specified and as directed. |
| 48 | M & L for cleaning , scraping out old rubbed paint / rust& Painting of transformercompleteof capacity up to 63 to 250 KVA 11/.433 KV outdoor / Indoor type with one coat ofspray painting with synthetic enamelled gray paint (first grade)by sprey painting machine ontransformer & Making SM NO on surface of transformer complete all as specified and directed. |
| 49 | Description same all as per item No 48 but capacity 300 to 500 KVA 11/0.433 V complete all as specified and directed. |
| 50 | Supply onlyLead acid battery 2 volt 200 AH TOBULAR (TBS) Make :- Exide/ Express/Amco |
| 51 | M & L in repair forearthing to OH/Sub stn with galvanised steel earth plate electrode60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI wire 4 mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead wireprotected by GI pipe 15mm dia light grade and connected to earth test point includingexcavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed. Note : Main earth lead beyond 7.5 meter shall measured and paid saperatly. |
| 52 | Description all as per above item no 51 but main earth lead 32 x 6 mm galvanised iron strip complete all as specified and directed. |
| 53 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor terminationheat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 54 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor terminationheat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm including testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 55 | M&L Cable jointing kit for 33 KV (Earthed) grade cable for outdoor terminationheat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm including testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 56 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor terminationheat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 95 sqmmincluding testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 57 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor terminationheat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 120sqmm including testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 58 | Supply and fix cable jointing kit for 11 KV grade cable for straight throughoutdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 coreXLPE armoured Al conductor cable of size 50 to 95sqmm including testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 59 | Supply and fix cable jointing kit for 11 KV grade cable for straight throughoutdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 coreXLPE armoured Al conductor cable of size 120 to 185sqmm including testing complete all as specified and as directed. Make - Denson /Raychem / 3M |
| 60 | Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11 KV grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole including laying of cable cover complete all as specified & as directed including taking out of old unserviceable cable. Make: Havells/Gloster/Polycab/KEI. Note- Cable Cover should be paid seperately |
| 61 | Excavating in trenchesnot exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cables & foundation of poles ,stay assembly and getting out in any type of soil complete all as specified and directed . |
| 62 | Excavating in trenchesexceeding 1.5 m wide and not exceeding 3 m depth and not less than 1.5 min depth for laying of cables & foundation of poles , stay assembly and getting out in any type of soil complete all as specified and directed . |
| 63 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete. |
| 64 | Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete. |
| 65 | Material and labour for sand cushioning to under ground cables ( 8 cm deep before laying of cable and 15 cm deep over the cable ) & punning gently complete all as specified and directed . |
| 66 | M&L for laying un-reinforced precast concrete cable cover, class HV , type 1 with ,size 300 mmX180mmX 40mm complete all as directed by Engineer-in-Charge. |
| 67 | M/L in repairs for cement concrete in foundation (1:4;8) type D2 using 40 mm graded broken stone aggregate for base of foundation complete as specified |
| 68 | M/L in repairsfor cement concrete in foundation (1:3;6) type C2 using 40 mm graded broken stone aggregate including form work complete as specified |
| 69 | M/L in repairsforPCC (1:2:4) type B1 (using 20mm graded stone aggregate) as in coping including necessary formworkcomplete all as specified and as directed. |
| 70 | Supply and fixingof GI tubing, light grade, 100 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repairs complete.Make - TATA / ZINDAL / Bansal . |
| 71 | Material and labourHT Cable rout indicator made out of PCC Post of 1:2:4of size not less than20 x 15 cm andone meter heightwith makingembossing the following letters of size 100 mm in the PCC Post\" HT CABLE \" including necessary excavation and PCC 1:2:4 (30 X 30 x 30 CM ) for embeding in the ground. |
| 72 | M&L forSynthetic insulating rubber mat suitable for 33 KV HT installationof size2 m x 1m x 25 mm completeall as specified and directed by EIC. |
| 73 | Supply and fixing digital over current protection relay ( 3 OC + 1 EF & INST. Protection )with micro processor based complete all as specified and directed . Make - CG , Cat No - CGI 14 N/C OR equivalent Make of L & T / Siemence. NOTE : - Relay is suitable as per existing type / Make for 11 / 33 KV VCB\"S / Control Panel . |
| 74 | Repair / Servicing / maintenance of Current/ Potential transformer (CT and PT) 33KV outdoor type, steel structure mounted type of any capacity including disconnecting of CT/PT from electric system including taking out from existing position, decanning of transformer oil, opening of cover complete checking of all connection and including replacing of old transformer oil and all gaskets, complete new painting as per existing and providing greasing/lubrication to other jointing/rusting components, reconditioning electric connections, replacinig unserviceable HT bushing, rubber / cork oil seals and damage spindle as required complete all as specified and as ditected. |
| 75 | Servicing / Calibration to 33 KV HT VCB panel and PCOB for Vaccum interruptor complete including the following : switching off electric supply, Checking of mechanical system for proper functioning, replacing closing buffer, triping buffer (VMX type), V I connection gap check, motor coil resistance check, closing coil resistance check, spring charging cut off switch check, aux switch check, NO-NC states check, trip coil resistance check, testing details, timing test, oil value test, breaker timing test, connector resistance test, IR value test, HV test, mechanical and electrical mechanism check, counter reading check, shock observer check, pre close/ post close circuit check, test and service position limit switch check, breaker drive screw operation check, trip coil assemble operation check, mechanical latch . Cleaning & servicing the fixed/ moving contact & blowing out dust and applying the proper lubrication/ greasing and reassembling the VCB including connection to HT panel complete to be replaced where reqd all as directed by EIC. Note:- (1) Maitenance of all HT VCB will be carried out as per maintenance schedule (2) Testing of above job to be carried out by engineers of authorised dealer/service centre. (3) Replacing new items shall be measured and paid separately as supply only |
| 76 | Servicing / Calibration to 11KV HT VCB/RMU panel complete including the following (a) Taking out 11KV HT VCB of 630 Amps rating trolley from HT Panel after switching off electric supply.Checking of mechanical system for proper functioning of upward/downward movement of HT VCB trolley including replacing closing buffer, triping buffer (VMX type), VI connection gap check, motor coil resistance check, closing coil resistance check, spring charging cut off switch check, aux switch check, NO-NC states check, trip coil resistance check, testing details, timing test, oil value test, breaker timing test, connector resistance test, IR value test, HV test, mechanical and electrical mechanism check, counter reading check, shock observer check, pre close/ post close circuit check, test and service position limit switch check, breaker drive screw operation check, trip coil assemble operation check, mechanical latch . Cleaning & servicing the fixed/ moving contact & blowing out dust and applying the proper lubrication/ greasing and reassembling the VCB including connection to HT panel complete to be replaced where reqd all as directed by EIC.Note:- (1) Maitenance of all HT VCB will be carried out as per maintenance schedule (2) Testing of above job to be carried out by engineers of authorised dealer/service centre. (3) Replacing new items shall be measured and paid separately as supply only. |
| 77 | Supply only shunt closing/tripping coil operated on 110 /30 volt system suitable for working of relay of HT SF6 / VCB complete all as specified and directed. |
| 78 | Supply and fixing in repairs spring charging motor suitable for fixing with 33/11 KV indoor type VCB panels complete all as specified and directed. Make - MICO/ABB/C&S/L&T. |
| 79 | Supply and fixing in repairs vaccum interputer suitable for 11 KV VCB trolly complete all as specified and directed. |
| 80 | Supply and fixing in repairs moving contacts of VCB made of copper and suitable for 11 KV VCB Trolley compete all as specified and directed. |
| 81 | Supply & fixing meter devices 3 phase digital type Amp meter 0- 120 Amp class 0.5 of size 96 mmx96 mm to match the ratio of existing CTs. Make:Conzerve Cat No DM 3258 or equivalent model of IMP/AE Bombay/Meco. |
| 82 | Supply & fixing meter devices 3 phase digital type Volt Meter 0- 12 KV class 0.5 of size 96mm x 96 mm to match the ratio of existing CTs. Make conzerve Cat No DM 3256 or equivalent model of IMP/AE Bombay/Meco. |
| 83 | Supply & fix lightening arrestor linear resistance type complete with all fitting,distribution class suitable for 33 KV system pole mounting type conforming to IS - 3070 Part-I including taking down existing unserviceable one complete all as specified and as directed. |
| 84 | Supply and fixing Pin type insulator, porcelain, vitreous, white, brown or green insulator, suitable for 33000 volts grade including taking out of unsv one complete all as specified and as directed. Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL . |
| 85 | Material and labour for spreading and leveling evenly(any thickness) 40 mm graded stone aggregated complete all as specified and directed. |
| 86 | Tracing out fault in 11KV underground cable any size with the help of fault detection machine and rectifying the same with joints as specified and directed to restore the supply complete all as specified. Note: (i). Joint kit shall be measured and paid separately. (ii)Earth work shall be measured and paid separately. However, width of trenches shall be allowed for payment as per authorized width given in SSR for each size of cable.(iii) All other necessary arrangements suitable for locating the faultsdeemed to be included in the unit rate quoted.(iv)T&P required for the entire job shallbe provided by the contractor at his own end and nothing extra shall be admissible on this account.(v) Cable required, if any shall be measured and paid for separately.(vi) Fault & location thereof shall be traced within 12 hours of intimation by the Engineer-in-Charge and shall be rectified within given time frame |
| 87 | Supply and fixing as in repairs PG clamp die cast aluminium of suitable size and for fixing clamplingACSR conductor connections for PT\"s CTs isolators all as specified |
| 88 | M&L for Shifting of the any make of transformer rating up to 500 KVAmounted onplinth/pole from existing location to new location and existing transformer vice versa,including removing and reconnections of HT/LT side, jumper / cable connection, control cable connection of both transformers including testing and commissioncomplete all as directed by Engr-in-Charge. Note:- (i) The rate quoted is deemed to be inclusive of necessary crane / vehicle charges for shifting and installation of the transformer. |
| 89 | Dismantling HT/LT pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge. |
| 90 | Supply and fix in replacement of old HT box of any size, Install, testing and commissioning of HT Junction Box size 1200x1000x1000mm, factory made, outdoor pedestal type, double door, fabricated out of 3.15mm thick CRCA sheet and angle iron! frame 50x50x6mm sloppy roof locking arrangement comprising50mm size Godrej brass pad lock with duplicate keys two earth terminal, suitable cabie gland for incoming and outgoing HT cable and protection of joint, grouting of feeder pillar box b y providing 90 cm long angle iron of size 50 x 50 x 6mm welded on all the four cornors embedded i n platform not less than 1 mtr height. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyster powder coating of flint grey shade. The panel shall having copper bus bar three stripsof minimum size 400mm x 40mm x 6mm with procelain H12 K V HT long insulator complete including taking down old one, complete all a s directed.Note: (i Quoted rate shall be deemed to include the cost of!platform a s specified i n particular specifications.(i) Joint shall be measured and paid for separately under relevant schedule item. (ii) Quoted rate shall also includes work for extension of cable loopand fixing in position all as specified |
| 91 | M&L for cleaning/Painting of 4 pole structure /2 Pole structure/single Pole structure of any type/size/length and removing existing painting by using wire brush usingwith emery paper and cleaningwith chemical agents, after cleaning the poles two coats of red oxide primer and two coats of synthetic aluminium painting satisfactorilyby Engr-in\"Chargeand Painting work carryout at any height and including marking of pole numbers as directed and safety eqpts & tools will be own arrangement and marking and colour washing of pole coping all as specified and directed of the following. |
| 92 | Two poles with cross Arms |
| 93 | Four Poles with cross Arms |
| 94 | Single HT 11mtr Pole with cross Arms |
| 95 | Material and labour for painting tothe Transformer yard fencing made out of GI wire mesh with two coats ofsynthetic enamel paint complete all as directed. |
| 96 | Supply, testing and fix in replacement HT overhead lines on 11 mtr poles with XLPE insulated AB Cable 3 core x 95 sqmm + 1 x70 sqmm massanger complete all as directed by Engg-in-Charge. |
| 97 | Anchoring Clamps with hooks suitable for all sizes of ABC cables incl old taking down |
| 98 | Tensioning Clamps suitable for all sizes of ABC cables incl old taking down |
| 99 | Supply and fixing Dead end clamps for LT/HT Cables incl old taking down |
| 100 | S&F steel work in tubular trusses including special shaped washer etc complete using ERW or induction butt welded tubes confirming to I.S. 1161-1998 |